3.2: Mounting the Nexus LED External Displays
The Nexus 1250/1252 LED Displays, Model # P40N, P41N and P43N, mount using a standard
ANSI C39.1 drill plan.
Secure the four mounting studs to the back of the panel with the supplied nuts.
Six feet of RS-485 communication/power cable harness is supplied. Allow for at least a 1.25-inch
(3.17cm) diameter hole in the back for the cable harness. See Chapter 5 for communication and
power supply details.
The cable harness brings power to the display from the Nexus 1250/1252 Meter, which supplies
15–20V DC. The P40N (or P41N or P43N) can draw up to 500 mA in display test mode.
Nexus P40N Display, Front View
ANSI C39.1 Drill Plan
Figure 3.3: Nexus P40N LED External Display Mounting Diagrams
Electro Industries/GaugeTech
4.38"Sq.
(11.12cm)
3.38" (8.58cm) Sq
Doc # E107706 V1.25
1.438"
(3.65cm)
Nexus P40N Display, Side View
.
4 X 0.198" (5.02mm)
+
1.687" (14.28cm)
.75" (19.05mm)