5.9: RS-4 4 85 Connection—Nexus Meter to the Nexus P60N External Display
To connect the Nexus P60N Touch Screen External Display, use the Stand Alone Interface Cable
provided with the display. The cable is six (6) feet long with 20 AWG conductors (see detail
below). Insert one end of the supplied cable into Port 3 of the Nexus 1250/1252 Meter. Port 3 is
factory-set to match the Nexus Display's baud rate of 9600. To use a port other than Port 3, you
must set the port's baud rate to 9600 using the Communicator EXT software (see the
Communicator EXT User Manual). Insert the other end of the cable into the back of the Nexus
P60N Display. The connectors fit only one way into the ports.
Nexus P60N Display, Back View (Detail)
Top
Factory Test
Connector
Bottom
P60N Connection Color Key
LCD
Nexus
5 DCIN
V+
(12-30V DC)
4 (GND)
V-
3 (485+)
A(+)
2 (485-)
B(-)
1 (GND)
S
Figure 5.11: Nexus Meter Connected to Nexus P60N Touch Screen Display
Electro Industries/GaugeTech
Nexus P60N Display Port
Color
Pattern
Red
Black
White
Black
Silver
Doc # E107706 V1.25
Stand Alone Interface Cable
Nexus Meter Port 3
5-12