INSTALLATION AND MAINTENANCE INSTRUCTIONS
B524RB(A) and B224RB(A) Plug-in
Relay Detector Bases
For use with the following models:
B524RB:
For use with any 500 Series detector
B224RB:
For use with any 200 Series detector
Specifications
Base Diameter:
Base Height
B224RB:
B524RB:
Mounting:
Operating Temperature Range:
Operating Humidity Range:
Electrical Ratings
Operating Voltage:
Time Averaged Standby Ratings:
Relay Characteristics
Coil:
Contact Type:
Contact Relay
Resistive:
Inductive:
Set Time:
Reset Time:
Before Installing
Please thoroughly read the system wiring and installation
manuals, and manual I56-407, Guide for Proper Use of Sys-
tem Smoke Detectors, which provides detailed information
on detector spacing, placement, zoning, and special appli-
cations. Copies of these manuals are available at no charge
from System Sensor. (For installation in Canada, refer to
CAN/ULC-S524, Standard for the Installation for Fire Alarm
Systems and CEC Part 1, Sec. 32.)
NOTICE: This manual should be left with the owner/user
of this equipment.
IMPORTANT: The detector used with these bases must be
tested and maintained regularly following NFPA 72 require-
ments. The detectors should be cleaned at least once a year.
D450-16-01
6.2 inches (157 mm)
1.2 inches (31 mm)
1.4 inches (36 mm)
4-inch square box with or without plaster ring, Min Depth - 1.5 inches (13 mm)
4-inch octagon box, Min. depth - 1.5 inches (13 mm)
3
1
/
-inch octagon box, Min. depth - 1.5 inches (13 mm)
2
0 to 49 C (32 to 120 F)
10% to 93% Relative Humidity (Non-condensing)
15 to 28 VDC
<500 A @ 24 VDC
2 coil latching
1 Form C
2 A @ 30 VDC
0.3 A @ 110 VDC (with .35 PF or greater)
0.3 A @ 120 VAC (with .35 PF or greater)
1.0 A @ 30 VDC (with .6 PF or greater)
4 seconds minimum, 20 seconds maximum
1 second minimum, 8 seconds maximum
1
3825 Ohio Avenue, St. Charles, Illinois 60174
General Information
Form C latching relay contacts are included for the control
of an auxiliary function. The relay operates 12 seconds
(nominally) after activation of the sensor head remote an-
nunciator output.
Mounting
The detector base mounts directly to 3
tagon and 4-inch square boxes, with or without a plaster
ring.
To mount, remove the decorative ring by rotating it in ei-
ther direction to unhook the snaps. Then, separate the ring
from the base. Install the base on the box, using the screws
supplied with the junction box and the appropriate slots in
the base. Replace the decorative ring on the base and ro-
tate it in either direction until the ring snaps in place (see
Figure 1).
A Division of Pittway
1-800-SENSOR2, FAX: 630-377-6495
1
/
- and 4-inch oc-
2
I56-659-06

Advertisement

loading
Need help?

Need help?

Do you have a question about the B224RB and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for System Sensor B224RB

  • Page 1 Copies of these manuals are available at no charge from System Sensor. (For installation in Canada, refer to Mounting CAN/ULC-S524, Standard for the Installation for Fire Alarm The detector base mounts directly to 3 - and 4-inch oc- Systems and CEC Part 1, Sec.
  • Page 2 Installation Guidelines Figure 1. Mounting the base to an electrical box: All wiring must be installed in compliance with all appli- cable local codes and any special requirements of the local authority having jurisdiction, using the proper wire sizes. The conductors used to connect smoke detectors to control panels and accessory devices should be color-coded to re- duce the likelihood of wiring errors.
  • Page 3 Figure 2. Wiring diagram: TWISTED PAIR RECOMMENDED OTHER INTELLIGENT DEVICES (–) (–) (–) (COMMON) (N.O.) (N.C.) 3 RELAY COMMON 1 NORMALLY CLOSED 2 NORMALLY OPEN CLASS A OPTIONAL WIRING A78-1577-15 A label is affixed to the base for recording the zone, ad- To activate this feature, break the tab from the detector dress, and type of detector being installed at the base loca- base as shown in Figure 3A (see page 4).
  • Page 4 NFPA 72 or at least once a year. Three-Year Limited Warranty System Sensor warrants its enclosed smoke detector base to be free from Repair Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL defects in materials and workmanship under normal use and service for a 60174.