Electro Industries 1252 Installation And Operation Manual page 62

High performance scada monitor
Table of Contents

Advertisement

RS-232 Extension
Cable
(1 to 1 wiring)
RS-485 Master
Unicom or Modem Manager
R T=
~120 Ohms
+ V - S B(-) A(+)
Port 1
RS-232 or
RS-485 (Set)
RS-485
RS-232
NOTE: You may use ANY port to connect a Nexus Display or RS-485 Master. However, if you are using
the Internal Modem (or Network) Option, Port 2 is labeled Modem (Ethernet) Gateway. Ports 1, 3 and 4 DO
NOT change. The I/O Modules MUST use Port 4 (Port 3 is an alternate).
Nexus P40N, P41N or P43N Display is shipped programmed to use Port 3—see section 5.7 for
e
Electro Industries/GaugeTech
I/O Modules and Display
require power connections
to the +/- voltage terminals
(dashed lines).
Nexus P40N External Display
– + + G
R T=
~120 Ohms
R T=
~120 Ohms
+ V - S B(-) A(+)
Port 2
Normally Slave
Modem/Ethernet Gateway
Figure 5.4: Communication Wiring
Doc # E107706 V1.25
For all communications: S=Shield. This connection is
used to reference the Nexus port to the same
potential as the source. It is not an earth-ground
connection. You must also connect the shield to
earth-ground at one point.
A(+) B(-) S - V +
R T=
~120 Ohms
R T=
~120 Ohms
+ V - S B(-) A(+)
+ V - S B(-) A(+)
Port 3
Port 4
Nexus I/O Module
A(+) B(-) S - V +
R T=
~120 Ohms
8 7 6
5 4
3 2 1 C
High Speed Inputs IRIG-B
details.
-
+
5-4