Explanationo ]ump
Settings
Y2 JUMPER
SETTING
If the jumper
for
MISCI
is set to Y2 the MISC1
screw
terminal
on
the backplate
will
control
a
second
stage
of cooling,
Y2 OPERATION
-SECTION
134
Controt
up to two Coot
stages,
The 2nd
Stage
of heat
or cool is turned
on when:
(A) The
1st Stage
has been
on for the time
required
(step
#23,
page
13.6).
It is adjustable
from
0-60
minutes
and the default
is two minutes,
An._d
(B) The
temperature
spread
from
the setpoint
is equaI
to or greater
than:
the setpoint
plus
the deadband
(step
#24,
page
13.6), plus
the 2nd deadband
(step
#21,
page
13.5).
This
2nd
deadband
is
adjustable
from
0-10
degrees
and
the default
is two degrees
e
Cooling
eadbantl_eadband,,. I
db
f _' db_ r
ad
"-6" _
O- O" X
Cool
I st Stage
2nd Stage
Setpoi_t
turn on
turn on
ITEM PEP, ATU REJ --INCREASE