Figure 16 Cabinet And Floor Planning Dimensional Data-Propeller Fan Condensing; Figure 17 Cabinet And Floor Planning Dimensional Data-Self-Contained System-Air-Cooled; Modules—Vertical Air Discharge - Emerson Liebert Challenger ITR Technical Data Manual

Row-based, floor-mounted nominal 23 or 33kw systems, air-cooled, water/glycol-cooled, glycool, chilled water, split systems, 50 & 60 hz
Hide thumbs Also See for Liebert Challenger ITR:
Table of Contents

Advertisement

Figure 16 Cabinet and floor planning dimensional data—Propeller fan condensing modules—Vertical air
discharge
Guard
Height
D
B
Left Air
Intake
Shaded area indicates
a recommended clearance
of 18" (457mm) for proper
air flow.
4-23/32"
(120mm)
Model Numbers
60 HZ
50 HZ
PFH067A-_H
PFH066A-_H
PFHZ67A-_H
PFHZ66A-_L
Figure 17 Cabinet and floor planning dimensional data—Self-contained system—Air-cooled condenser or
drycooler
2"
(51mm)
A
Removable front panel for
access to high voltage and
low voltage connections,
and refrigeration components.
36-1/8"
(918mm)
25-3/32 "
(637mm)
46-7/32 "
(1174mm)
Dimensional Data in. (mm)
A
B
53
36-1/4
(1343)
(918)
Top Air
Discharge
C
4" Typ.
53-3/16"
(102mm)
(1351mm)
2" Typ.
(51mm)
2"
(51mm)
Footprint Dimensions
Module Weight
C
D
lbs (kg) net.
38-1/2
5-1/2
488
(978)
(140)
(222)
42
Dimensional Drawings
Right
Air
Intake
Shaded area indicates
a recommended clearance
of 18" (457mm) for proper
air flow.
Shaded area indicates
a recommended clearance
of 24" (610mm) for component
access.
1/2" Bolt-Down
Holes (6 places)
2"
32-1/8"
(51mm)
(816mm)
DPN000131
Rev. 0
Liebert Lee-Temp Receiver
L = 40" (1016mm)
W = 7-1/2" (190mm)