Configuring Drive Parameters
To the 15 option codes for standard L100 inverters, L100DN Series inverters remove the
code for the [AT] input, and add the following 7 options:
Option
Terminal
Code
Symbol
20
STA
21
STP
22
F/R
25
DNT
27
UP
28
DWN
31
OPE
NOTE: The assignment of [DNT] to an input terminal is optional. It is useful if you
need to switch between DeviceNet network control and local control during running.
Alternatively, you can use parameter P_43 DeviceNet Control Enable, which works
similarly but does not require an input terminal. If assigned, the [DNT] setting has prece-
dence over the P_43 setting. More information is in "Step 7 – Control Test – Verify
Network Host Can Control Inverter" on page 54.
Input Function Summary Table
Function Name
Start Motor
ON
OFF
Stop Motor
ON
OFF
FWD/REV
ON
OFF
DeviceNet Select
ON
OFF
Remote Control
ON
UP Function (motor-
ized speed pot.)
OFF
Remote Control
ON
DOWN Function
(motorized speed
OFF
pot.)
Force Operation
ON
from Digital
Operator
OFF
Description
Start motor rotation on momentary contact (uses
acceleration profile)
No change to motor operation
Stop motor rotation on momentary contact (uses
deceleration profile)
No change to motor operation
Select reverse direction of rotation
Select forward direction of rotation
Inverter operates under DeviceNet network
control
Inverter operates under local control (keypad and
input terminals)
Accelerates (increases output frequency) motor
from current frequency
No change to output frequency
Decelerates (decreases output frequency) motor
from current frequency
No change to output frequency
Forces the operator interface Run command to
over-ride commands from input terminals (such
as [FW], [RV])
Run command operates normally, as configured
by A_02