Electrical Main Service; Wiring Grounding And Bonding; Circuit Breaker Installation And Wiring - Hayward Aqua Plus® Installation Manual

Model: pl-plus installation
Hide thumbs Also See for Aqua Plus®:
Table of Contents

Advertisement

Remote Keypad
Temp Sensor Inputs
External Input
Heater Output
Valve Connectors
Flow Switch
The Aqua Plus Control Center requires both high and low voltage connections. Low voltage connections will be made
to actuators, sensors, remote keypad, etc. High voltage connections will be made to pumps, lights, etc., as well as
providing direct input power to the Control Center. Always:
-Ensure that Power is disconnected prior to doing any wiring
-Follow all local and NEC (CEC if applicable) codes
-Use copper conductors only
Main Service (Power to the Circuit Breaker Subpanel)
The Aqua Plus circuit breaker subpanel is rated for 100A service. Run properly rated conductors (L1, L2, N, and
ground) from the primary house electrical panel to the main power connections on the Aqua Plus circuit breaker base.
The connection at the main house panel should be to a 240VAC circuit breaker rated at 100A maximum.
Grounding and Bonding
Connect a ground wire from the primary electrical panel to the Aqua Plus ground bus bar. Also ground each piece of
high voltage (120 or 240VAC) equipment that is connected to the Aqua Plus control relays or circuit breakers. The
Aqua Plus should also be connected to the pool bonding system by an 8AWG (6AWG for Canada) wire. A lug for
bonding (2 for Canada) is provided on the outside/bottom of the Aqua Plus enclosure.

Circuit Breaker Installation and Wiring

Circuit breakers are to be supplied by the installer. Refer to the circuit breaker chart below for a list of suitable circuit
breakers that can be used. Follow the code and the circuit breaker manufacturer's rating requirements regarding the
size and temperature rating for wiring. Note that some pool equipment may be required to be connected to ground
fault circuit breakers—check local and NEC (CEC) codes.
4. Electrical Wiring
Wireless Base
Receiver Connector
x
x
Cell Connector
Subpanel
SUITABLE LISTED BREAKERS
Manufacturer
Single Double
BR
BR
Cutler-Hammer
MP-T
Murray
MP-T
QP
QP
Siemens
HOM
Square D
HOM
TB
Thomas & Betts
TB
THQL
THQL
G.E.
AQL-CHEM Connector
Ground Bus Bar
Twin
Quad
Filler Plates
GFCB
BRFP
BRD
BRD
GFCB
MH-T
MH-T
MP-GT
LX100FP
QPF
QF3
QT
QT
HOMT
HOMT
HOM-GFI
HOMFP
FP-1C-TB
TBBD
TBBQ
GFB
THQL-GF
TFH
10
"Local" Display
High Voltage
Relays
Control Power
Input
pH Dispense
Output
Bonding Lug(s)
Tightening
Torque
25lb-in
25lb-in
25lb-in
25lb-in
25lb-in
25lb-in

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aqua plus pl-plusAqua plus pl-plus-20

Table of Contents