"OPEN TO LEFT" ADJUSTMENT PROCEDURES
Left Gate Motion Adjustment (R160)
1. Initiate opening the gate.
2. Wait 4 to 5 seconds, then lightly "tug"against the edge of the gate to simulate an obstacle.
3. If the gate does not stop, reclose the gate and adjust the pot slightly counterclockwise.
4. Repeat steps 1-3 until the gate stops when tugged and has the desired sensitivity.
Right Gate Motion Adjustment (R69)
1. Open the gate fully, then initiate closing the gate.
2. Wait 4 to 5 seconds, then lightly "bump" the leading edge of the gate to simulate an obstacle.
3. If the gate does notstop or back up, reopen the gate and adjust the pot slightly
counterclockwise.
4. Repeat steps 1-3 until the gate stops or backs up when bumped and has the desired
sensitivity.
INRUSH CURRENT ADJUSTMENT (R203)
1. Turn the pot fully counterclockwise.
2. Open the gate.
3. If the gate stops due to a fault condition, slightly adjust the pot clockwise.
4. Repeat steps 2 and 3 until the gate cycles without a fault.
5. Open gate fully, then iInitiate closing the gate.
6. If the gate stops or backs up due to a fault condition, slightly adjust the pot clockwise.
7. Repeat steps 6 and 7 until the gate cycles without a fault and has the desired sensitivity.
I. BASIC GATE OPERATOR PROGRAMMING
Even if you plan to program the gate operator by telephone, you may want to enter some immediate
instructions during installation. The following list of instructions will help you set basic controls so the
gate will operate properly until you have time for full programming, either directly or by telephone. For
complete programming instructions, refer to the enclosed manual "Programming Instructions For The
LiftMaster SL 1000-X1 and SW 2000-X1 Gate Operators" (Doc. No. 6001193).
To access programming mode: enter ∗∗∗ 000000 (3 asterisks, 6 zeroes)
To program a command: a) enter step number b) enter required digits of data c) enter # (pound sign)
To exit programming mode: enter 00# (2 zeroes, 1 pound sign)
Step
01
Gate Type
06
Anti-Tailgate Enable (ATG)
08
Reclose Time (RT)
09
Maximum Retry Count
10
Retry Pause Time
11
Reverse Sense Backup Inches
13
Safety Bar Backup If Closing
14
Safety Bar Backup If Opening
15
Return Factory Set Defaults
Rev C
Purpose
1
1
Up to 3
1
Up to 2
Up to 3
Up to 3
Up to 3
Doc 6001194 (01-20259)
Required Digits
6
Acceptable Input
0 - 1 (0 = Slide, 1 = Swing)
0 - 1 (0 = Disabled, 1 = Enabled)
0 - 250, expressed in seconds
(0 = Disabled)
0 - 2 (0 = Do not retry)
30 - 99, expressed in seconds
0 - 499, expressed in inches
0 - 499, expressed in inches
0 - 499, expressed in inches
101010