Table 3 Liebert Challenger Itr Air-Cooled Data-60 Hz (Continued) - Emerson Liebert Challenger ITR Technical Data Manual

Row-based, floor-mounted nominal 23 or 33kw systems, air-cooled, water/glycol-cooled, glycool, chilled water, split systems, 50 & 60 hz
Hide thumbs Also See for Liebert Challenger ITR:
Table of Contents

Advertisement

Table 3
Liebert Challenger ITR air-cooled data—60 Hz (continued)
System Type
Indoor Unit
Infrared Humidifier - Standard
Capacity - lb/hr (kg/hr)
Steam Generating Humidifier - Optional
Capacity - lb/hr (kg/hr)
Filter Section - Efficiencies per ASHRAE 52.1 - Disposable Type
20% efficiencies available in 2" (51mm) - Standard, or optional 4" (102mm) depths; other optional 4" (102mm) efficiencies
are: 30%, 40-45%, 60-65%
Nominal Size - inches
Nominal Size - mm
Effective Surface Area - ft
Connection Sizes Liebert Challenger ITR Unit
Humidifier Supply Line
Condensate Drain Line
Condenser Air 95°F (35°C) Ambient
Ext. Static, in. WG (Pa)
Liquid Line Connection
Hot Gas Connection
Suction Line Connection
Self-Contained
BR 067A
11 (5)
kW
4.8
11 (5)
kW
3.9
28.5 x 29.5
724 x 749
2
2
(m
)
24.1 (2.2)
Liquid Line
1/2 OD Cu
Hot Gas Line
7/8 OD Cu
Suction Line
N/A
1/4 OD Cu
1/2 FPT
Model
CSF104
Motor, hp (kW)
3/4 (.56)
N/A
CFM (CMH)
6200 (10533)
5/8 OD Cu
1-1/8 OD Cu
N/A
w/Outdoor Prop-Fan
Condensing Unit
BR 060E
11 (5)
4.8
11 (5)
3.9
28.5 x 29.5
724 x 749
24.1 (2.2)
1/2 OD Cu
N/A
1-1/8 CD Cu
1/4 OD Cu
1/2 FPT
PFH067A_ _H
3/4 (.56)
N/A
6700 (11383)
1/2 OD Cu
N/A
1-1/8 OD Cu
25
System Data
Split Systems
w/Indoor Centrifugal
Condensing Unit
BR 060E
11 (5)
4.8
11 (5)
3.9
28.5 x 29.5
724 x 749
24.1 (2.2)
1/2 OD Cu
N/A
1-1/8 CD Cu
1/4 OD Cu
1/2 FPT
MC_65A
2 (1.5)
0.5 (125)
3500 (5947)
1/2 OD Cu
N/A
1-1/8 OD Cu

Advertisement