Table 18 Scroll Compressor And Main Fan (For Comparison Purposes Only); Table 19 Outdoor Condensing Units - Emerson Liebert Challenger ITR Technical Data Manual

Row-based, floor-mounted nominal 23 or 33kw systems, air-cooled, water/glycol-cooled, glycool, chilled water, split systems, 50 & 60 hz
Hide thumbs Also See for Liebert Challenger ITR:
Table of Contents

Advertisement

Table 18
Scroll compressor and main fan (for comparison purposes only) *
Voltage
208
230
(3, 60 Hz)
Scroll Compressor
RLA
20.7
20.7
LRA
128.0
128.0
Main Fan
Motor
1.5 hp (1.1 kW)
RLA
5.7
5.2
LRA
35.9
31.2
Motor
2.0 hp (1.5 kW)
RLA
7.5
6.8
LRA
46.9
40.8
Motor
3.0 hp (2.2 kW)
RLA
10.6
9.6
LRA
66.0
58.0
* Contact factory for 380-3-60 data.
Table 19
Outdoor condensing units
Electrical Data 60 Hz 95°F (35°C) Ambient
Voltage
Model
FLA
208/230-3-60
WSA
OPD
FLA
380-3-60
WSA
OPD
FLA
460-3-60
WSA
OPD
FLA
575-3-60
WSA
OPD
460
575
10.0
7.4
63.0
49.0
2.6
2.1
15.6
12.6
3.4
2.7
20.4
16.2
4.8
3.9
26.8
23.4
Electrical Data 60 Hz 105°F (40°C) Ambient
PFH067A-_L
Voltage
24.1
29.3
208/230-3-60
45.0
12.4
15.1
380-3-60
25.0
11.7
14.2
460-3-60
20.0
9.1
11.1
575-3-60
15.0
45
Model
PFH067A-_H3
FLA
24.2
WSA
29.4
OPD
50.0
FLA
12.4
WSA
15.1
OPD
25.0
FLA
11.7
WSA
14.2
OPD
20.0
FLA
9.3
WSA
11.3
OPD
15.0
Electrical Data