Table 23 Fan Speed Control Condensers; Table 24 Liebert Lee-Temp Condensers; Table 25 Liebert Lee-Temp Receiver Heater Pads For Use W/Csl Condensers; Table 26 Drycooler And Pump Package - 95°F (35°C) Ambient - Emerson Liebert Challenger ITR Technical Data Manual

Row-based, floor-mounted nominal 23 or 33kw systems, air-cooled, water/glycol-cooled, glycool, chilled water, split systems, 50 & 60 hz
Hide thumbs Also See for Liebert Challenger ITR:
Table of Contents

Advertisement

Table 23
Fan speed control condensers *
95°F (35°C) Ambient, 1 Phase - 60 Hz
CSF 104
Voltage
208/230
FLA
4.8
WSA
6.0
OPD
15.0
* Contact factory for 380-3-60 data.
Table 24
Liebert Lee-Temp condensers *
95°F (35°C) Ambient, 3 Phase - 60 Hz
CSL104
Voltage
208/230
FLA
3.5
WSA
4.4
OPD
15.0
* Contact factory for 380-3-60 data.
Table 25
Liebert Lee-Temp receiver heater pads for use w/CSL condensers
Volts
120
Watts/Pad
150
FLA
1.4
WSA
1.8
OPD
Separate electrical source required for continuous operation
of single phase heater pads for Liebert Lee-Temp.
Table 26
Drycooler and pump package - 95°F (35°C) ambient *
Voltage
208/230
Glycol
DSF Model
112
Pump Hp
3/4
FLA
7.0
WSA
7.9
OPD
15
Glycol DS0174
DSF Model
174
Pump Hp
1.5
FLA
13.6
WSA
15.3
OPD
20
GLYCOOL
DSO Model
112
Pump Hp
1-1/2
FLA
10.1
WSA
11.8
OPD
15
1. Pump and drycooler powered from same 3 phase feeder.
* Contact factory for 380-3-60 data.
460
575
2.5
1.9
3.1
2.4
15.0
15.0
460
575
1.7
1.4
2.1
1.8
15.0
15.0
230
150
0.7
0.9
15
15
460
575
112
112
3/4
3/4
3.3
2.7
3.7
3.1
15.0
15.0
174
174
1.5
1.5
6.4
5.2
7.2
5.8
15.0
15.0
112
112
1-1/2
1-1/2
4.7
3.8
5.5
4.4
15
15
47
Electrical Data

Advertisement

Table of Contents
loading

Table of Contents