Carrier Debonair 33CS Installation, Start-Up, And Operating Instructions Manual
Carrier Debonair 33CS Installation, Start-Up, And Operating Instructions Manual

Carrier Debonair 33CS Installation, Start-Up, And Operating Instructions Manual

Flush-mounted flatstat commercial programmable thermostat

Advertisement

CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
Select Thermostat Location . . . . . . . . . . . . . . . . . . . . . . 2
Set Clock. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Configure Advanced Setup. . . . . . . . . . . . . . . . . . . . . . . 4
Install Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Program Thermostat Schedules. . . . . . . . . . . . . . . . . . 6
Factory Defaults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Calibrate Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Check Thermostat Operation. . . . . . . . . . . . . . . . . . . . . 7
Final Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-9
Auto-Changeover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Two-Stage Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Clock Backup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Fan Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Emergency Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Electric Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Holiday Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Remote Temperature Sensor . . . . . . . . . . . . . . . . . . . . . 8
Keypad Lock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Dry Contact Switch/External Control . . . . . . . . . . . . . 8
10-Watt Resistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
IMPORTANT: Read entire instructions before starting
the installation.

SAFETY CONSIDERATIONS

Read and follow manufacturer instructions carefully. Fol-
low all local electrical codes during installation. All wiring
must conform to local and national electrical codes. Improper
wiring or installation may damage thermostat.
Recognize safety information. This is the safety alert sym-
bol
. When the safety alert symbol is present on equipment
or in the instruction manual, be alert to the potential for person-
al injury.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 111
Book 1
4
Tab
11a 13a
Commercial Programmable Thermostat
Installation, Start-Up and
Operating Instructions
Part Numbers 33CS250-FS
and 33CS220-FS
Page
Catalog No. 533-352
Printed in U.S.A.
Flush-Mounted FlatStat
Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety alert symbol.
DANGER identifies the most serious hazards which will result
in severe personal injury or death. WARNING signifies a haz-
ard which could result in personal injury or death. CAUTION
is used to identify unsafe practices which would result in minor
personal injury or property damage.

GENERAL

The commercial, 7-day, programmable thermostats are
wall-mounted, low-voltage thermostats which maintain room
temperature by controlling the operation of an HVAC (Heating,
Ventilation, and Air Conditioning) system. Separate heating
and cooling set points and auto-changeover capability allow 4
different programming time periods for energy savings.
All thermostats allow up to 4 time/temperature settings to
be programmed per 24-hour period. Each thermostat stores
programs for 7 independent days. Batteries are not required.
During power interruption the internal NEVER-LOST™
memory stores programmed schedules for an unlimited
amount of time while the clock continues to run for at least
48 hours.
The thermostat can be configured to accept several different
equipment configurations, including heat pump operation.
NOTE: The thermostat is not factory-configured for use in heat
pump applications. The advanced setup must be performed to
configure the thermostat for use with heat pump units.
NOTE: The 33CS250-FS thermostats have wiring connections
for a remote room sensor and dry contacts. The 33CS220-FS
thermostats do not have these connections.
PACKAGE CONTENTS
ITEM
Thermostat
Cutout Template
1-in. Screws (Junction Box Installation)
1
1
/
-in. Self-Tapping Screws
2
(Non-Junction Box Installation)
Plastic Tabs
Power Resistor (270 ohm, 10 Watt)
Form 33CS-35SI
Pg 1
Debonair®
33CS
QUANTITY
1
1
2
2
2
1
105
9-00
Replaces: New

Advertisement

Table of Contents
loading

Summary of Contents for Carrier Debonair 33CS

  • Page 1: Table Of Contents

    Debonair® 33CS Flush-Mounted FlatStat Commercial Programmable Thermostat Installation, Start-Up and Operating Instructions Part Numbers 33CS250-FS and 33CS220-FS CONTENTS Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety alert symbol. Page DANGER identifies the most serious hazards which will result SAFETY CONSIDERATIONS .
  • Page 2: Installation

    INSTALLATION b. Disconnect wires from existing thermostat. Do not allow wires to fall back into the wall. As each wire Select Thermostat Location — The thermostat should is disconnected, record wire color and terminal be mounted: connection. • approximately 5 ft from the floor c.
  • Page 3: Install Thermostat (Without Junction Box)

    → 8. Turn on power to unit. The thermostat will receive power 1. Turn off all power to unit. from the unit. The thermostat will be powered by 24 v, 2. Using cutout template provided, cut hole into wall. See nominal (18 to 30 vac).
  • Page 4: Set Clock

    On dry wall installations (see Fig. 5): DRY WALL a. Push two 1 -in. self tapping screws through 1 1/2” SCREW mounting holes in thermostat. PLASTIC TAB b. Attach 2 plastic tabs to 2 mounting screws. Only turn 3 or 4 threads into tabs. Do not fully tighten THERMOSTAT tabs onto screws.
  • Page 5: Install Accessories

    FAN CONFIGURATION (Step 3) — The fan configuration FILTER’’ icon is displayed. The range is 0 to 1950 hours. Set can be set to On or Auto. When the configuration is set to On, the variable to 0 to disable this function. The default is the fan will run continuously during the occupied schedule and 500 hours.
  • Page 6: Program Thermostat Schedules

    wiring, or other high voltage wiring. Do not use building raise or lower the heating set point until the desired tem- metalwork as a ground. Use only unshielded wire. perature is shown. The range of acceptable values is 35 to 99 F (1 to 37 C) or ‘‘OF’’...
  • Page 7: Factory Defaults

    Table 3 — Daily Schedule Planner SCHEDULE OF THE Occupied 1 Occupied 2 Occupied 3 Unoccupied WEEK Start / Stop / Heat / Cool Start / Stop / Heat / Cool Start / Stop / Heat / Cool Heat / Cool Monday Tuesday Wednesday...
  • Page 8: Fan Operation

    Fan Operation — Override button to enter into Holiday Programming mode. If Fan On is selected, the fan will run Press the DOWN ARROW to set the number of days to zero. continuously during occupied schedule and Heat, Cool, and Holiday mode will be disabled.
  • Page 9: 10-Watt Resistor

    Connecting transformers that are not phased correctly may thermostat. All other units will require one set of isolated con- result in a direct short, which could damage transformers and/ tacts for each of the following: Heat, Cool, Fan, and Reversing or the thermostat.
  • Page 10: Troubleshooting

    → TROUBLESHOOTING Table 4 — Thermostat Troubleshooting PROBLEM SOLUTION Display on thermostat not illuminated Check for 24 vac at the R terminal connection. Terminal R must be connected for proper thermostat operation. ‘‘Service Filter’’ is displayed on thermostat After the configured number of blower operating hours, the Service Filter mes- sage will be displayed.
  • Page 12 Copyright 2000 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 PC 111 Catalog No. 533-352 Printed in U.S.A. Form 33CS-35SI Pg 12 9-00 Replaces: New...

This manual is also suitable for:

Debonair 33cs250-fsDebonair 33cs220-fs

Table of Contents