Adjusting the Deadband
MULTI-STAGE OPERATION - Controls up to three Heat and two Cool
stages.
The 2nd Stage of heat or cool is turned on when:
(A) The 1st Stage has been on for the time required (step #23,
page 13.6). It is adjustable from 0-60 minutes and the default
is two minutes.
And
(B) The temperature spread from the setpoint is equal to or greater
than: the setpoint plus the 1st stage deadband (step #20, next
page), plus the 2nd stage deadband (step #21, next page).
This 2nd stage deadband is adjustable from 0-10 degrees and
the default is two degrees.
The 3rd Stage of Heat is turned on when:
(A} The 2nd stage has been on for the time required (step #24,
page 13.6). It is adjustable from 0-60 minutes and the default
is two minutes.
And
(B} The temperature from the setpoint is equal to or greater
than: the setpoint plus the 1st stage deadband (step #20, next
page), plus the 2nd stage deadband (step #21, next page)
plus the 3rd stage deadband (step #22, next page). This 3rd
stage deadband is adjustable from 0-10 degrees and the
default is two degrees.
3rd Slage
2nd Slage
1st Slage
Heat
Cool
1st S_age
2nd Stage
lum
on
lurn
on
lurn
on
Setpoint
Setpoint
lurn
on
lurn
on
_---DECREASE--LTEMPERATUREJ--INCREASE_
The above figure assumes the minimum on time for the prior stage has
been met to allow the next stage to turn on, once the deadbands have
been exceeded.