Table 10 Liebert Challenger Itr Glycol Cooled Data, 60 Hz - Emerson Liebert Challenger ITR Technical Data Manual

Row-based, floor-mounted nominal 23 or 33kw systems, air-cooled, water/glycol-cooled, glycool, chilled water, split systems, 50 & 60 hz
Hide thumbs Also See for Liebert Challenger ITR:
Table of Contents

Advertisement

Table 10
Liebert Challenger ITR glycol cooled data, 60 Hz
System Type
BR = Horizontal Flow
BM = Horizontal Flow with Econ-O-Coil
Indoor Unit
Net Capacity Data
100°F DB, 70°F WB (37.8°C DB, 21.1°C WB) 20% RH
Non Standard Flow Rates
95°F DB, 68.3°F WB (35°C DB, 20.2°C WB) 24% RH
Non Standard Flow Rates
90°F DB, 66.5°F WB (32°C DB, 19.2°C WB) 28% RH
Non Standard Flow Rates
85°F DB, 64.4°F WB (29.4°C DB, 18°C WB) 32% RH
Non Standard Flow Rates
80°F DB, 62.7°F WB (26.7°C DB, 17.1°C WB) 38% RH
80°F DB, 66.5°F WB (26.7°C DB, 19.2°C WB) 50% RH
°F
°F
°C
75
DB, 62.5
WB (23.9
DB, 16.9
75°F DB, 61.1°F WB (23.9°C DB, 16.2°C WB) 45% RH
72°F DB, 60.1°F WB (22.2°C DB, 15.6°C WB) 50% RH
72°F DB, 58.7°F WB (22.2°C DB, 14.8°C WB) 45% RH
GLYCOOL Coil Sensible Capacity
75°F DB, 62.5°F WB (23.9°C DB, 16.9°C WB) 45°F (7.2°C) EGT
Fan Data (Blower A12x9AT)**
Standard Air, CFM (CMH)
Standard Fan Motor, hp (kW)
Opt Fan Motor, hp (kW)
Ext Static, in. WG (Pa)
Evaporator Coil (V-Frame, at standard conditions)
Face Area, ft.
Face Velocity, FPM (m/s)
Electric Reheat 2 Stage (Stainless Steel, Fin Tubular) - Standard
Capacity, inc. motor heat, BTU/H(element kW)
Hot Water Reheat 180°F (82.2°C) EWT, 75°F (23.9°C) EAT - Optional (includes standard air volume and optional fan motor hp)
Capacity, inc. motor heat, BTU/H(kW)
Flow Rate, GPM (l/s)
Pressure drop, ft. (kPa)
Hot Gas Reheat - Optional (includes standard air volume and optional fan motor)
Capacity, inc. motor heat, BTU/H (kW)
*
The net capacity data has fan motor heat factored in for all ratings and the entering air condition of 72°F (22.2°C) and 50% RH is the standard rating for
ASHRAE 127-2001.All capacities are nominal values; actual performance will be ±5%. All above data is based on 40% ethylene glycol solution.
** Data rated with 2" 20% ASHRAE filter. Some options or combinations of options may result in reduced airflow. Consult factory for recommendations.
Self-Contained
BR 071WG
BTU/H
Total
69,800
Sensible
69,800
1800 CFM, 21.5 GPM,
27.4 FT PD
Total
68,600
Sensible
68,600
2100 CFM, 21.5 GPM,
27.4 FT PD
Total
64,700
Sensible
64,700
2100CFM,18.5 GPM, 20.9FT PD
Total
62,800
Sensible
62,800
2300 CFM
Total
62,400
Sensible
62,400
Total
62,900
Sensible
53,200
°C
WB) 50% RH
Total
58,900
Sensible
51,500
Total
59,000
Sensible
59,000
Total
56,500
Sensible
50,500
Total
56,900
Sensible
56,900
2800 (4760)
1-1/2 (1.1)
2 (1.5)
.3 (75)
2
2
(m
)
6.67 (.62)
Rows
405 (2.1)
56,200 (15)
88,700 (26.0)
5.0 (.32)
16.9 (50.4)
54,900 (16.1)
Glycol Cooled
Split Systems
BR 060E
kW
BTU/H
20.5
71,600
20.5
71,600
2100 CFM
20.1
72,300
20.1
72,300
2600 CFM
19.0
69,900
19.0
69,900
18.4
66,200
18.4
66,200
18.3
62,500
18.3
62,500
18.4
63,000
15.6
53,200
17.3
58,800
15.1
51,500
17.3
59,000
17.3
59,000
16.6
56,500
14.8
50,500
16.7
56,900
16.7
56,900
2800 (4760)
1-1/2 (1.1)
2 (1.5)
.3 (75)
6.67 (.62)
4
405 (2.1)
56,200 (15)
88,700 (26.0)
5.0 (.32)
16.9 (50.4)
54,900 (16.1)
32
System Data
GLYCOOL
Self Contained
BM 061G
kW
BTU/H
21.0
66,000
21.0
66,000
2600 CFM, 20.5 GPM,
24.6 FT PD
21.2
64,700
21.2
64,700
2300 CFM, 19.5 GPM,
22.5 FT PD
20.5
65,300
20.5
65,300
19.5 GPM, 22.5 FT PD
19.4
61,500
19.4
61,500
18.3
58,200
18.3
58,200
18.5
59,900
15.6
51,200
17.2
55,900
15.1
49,500
17.3
55,000
17.3
55,000
16.6
53,600
14.8
48,500
16.7
53,000
16.7
53,000
47,700
2800 (4760)
2 (1.5)
N/A
.3 (75)
6.67 (.62)
4
4
405 (2.1)
57,700 (15)
N/A
5.0 (.32)
16.9 (50.4)
N/A
kW
19.3
19.3
19.0
19.0
19.1
19.1
18.0
18.0
17.1
17.1
17.6
15.0
16.4
14.5
16.1
16.1
15.7
14.2
15.5
15.5
14.0