Quick Start Guide May 2021 Contents About this guide...........................3 Wiring diagram for RTDs......................5 Wiring diagram for thermocouples....................6 Additional RTD specifications....................... 7 Additional thermocouple specifications..................9 Product certifications......................... 10 Declaration of Conformity......................23 China RoHS..........................25 Emerson.com/Rosemount...
Be aware of the following situations: • If an I.S. approved Rosemount 214C Sensor is ordered with a housing, a transmitter enclosed in that housing may have a different I.S. approval rating. Refer to the transmitter IS certificate if applicable.
Page 4
Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access by unauthorized personnel to protect end users’ assets. This is true for all systems used within the facility. CAUTION Refer to Product Certification section of this Quick Start Guide documentation. Emerson.com/Rosemount...
May 2021 Quick Start Guide Wiring diagram for RTDs Figure 2-1: RTD Lead Wire Configuration per IEC 60751 - Single Element 3-wire 4-wire White White White Note To configure a single element, 4-wire RTD as a 3-wire system, connect only one white lead.
IEC 60584 Themocouple ASTM E230 Thermocouple Type POS (+) NEG (-) POS (+) NEG (-) Black White White Green White Yellow Brown White Blue Note Dual thermocouple sensors are shipped with one pair of the wires shrink- wrapped together. Emerson.com/Rosemount...
May 2021 Quick Start Guide Additional RTD specifications Note All specifications in this section apply to all RTDs unless noted otherwise. All RTDs meet and/or exceed type and routine tests for sensors/thermometers per IEC 60751:2008. Insulation resistance 1000 MΩ minimum insulation resistance when measured at 500 VDC at room temperature.
Page 8
Sensor type RT and RH: Meets 3 g vibration between 20 and 500 Hz for 150 hours. Sensor type RW: Meets 1 g vibration between 20 and 500 Hz for 150 hours. 4.10 Functional specifications Overvoltage Category I Power Environmental Pollution Degree 4 Emerson.com/Rosemount...
May 2021 Quick Start Guide Additional thermocouple specifications Note All specifications in this section apply to all thermocouple types unless noted otherwise. All thermocouples meet and/or exceed type and routine tests for sensors/thermometers per IEC 61515:2016. Insulation resistance 1000 MΩ minimum insulation resistance when measured at 500 VDC at room temperature.
Conformity can be found at Emerson.com/Rosemount. Ordinary Location Certification The Rosemount 214C has been examined and tested to determine that the design meets the basic electrical, mechanical, and fire protection requirements by a nationally recognized test laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).
Page 11
May 2021 Quick Start Guide 6.1.2 N5 USA Division 2 (NI) Certificate 70044744 Standards FM 3600:2011, FM 3611:2004, UL 50E:2007, UL 61010-1:2010, ANSI/ISA 60529:2004 Markings NI CL I, DIV 2, GP A, B, C, D; T6 (-50 °C ≤ T ≤...
Page 12
-50 °C for models with enclosure designation “AD1” or “SD1” 6.2.2 I1 ATEX Intrinsic Safety Certificate Baseefa16ATEX0101X Standards EN 60079-0:2012+A11:2013, EN 60079-11:2012 Markings II 1 G Ex ia IIC T5/T6 Ga (SEE CERTIFICATE FOR SCHEDULE) Thermocouples; P = 500 mW T6 -60 °C ≤ T ≤ +70 °C Emerson.com/Rosemount...
Page 13
May 2021 Quick Start Guide RTDs; P = 192 mW T6 -60 °C ≤ T ≤ +70 °C RTDs; P = 290 mW T6 -60 °C ≤ T ≤ +60 °C T5 -60 °C ≤ T ≤ +70 °C Special Conditions for Safe Use (X): The equipment must be installed in an enclosure which affords it a degree of ingress protection of at least IP20.
Page 14
-50 °C for models with enclosure designation “AD1” or “SD1”. 6.3.2 I7 IECEx Intrinsic Safety Certificate IECEx BAS 16.0077X Standards IEC 60079-0:2011, IEC 60079-11:2011 Markings Ex ia IIC T5/T6 Ga (SEE CERTIFICATE FOR SCHEDULE) Thermocouples; P = 500 mW T6 -60 °C ≤ T ≤ +70 °C Emerson.com/Rosemount...
Page 15
May 2021 Quick Start Guide RTDs; P = 192 mW T6 -60 °C ≤ T ≤ +70 °C RTDs; P = 290 mW T6 -60 °C ≤ T ≤ +60 °C T5 -60 °C ≤ T ≤ +70 °C Special Condition for Safe Use (X): The equipment must be installed in an enclosure which affords it a degree of ingress protection of at least IP20.
Page 16
1. Refer to certificate for details regarding process and ambient temperature limits. 2. When the Rosemount 214C Sensor is provided with an enclosure with a display cover, the maximum ambient shall be 95 °C. 3. The non-metallic label on the device may store an electrostatic charge and become a source of ignition in Group III atmospheres.
Page 17
May 2021 Quick Start Guide Special Conditions for Safe Use (X): The equipment must be installed in an enclosure which affords it a degree of ingress protection of at least IP20. China 6.5.1 E3 China Flameproof Certificate GYJ17.1010X (CCC 认证) Standards GB 3836.1-2010, GB 3836.2-2010, GB 12476.1-2013, GB 12476.5-2013 Markings...
Page 21
May 2021 Quick Start Guide 分:危险场所电气安装(煤矿除外)”、GB3836.16-2006“爆炸性气 体环境用电气设备 第 16 部分:电气装置的检查和维护(煤矿除 外)”和 GB50257-2014“电气装置安装工程爆炸和火灾危险环境电 力装置施工及验收规范”的有关规定. Korea 6.6.1 EP Korea Flameproof Certificate 17-KA4BO-0305X Markings Ex d IIC T6…T1, T6 (-50 °C ≤ T ≤ +80 °C), T5 (-50 °C ≤ T ≤ +95 °C), T4…T1 (-50 °C ≤...
Page 22
Combination of E5 and E6 Combination of E1 and E5 Combination of E1, E5, and E6 Combination of E1, E5, E6, and E7 Combination of EM and IM Combination of N1, N5, N6, and N7 Combination of EP and IP Emerson.com/Rosemount...
May 2021 Quick Start Guide China RoHS 214C 2/9/2021 214C Temperature Sensor China RoHS List of 214C Temperature Sensor Parts with China RoHS Concentration above MCVs / Hazardous Substances Hexavalent Polybrominated Polybrominated Part Name Lead Mercury Cadmium Chromium biphenyls diphenyl ethers (Pb) (Hg) (Cd)
Page 26
Quick Start Guide May 2021 Emerson.com/Rosemount...
Page 27
May 2021 Quick Start Guide Quick Start Guide...