Bryant DuraPac 558F Installation & Service Instructions Manual page 24

Single package rooftop electric heat/electric cooling unit
Hide thumbs Also See for DuraPac 558F:
Table of Contents

Advertisement

UNIT
558F
180†
180**
210†
210**
240†
240**
300†
300**
*Approximate fan rpm shown.
†Indicates standard drive package.
UNIT
UNIT
558F
VOLTAGE
208/230
180
460
208/230
210
460
208/230
240
460
208/230
300
460
LEGEND
BHP — Brake Horsepower
BkW — Brake Kilowatts
*Extensive motor and electrical testing on these units ensures that the full horse-
power (brake kilowatt) range of the motors can be utilized with confidence. Using
Table 15 — Evaporator-Fan Motor Efficiency
MOTOR
HORSEPOWER
5 Hp
7.5 Hp
10.0 Hp
NOTE: All indoor-fan motors 5 hp and larger meet the minimum efficiency
requirements as established by the Energy Policy Act of 1992 (EPACT) effective
October 24, 1997.
XII. BASE UNIT OPERATION
A. Cooling, Units without EconoMi$er
When thermostat calls for cooling, terminals G and Y1 are
energized. The indoor (evaporator) fan contactor (IFC), and
compressor contactor no. 1 (C1) are energized and evaporator-
fan motor, compressor no. 1 and condenser fans start. The
condenser-fan motors run continuously while unit is cooling. If
the thermostat calls for a second stage of cooling by energizing
Y2, compressor contactor no. 2 (C2) is energized and compres-
sor no. 2 starts.
B. Heating, Units without EconoMi$er (If Accessory or
Optional Heater is Installed)
Upon a call for heating through terminal W1, IFC and
heater contactor no. 1 (HC1) are energized. On units
equipped for 2 stages of heat, when additional heat is
needed, HC2 is energized through W2.
C. Cooling Units with EconoMi$er
When the OAT is above the ECON SP set point and the room
thermostat calls for Stage 1 cooling (R to G + Y1), the indoor-fan
motors (IFM) is energized and the EconoMi$er damper modu-
lates to minimum position. The compressor contactor and OFC
are energized to start the compressor and outdoor-fan motor
(OFM). After the thermostat is satisfied, the damper modulates
to the fully closed position when the IFM is deenergized.
Table 13 — Fan Rpm at Motor Pulley Settings*
1
1
0
/
1
1
/
2
2
††
††
††
††
††
††
††
††
††
††
1095
1077
††
††
1287
1265
††
††
††
††
††
††
††
††
††
††
1283
1269
††
††
††
††
Table 14 — Evaporator-Fan Motor Performance
MAXIMUM
ACCEPTABLE
CONTINUOUS
BHP*
6.13
6.13
5.90
5.90
8.70
9.50
10.20
11.80
MOTOR EFFICIENCY
(%)
87.5
88.5
89.5
MOTOR PULLEY TURNS OPEN
1
1
2
2
/
3
3
/
2
1021
1002
984
965
1200
1178
1156
1134
1058
1040
1021
1002
1243
1222
1200
1178
1151
1132
1114
1095
1369
1347
1325
1303
1247
1225
1203
1182
1551
1524
1497
1470
**Indicates alternate drive package.
††Due to belt and pulley size, pulley cannot be set to this number of turns open.
MAXIMUM
ACCEPTABLE
CONTINUOUS
BkW*
4.57
4.57
4.40
4.40
6.49
7.08
7.61
8.80
your fan motors up to the horsepower (brake kilowatt) ratings shown in this table
will not result in nuisance tripping or premature motor failure. Unit warranty will
not be affected.
NOTE: All indoor-fan motors 5 hp and larger meet the minimum efficiency re-
quirements as established by the Energy Policy Act of 1992 (EPACT) effective
October 24, 1997.
When the OAT is below the ECON SP setting and the room
thermostat calls for Stage 1 cooling (R to G + Y1), the
EconoMi$er modulates to the minimum position when the
IFM is energized. The EconoMi$er provides Stage 1 of cooling
by modulating the return and outdoor air dampers to main-
tain a 55 F supply air set point. If the supply-air temperature
(SAT) is greater than 57 F, the EconoMi$er modulates open,
allowing a greater amount of outdoor air to enter the unit. If
the SAT drops below 53 F, the outdoor air damper modulates
closed to reduce the amount of outdoor air. When the SAT is
between 53 and 57 F, the EconoMi$er maintains its position.
If outdoor air alone cannot satisfy the cooling requirements
of the conditioned space, and the OAT is above the MECH
CLG LOCKOUT set point, the EconoMi$er integrates free
cooling with mechanical cooling. This is accomplished by the
strategies below.
NOTE: Compressors have a two-minute Minimum On and
Minimum Off, which are accomplished by the strategies below.
1. If Y1 is energized, and the room thermostat calls for
Y2 (2-stage thermostat), the compressor and OFC are
energized. The position of the EconoMi$er damper is
maintained at its current value.
2. If Y1 is energized for more than 20 minutes, and Y2 is
not energized (whether or not a 2-stage thermostat is
used), the compressor and OFC are energized. The
position of the EconoMi$er damper is maintained at
its current value.
3. If Y1 is energized, and compressor no. 1 is already
energized (see Step 2) and the room thermostat calls
for Y2, compressor no. 1 continues to operate. If Y2
remains energized for more than 20 minutes, com-
pressor no. 2 is energized.
24
1
4
4
/
5
2
2
947
928
910
1112
1091
1069
984
965
947
1156
1134
1112
1077
1058
1040
1281
1259
1237
1160
1138
1116
1443
1415
1388
MAXIMUM
ACCEPTABLE
MAXIMUM
OPERATING
AMP DRAW
WATTS
5,180
5,180
5,180
5,180
7,915
8,640
9,510
11,000
1
5
/
6
2
891
873
1047
1025
928
910
1091
1069
1021
1002
1215
1193
1095
1066
1361
1332
15.8
7.9
15.8
7.9
22.0
13.0
28.0
14.6

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Durapac series

Table of Contents