Battery Backup Time; Battery Recharge Time - Toshiba 1800 Series User Manual

1800 series uninterruptible power systems (ups) 1500/2000/2400va
Hide thumbs Also See for 1800 Series:
Table of Contents

Advertisement

Battery BackuP tiMe

The exact amount of backup time provided will vary depending on the UPS
model being used, number of batteries, condition of the batteries and other
factors. However, the chart below gives the times that can be expected from
the standard units with batteries in good condition. For longer runtime options
contact your Toshiba sales representative or the Toshiba marketing department
at 877-867-8773 or by e-mail at toshibaups@tic.toshiba.com.
UPS Model
1500 VA**
2000 VA**
2400 VA
* Times given are approximate and will vary depending on the age of the batteries, the battery
temperature, the number of previous discharges and the type of load.
** Products are under development, specification may change.

Battery recHarGe tiMe

The following table gives estimates of the time required to recharge the UPS's
batteries. The recharge time may vary depending on the battery temperature,
the age of the batteries, and other factors.
2
taBLe 1 - BackuP tiMe as a % oF rated Load*
100%
13 min
10 min
7 min
taBLe 2 - Battery recHarGe tiMe*
Unit
1500 VA
2000 VA
2400 VA
* recharge times are to 90% full capacity.
75%
50%
22 min
35 min
17 min
25 min
12 min
20 min
Batteries
3 ½ hours
3 ½ hours
3 ½ hours
25%
65 min
53 min
44 min
1800 Series User Manual