Hitachi L100DN DeviceNet Series Addendum Read This First Manual page 30

Table of Contents

Advertisement

30
Configuring Drive Parameters
"P" Group: DeviceNet Network Settings
The following table describes the DeviceNet network settings for L100DN inverters.
Func.
Name
Code
P_41 DeviceNet baud rate
P_42 DeviceNet MAC ID
P_43 DeviceNet control
enable
P_44 DeviceNet comm
watchdog timer
P_45 Inverter action on
DeviceNet comm error
P_46 DeviceNet polled I/O:
Output instance number
P_47 DeviceNet polled I/O:
Input instance number
P_48 Inverter action on
DeviceNet idle mode
P_49 DeviceNet motor poles
setting for RPM
Note 1:
"P" Function
Description
Three options; select codes:
00... 125 kbps
01... 250 kbps
02... 500 kbps
Selects the DeviceNet node
address, range is 0 to 63
Two options; select codes:
00... Disable
01... Enable
Range is 0.00 to 99.99 seconds
Five options:
00... Trip
01... Decelerate and trip
02... Hold last speed
03... Free-run stop
04... Decelerate and stop
Three settings:
20, 21, 100 *1
Three settings:
70, 71, 101 *1
Five options:
00... Trip
01... Decelerate and trip
02... Hold last speed
03... Free-run stop
04... Decelerate and stop
Range is 00 to 38 (even
numbers only), two types:
00... For freq. setting (Hz)
02 to 38... For speed (RPM)
Functions P_46 and P_47 must be set as a corresponding pair. Valid settings
for P_46 / P_47 are 20 / 70, 21 / 71, or 100 / 101 (default). Other setting
combinations can cause a DeviceNet network error.
Defaults
Run
Mode
–FE
–FU
–F
Edit
(CE)
(UL)
(Jpn)
00
00
00
63
63
63
01
01
01
1.00
1.00
1.00
01
01
01
100
100
100
101
101
101
01
01
01
00
00
00
Units