Emerson 210-2002 Product Information Sheet page 5

Wall-mounted dewpoint sensor

Advertisement

Wall-Mounted Dewpoint Sensor
10. Press the Clear and Enter buttons together
and hold for five seconds. The word CAL will
appear in the topline of the LCD display:
11. Use the arrow buttons to toggle to the Zero
Calibration mode.
NOTE: Prior to pressing the Enter button, the zero
gas should be flowing to the dewpoint sensor
for atleast five minutes.
12. When ZERO is displayed, press the Enter
button to initiate the calibration process.
13. Once the Enter button is pressed, the
calibration process will take five to seven
minutes during which time the green LED
below the display will flash. Once calibration
is completed, the sensor will revert to its
normal display mode.
Emerson
TM
, Emerson. Consider It Solved
Intelligent Store
TM
is a trademark of Emerson Climate Technologies. All other trademarks are the property of their respective owners.
Product Information Sheet
TM
and Emerson Climate Technologies
© 2011 Emerson Climate Technologies, Inc. All rights reserved.
Vaporstat™ is a registered trademark of Telaire company.
51
Calibration Layout
Refer to the calibration topic of the manufacturer's
manual for the sensor's zero calibration layout.
Contact your CPC sales representative for calibration
kit (P/N 210-2005) purchasing information.