Technical Specifications

Enclosure Specifications

Ac Power
Requirements
Requirement
ac line voltage
ac line current
Power consumption
Power factor
Heat dissipation
In-rush current
Startup surge current
ac protection
ac receptacle type
Ride-through time
Current sharing
2-Gigabit Disk-Array Enclosure (DAE2) Hardware Reference
A-2
Technical enclosure specifications include power requirements, size,
drive, interface, and standards information.
The input current, power (VA), and dissipation per DAE2 are based
on the requirements that a maximum DAE2 configuration places on
the power supplies and cooling system to provide internal regulated
power. Typical values will be less, depending on the number and
manufacturer of disk modules. These values represent either
the values for a single power supply line cord, or
the sum of values shared by the line cords of two power supplies
in the same DAE2, with the division between the line cords and
supplies at the current sharing ratio (approximately 50% each).
A failure of one of the two power supplies in the DAE2 results in the
remaining supply and cord supporting the full load. You must use a
rackmount cabinet with ac power distribution, and have main branch
ac distribution that can handle these values for each disk enclosure in
the cabinet.
DAE2 (Fibre Channel)
100 to 240 V ac + 10%, single phase, 47 to 63 Hz
4.0 A at 100 V ac, 1.6 A at 200 V ac
400 VA(392 W) max (fully configured)*
6
1.41 x10
J/hr (1,330 BTU/hr) max *
25 A max for 1/2 line cycle, per power supply at 240 V ac
15 A max for 1/2 line cycle, per power supply at 120 V ac
15 A pk (10.6 A rms) max for 100 ms, at any line voltage
10 A fuse in each power supply, both phases
IEC320-C14 appliance coupler, per power supply
60% max, 40% min, between power supplies
* A fully configured DAE2 includes two power supplies, two LCCs, and 15 disk drives.
Description
3.0 A at 100 Vac, 1.4 A at 200 V ac
300 VA (294 W) max (fully configured)*
0.98 min at full load, low voltage
6
1.06 x10
J/hr (1,017 BTU/hr) max *
30 ms min
DAE2-ATA