NOTE: Dimensions are in inches.
Fig. 35 — Condenser-Fan Adjustment,
558F180,210,300
NOTE: Dimensions are in inches.
Fig. 36 — Condenser-Fan Adjustment,
558F240
VII. ECONOMI$ER ADJUSTMENT
A. LED indication
The EconoMi$er controller features an onboard diagnostic
LED (light-emitting diode) that flashes to indicate its status.
See Table 16 for flash codes. The controller also has terminal
connections (REM LED) for remotely mounting an LED, if
desired. The flash code priorities are as follows:
1. On/Off or continuous flash
2. Critical fault
3. Non-critical fault
If any sensors are opened, shorted, or removed, the
EconoMi$er determines whether the failure is critical or
FLASH CODE
Constant On
Normal operation
Constant Off
No power
Continuous
CONFIG button pushed and held
Flash
between 3 and 9 seconds
Flash One
Control board fault
Flash Two
Thermostat fault (i.e., Y2 without Y1)
Flash Three
Actuator fault
Flash Four
Discharge air thermistor fault
Flash Five
Outdoor air temperature sensor fault
Flash Six
Outdoor air humidity sensor fault
Flash Seven
Return air temperature sensor fault
Flash Eight
Return air humidity sensor fault
Flash Nine
Carbon Dioxide (CO
Flash Ten
Onboard adjustment potentiometer fault
Table 16 — EconoMi$er Control Module Flash Code Identification
CAUSE
) sensor fault
2
non-critical and flashes the appropriate code. If a non-critical
sensor fault occurs (i.e., outdoor air humidity), the
EconoMi$er automatically reconfigures its control strategy
to a more appropriate mode. If a critical sensor fault occurs
(i.e., supply air sensor), the EconoMi$er reverts to a safe
mode of operation until the sensor problem is resolved.
B. Manual Configuration Pushbuttom
The EconoMi$er controller also features an onboard button
(CONFIG) to help troubleshoot the system. See Fig. 17. The
button can perform 3 different functions.
Pressing the CONFIG button for more than three seconds,
but less than ten seconds and then releasing will start the
automatic test procedure. The damper will modulate fully
open, wait, and modulate closed. This process takes three
minutes to complete. Use this feature to determine if the
actuator can be commanded.
If the CONFIG button is pressed and held for ten seconds
and less than 30 seconds then released, the EconoMi$er
controller reconfigures its mode of operation based on the
sensors that are connected and functioning normally, and
cancels the automatic test procedure.
If the EconoMi$er controller recognized a non-critical sensor
fault, and flashed a code (i.e., FLASH 6, outdoor air
humidity sensor fault) the FLASH CODE will be cleared,
and normal operation begins. Ensure faulty sensor is
removed before clearing faults.
If the EconoMi$er controller recognizes a critical sensor
fault, and flashes a code (i.e., FLASH 4, discharge air ther-
mistor fault) the FLASH code will not be cleared, and the
EconoMi$er will remain in the safe operation mode. The
sensor fault must be corrected to enable EconoMi$er to
revert to normal operation.
If the CONFIG button is pressed and held for more than
30 seconds and released, the EconoMi$er controller will
enable the enthalpy comparison strategy (with outdoor air
enthalpy and return air enthalpy sensors installed).
VIII. POWER FAILURE
Dampers have a spring return. In event of power failure,
dampers will return to fully closed position until power is
restored. Do not manually operate damper actuator.
ACTION TAKEN BY ECONOMI$ER
Normal operation.
No operation.
Outdoor air damper is stroked fully open, then closed
(automatic test procedure takes 3 minutes to complete).
System shutdown.
System shutdown until corrected.
Revert to mechanical cooling only.
Continue operation with damper at minimum position.
Revert to mechanical cooling only.
Continue operation with damper at minimum position.
Disable mechanical cooling lockout.
Continue operation with dry bulb or dry bulb differential switchover.
Continue operation with single enthalpy EconoMi$er
switchover or dry bulb EconoMi$er switchover (without
humidity sensor).
Continue operation with single enthalpy, differential dry
bulb, or dry bulb EconoMi$er switchover.
Continue operation without ventilation control.
Continue operation with default potentiometer settings.