General Site Preparation Guidelines
Environmental Elements

Electrostatic Discharge (ESD) Prevention

Static charges (voltage levels) occur when objects are separated or rubbed together. The voltage level of a
static charge is determined by the following factors:
Types of materials
Relative humidity
Rate of change or separation
Table 2-1
Effect of Humidity on ESD Charge Levels
Personnel Activity
Person walking across a linoleum floor
Person walking across a carpeted floor
Person getting up from a plastic chair
a. Source: B.A. Unger, Electrostatic Discharge Failures of Semiconductor Devices (Bell Laboratories,
1981).
b. For the same relative humidity level, a high rate of airflow produces higher static charges than a
low airflow rate.
c. Some data in this table has been extrapolated.
Static Protection Measures
Follow these precautions to minimize possible ESD-induced failures in the computer room:
Maintain recommended humidity level and airflow rates in the computer room
Install conductive flooring (conductive adhesive must be used when laying tiles)
Use conductive wax if waxed floors are necessary
Ensure that all equipment and flooring are properly grounded and are at the same ground potential
Use conductive tables and chairs
Use a grounded wrist strap (or other grounding method) when handling circuit boards
Store spare electronic modules in antistatic containers

Acoustics

Computer equipment and air conditioning blowers cause computer rooms to be noisy. Ambient noise level in a
computer room can be reduced as follows:
Dropped ceiling—Cover with a commercial grade of fire-resistant, acoustic rated, fiberglass ceiling tile
Sound deadening—Cover the walls with curtains or other sound deadening material
Removable partitions—Use foam rubber models for most effectiveness
30
a
Humidity
26%
6,150V
18,450V
24,600V
b
and Charge Levels (voltages)
32%
40%
5,750V
4,625V
17,250V
13,875V
23,000V
18,500V
c
50%
3,700V
11,100V
14,800V