Installing the BladeCenter S chassis in a rack

Use the rack template and the rack installation kit that comes with the BladeCenter
S system to correctly install it in a rack.
Before you begin, review the "Installation guidelines" on page 25.
If you are installing the BladeCenter S chassis in the Office Enablement Kit, see the
Office Enablement Kit Installation and User's Guide.
Rack requirements:
v Make sure that the room air temperature is below 35°C (95°F).
v Do not block any air vents; usually, 15 cm (6 in.) of air space in the rear and 5
v Three or more people are required to install the device in a rack.
v Do not leave any unused U space within a rack open. Blank filler panels must
v Install your BladeCenter S chassis only in a rack cabinet with perforated front
v Do not extend more than one device out of the rack at the same time.
v Remove the rack doors and side panels to provide easier access during
v The rack-mounting flanges must have holes and clearances per EIA-310-D.
v Make sure that there is sufficient room in front of the front EIA flange to provide
v Make sure that there is sufficient room behind the rear of the rear EIA flanges to
v Rack weight-handling capacity must be sufficient for the aggregate weight of the
v The rack must be stabilized with stabilization brackets and leveling pads so that
To install the BladeCenter S chassis in a rack, complete the following steps:
32
BladeCenter S Type 7779/8886: Installation and User's Guide
b. Remove all fan modules.
cm (2 in.) in the front provides proper airflow.
be used to prevent recirculation of warm air.
and rear doors or in a rack that is equipped with an IBM Rear Door Heat
eXchanger.
installation.
minimum bezel clearance of 70 mm (2.76 inches) deep.
provide for adequate cable management and routing.
BladeCenter S chassis, blade servers, power distribution units, and power cables.
it does not become unstable when it is fully populated.
1. Read "Safety" on page v and "Handling static-sensitive devices" on page 26.
Fan
error
LED