Download Print this page
Ei Electronics Ei186 Instructions

Ei Electronics Ei186 Instructions

Low voltage panel smoke & heat alarm
Hide thumbs Also See for Ei186:

Advertisement

Quick Links

RECOMMENDED LOCATIONS
READ THIS FIRST
Figure 2 illustrates where Smoke Alarms and Heat Alarms
CHECK OPERATION OF SYSTEM
should be located in a typical two storey house. Note the
spacings in "Recommended Protection" which ensure the early
TEST BUTTON OPERATES ON ALL ALARMS.
detection of fire and the warning will be heard.
ALL
INTERCONNECTED
ALARMS
OPERATE
Locate Heat Alarms in rooms adjoining or on escape routes -
WHEN EACH TEST BUTTON IS PRESSED FOR 10
kitchens, garages, boiler houses etc. where Smoke Alarms are
SECONDS.
unsuitable. Install within 5.3m (17 feet) of potential sources of
fire.
(EI181/184/186 ONLY) IF THE UNIT BEEPS EVERY
40 SECONDS FOR OVER 20 MINUTES THE
Recommended Protection
BATTERY IS PROBABLY DEPLETED. REMOVE
UNIT FROM CEILING (SEE FIG 1) AND REPLACE
BATTERY.
Minimum protection
Smoke Alarms located on:-
DO NOT ATTEMPT TO OPEN THE ALARM AS IT IS
each storey
PERMANENTLY SEALED FOR SAFETY.
every 7.5 metres (25ft) of hallways and
IF A NUISANCE ALARM OCCURS PRESS THE
escape routes
TEST/HUSH BUTTON TO SILENCE THE ALARM
Within 3m (10th) of all bedroom doors.
FOR 10 MINUTES.
- Interconnect all Alarms
UNIT WILL NOT FIT
ON THE MOUNTING
Maximum protection
PLATE WITHOUT A
BATTERY INSTALLED
Smoke Alarms located as above plus:-
(EI181/184/186 ONLY)
All rooms (except bathrooms, shower
TAMPERPROOF
MOUNTING PLATE
rooms & kitchens)
CATCH
SEALING
GASKET
Heat Alarms located in Kitchens, garages,
boiler rooms etc. Within 5.3m (17ft) of
CONTINUOUS
PUSH SCREWDRIVER
potential fire sources.
GREEN PANEL
STRAIGHT IN
POWER ON
TO RELEASE CATCH
LIGHT
Multi Storey Dwelling with Recommended Protection
SLIDE
OFF
(PUSH COVER BACK)
Fit both Ionisation &
Optical type alarms.
Ionisation -
Figure 1a
Best for fast flaming
fires.
Optical -
Best for smouldering
BASE
fires.
BATTERY
SNAPS
(EI181/184/186
ONLY)
4 WAY PLUG
ENGAGES SOCKET
ON MOUNTING PLATE
Figure 1b
TO CONNECT TO PANEL
AND
BATTERY
2
Single Storey Dwelling.
LOCATING ALARMS
If the Home is on one level (a bungalow or mobile home for
SMOKE ALARMS
example) you should put the first Smoke Alarm in a corridor or
Sufficient smoke must enter the Smoke Alarm before it will
hallway between the sleeping and living areas. Place it as near
respond. The Smoke Alarm needs to be within 7.5 metres (25
to the living area as possible, but make sure you can hear it
ft) of the fire to respond quickly. It also needs to be in a position
loudly enough to wake a person in the bedrooms. (for example,
where its alarm can be heard throughout your home, so it can
see figure 3) Single storey Dwelling with Recommended
wake the occupants in time for all to escape. A single Smoke
ProtectionSingle
Storey
Alarm will give some protection if it is properly installed, but
Protection
most homes will require two or more to ensure that a reliable
early warning is given. For maximum protection you should put
BEDROOM
individual Smoke Alarms in all the rooms where fire is most
likely to break out, (apart from kitchens, bathrooms etc. see
Locations to Avoid).
Figure 3
A Smoke Alarm should be located between the sleeping area
and the most likely sources of fire (living room or kitchen for
BEDROOM
example). It should not be more than 7.5 metres (25 ft) from the
door to any room where a fire might start on the escape route
from the house.
If the bungalow is very large and the corridor or hallway is more
Important: These Smoke/Heat Alarms are designed for a
than say 15 metres (50 ft) long, one Smoke Alarm will not be
single occupancy in a residential type environment.
sufficient. This is because no matter where it is located it will be
A Smoke Alarm should be sited within 3m of bedroom doors for
more than 7.5 metres from potential fires.
improved audibility.
In houses with more than one sleeping area, Smoke Alarms
HEAT ALARMS
should be placed between each sleeping area and the living
area.
The Heat Alarm gives a fire warning when the temperature at
the unit reaches 58°C. It is ideal for kitchens, garages, boiler
Multi Storey Dwellings
houses and other areas where there are normally high levels of
If the dwelling has more than one storey it must have an
fumes, smoke or dust i.e. places where Smoke Alarms cannot
interconnected alarm on each level for minimum protection.
be installed without the risk of excessive nuisance alarms.
Maximum Protection
A Heat Alarm should only be used in a room adjoining an
escape route, in conjunction with Smoke Alarms on the escape
For maximum protection you should put individual Smoke
routes.
Alarms in all the rooms where fire is most likely to break out
(apart from the locations to avoid, mentioned below). Ensure
All the Heat Alarms and Smoke Alarms should be
that they are all interconnected. The living room is the most
interconnected to ensure the early warning will be heard,
likely place for a fire to start at night, followed by the kitchen and
particularly by somebody sleeping. A properly designed early
then the dining room. You should also consider putting Smoke
warning fire system ensures the alarm is given before the
Alarms in any bedrooms where fires might occur, for instance,
escape routes become blocked with smoke. Therefore, there
where there is an electrical appliance such as an electric
must be Smoke Alarms along the escape routes as Heat
blanket or heater, or where the occupant is a smoker. You
Alarms would not give sufficient warning. However, a fire in a
could also consider putting Smoke Alarms in any rooms where
closed room (e.g. kitchen) adjoining the escape route, can
the occupant is unable to respond very well to a fire starting in
eventually cause the corridor to become smoke-logged due to
the room, such as an elderly or sick person or a very young
smoke leaking out from around the door before adequate
child.
warning can be given by detectors in the corridor. (Smoke
leaking out from a room is often cool and slow moving so it can
Fire Authorities (including the Home Office, UK) recommend
take a long time to rise to the ceiling, and travel to a detector
that both Optical and Ionisation Smoke Alarms should be
which could be some distance away). A Heat Alarm in the
fitted for the fastest response to all types of fires. An Optical
closed room will give early warning of fire in that room and help
Alarm should be located downstairs to detect slow smouldering
overcome this problem.
fires (e.g. from a cigarette burning in a couch or bedding,
3
overheated PVC wiring etc). An Ionisation Alarm should be
located upstairs to detect fast flaming fires (e.g. paper burning
in a container or a grease fire in the kitchen) which could rapidly
block the main escape route.
Checking you can hear the Smoke & Heat Alarms
With the Alarm sounding in its intended location, check you are
able to hear it in each bedroom with the door closed, above the
sound of the radio. The radio should be set to a reasonably loud
conversation level. If you can't hear it over your radio the
chances are that it wouldn't wake a person.
If a Smoke Alarm is too far away for it to wake a person, it is
best to interconnect to another Smoke Alarm or Heat Alarm
See Figures 2 & 3
near the bedroom, so when one alarm senses fire, all
interconnected alarms respond (see below for further details).
LOCATIONS TO AVOID
Don't place Smoke Alarms in any of the following areas:
• Bathrooms, kitchens, shower rooms, garages or other
rooms where the smoke alarm may be triggered by steam,
condensation, normal smoke or fumes. Keep at least 6
metres (20 feet) away from sources of smoke.
Don't place Heat Alarms in any of the following areas:
• Bathrooms, shower rooms or other room where the unit
may be triggered by steam or condensation.
Don't place Smoke or Heat Alarms in any of the following
areas:
• Places where the normal temperature can exceed 40°C
(104°F) or be below 4°C (39°F) e.g. attics, furnace rooms
etc. directly above ovens or kettles, as the heat/steam
could cause nuisance alarms.
• Near a decorative object, door, light fitting, window
Figures 2
moulding etc., that may prevent smoke or heat from
entering the Alarm.
• Surfaces that are normally warmer or colder than the rest of
the room (for example attic hatches, uninsulated exterior
walls etc). Temperature differences might stop smoke or
heat from reaching the unit.
• Next to or directly above heaters or air conditioning
vents, windows, wall vents etc. that can change the
direction of airflow.
• In very high or awkward areas (eg. over stairwells) where it
may be difficult to reach the alarm (for testing, hushing or
battery replacement).
• Locate away from very dusty or dirty areas as dust build-up
in the chamber can impair performance. It can also block the
insect screen mesh and prevent smoke from entering the
6
4
smoke detector chamber.
• Locate the unit at least 1 metre (3 feet) from dimmer
controlled lights and wiring - some dimmers can cause
interference.
• Locate unit at least 1.5m (5 feet) and route wiring at least 1m
(3 feet) away from fluorescent light fittings as electrical
"noise" and/or flickering may affect the unit.
Dwelling
with
Recommended
• Do not locate in insect infested areas. Small insects getting
into the smoke detector chamber can cause intermittent
alarms. Insects and contamination on the Heat Alarm sensor
can increase its response time.
KITCHEN
POSITIONING SMOKE/HEATALARMS
The locations must comply with applicable building regulations.
DINING
BEDROOM
Hot smoke rises and spreads out, so a central ceiling position is
the preferred location. The air is "dead" and does not move in
corners, therefore Smoke & Heat Alarms must be mounted
away from corners. Place the unit at least 300mm (12 inches)
from any light fitting or decorative object which might obstruct
smoke / heat entering the Alarm. Keep at least 300mm (12")
away from walls. See figure 4. (Smoke Alarms should be
located directly on the ceiling or up to 570mm below it. Heat
Alarms should be located directly on the ceiling or up to 90mm
below it).
Wall mounting is not recommended for these Alarms.
Sloping Ceiling
In areas with sloping or peaked ceilings install your
Smoke/Heat Alarm 90mm (3 feet) from the highest point
measured horizontally (see figure 5), because "dead air" at the
apex may prevent smoke from reaching the unit.
Figure 4
IDEAL FOR CENTRE
OF CEILING
DEAD AIR
SPACES
NEVER WITHIN
300mm OF ANY
WALL / CORNER
5
7
INTERCONNECTING SMOKE/HEAT
ALARMS
When a fire is sensed the alarm must be given throughout the
house. Up to twenty (20) Smoke Alarms (models EI 180, 181,
185, 186 only) and Heat Alarms (model EI 183, 184 only) can
be interconnected so that when one senses fire all alarm.
Caution: Do not interconnect to any other type of alarm.
The unit initiating the alarm can be identified by the red LED on
the cover flashing every second. Figure 6 shows the
interconnect wiring.
UNIT 1
UNIT 2
+
+
IC
IC
-
-
COMMON
COMMON
NO
NO
COMPATIBLE
NC
NC
10.5 - 30 VOLT
PANEL
+V
0V
NORMALLY
OPEN
CIRCUIT
INTERCONNECT
Figure 6a Circuit for Normally Open Relay Contacts
UNIT 1
UNIT 2
+
+
IC
IC
-
-
COMMON
COMMON
NO
NO
COMPATIBLE
NC
NC
10.5 - 30 VOLT
PANEL
+V
0V
NORMALLY
EOL
*
CLOSED
DEVICE
CIRCUIT
INTERCONNECT
*
EOL - ND
E
O L
F INE DEVICE, SPECIFIED BY PANEL
Figure 6b Circuit for Normally Closed Relay Contacts
Note: It is only necessary to wire one relay to the control panel.
If any alarm senses fire this relay will change state due to the
signal on the interconnect line.
These Alarms should be interconnected only within the
confines of a single family living unit. If they are interconnected
between different units there may be excessive nuisance
alarms. Everybody may not be aware that they are being tested
or that it is a nuisance alarm caused by cooking etc. When one
unit alarms all relays will switch.
Systems using more than 3 or 4 alarms must be very carefully
8
planned to ensure nuisance alarms are not excessive, e.g.
from cooking or weekly testing.
Smoke Alarm Locator Switch (EI 159) should be incorporated
into the system and be readily accessible to all occupants so
that the source of an alarm can be quickly identified. (see
Accessory section).
All Alarms must be cleaned and maintained regularly.
A competent person must be on call to quickly remove any
faulty alarms (i.e. units with red light flashing), which are
causing all alarms to sound.
INSTALLING SMOKE/HEAT ALARMS
The Alarm is designed to be permanently mounted , using it's
own built-in terminal blocks to connect it to the panel. The
mounting plate can be screwed directly to the ceiling after
connecting the wires.
IMPORTANT PRECAUTION: Do not install the actual alarm
itself in new or renovated buildings until all work is
completed (including floor coverings) and the building has
been fully cleaned. The wiring can be installed when
appropriate. (Excessive dust and debris from building
work can contaminate the smoke chamber or heat sensor
and cause problems, it will also invalidate the guarantee).
If it must be installed, cover it completely, particularly
around the edges, with a dust cover (eg. with the
elasticated cover supplied or a plastic bag), until all
cleaning is finished.
Warning: Wiring should only be installed by an Electrician in
accordance with current IEE wiring regulations for electrical
installation. The installation must also be in accordance with
the control panel instructions and the instructions in this leaflet.
Warning: The mains circuit used to power the control panel
must be a 24 hour voltage circuit and be wired on a separate
circuit (one with no other lights or applilances) to ensure
Figure 5
maximum reliability of the supply.
Warning: The Alarms must be connected to a panel that
supplies a permanent voltage that cannot be switched off.
Warning: For safety reasons the voltage supply from the
control panel must not be greater than 30V (peak or d.c.) and
900mm
must be either independent of the supply mains or isolated from
(3 ft)
it by double or reinforced insulations.
Warning: If the control panel is not provided with an ALL-POLE
MAINS SWITCH (with a contact specification of at least 3mm in
each pole), then the electrical installation of the building shall
incorporate an ALL-POLE MAINS SWITCH, (with a contact
separation of at least 3mm in each pole).
9
Pages 2 to 11
B14090 Rev-1
12/03/01
Installation
Select a location complying with the above advice.
1. Remove the mounting plate from the Smoke Heat Alarm by
releasing the tamper-proof catch with a small screwdriver as
shown in figure 1a and sliding the alarm from the plate.
2. Lift the foam flap covering the circuit on the mounting plate. If
necessary move the jumpers on S1 and/or S2 (see figure 7) by
carefully lifting them and placing them over the required pins.
3. If surface wiring the unit remove the required breakaways.
2
Low voltage signal cable is satisfactory (e.g. wire 0.22mm
)
provided the resistance between the units and the panel is less
than 20 ohms.
All wiring must comply with local codes. Connect the wires to
the terminals as shown in the wiring diagram (figure 6). The
gasket flap can be tucked behind the terminals while this is
being done. Place gasket flap back over circuit board and
terminals.
Figure 7a
P
C
MAIN
BREAKAWAYS
BREAKAWAYS
FOR
FOR
S1
SURFACE
STRAIGHT
MOUNTING
THROUGH
WIRING
COMMON
NO
P
C
NC
S1
NR
R
S2
+
IC
-
NR
R
SEALING
GASKET
FLAP FOLDED
S2
BACK
S1
POSITION C
RELAY ON CONTINUOUSLY WHEN IN ALARM (AS SUPPLIED)
POSITION P
RELAY PULSED FOR 5 SECONDS WHEN UNIT ALARMS
S2
POSITION NR
NO RESISTANCE IN SERIES WITH RELAY CONTACTS (AS SUPPLIED)
POSITION R
RESISTORS CONNECTED TO CONTACTS AS SHOWN BELOW
68K
R
C
NR
22K
NO
NC
Figure 7b
4. Carefully align the mounting plate and screw into place. With
recessed wiring, ensure the rear gasket seals around the edge
10
of the hole in the ceiling. This is to prevent air draughts affecting
the smoke / heat entering the alarm. If the orifice is too large it
should be sealed with silicone rubber or equivalent.
Check the battery is connected in the back of the alarm ( EI
181, 184, 186 only).
Carefully line up the unit on the base and slide on.
Press the test/hush button for 10 seconds. The horn should
sound (EI 181, 184, 186 only).
7. Connect the panel power to the alarm circuit. The green light
on the mounting plate should turn on.
Check the operation of the Alarm as outlined in the next
section.
CHECKING AND MOUNTING YOUR
ALARMS
INSPECTION & TESTING PROCEDURE
After installation, after re-occupation following a holiday, and
weekly, check all your Alarms as follows:
Check the green light is illuminated on the mounting plate. This
shows the panel is supplying power.
Press the test button for up to 10 seconds to ensure the
sensor chamber, electronics and sounder are working. A red
light on the cover will flash while horn is sounding. The relay
contacts should change over with the EI185, EI186 relay
contacts when the horn sounds with the EI180, EI181, EI183,
EI184, it contacts within 6 seconds after the horn sounds. The
alarm will stop when the button is released. Pressing the test
button simulates the effect of smoke or heat during a real fire
and is the best way to ensure the Alarm is operating correctly.
WARNING: DO NOT TEST WITH FLAME.
This can set fire to the Alarm and damage the house.
We do not recommend testing with smoke or heat as the results
can be misleading unless special apparatus is used.
Check for any sign of contamination such as cobwebs or dust
and clean the alarm as described below if necessary.
Interconnected alarms
Test the first unit by pressing the button. All the detectors
should alarm within about 5 seconds of the first horn sounding
and the red light on the first unit only will flash once a second.
The relay contacts should change over about 6 seconds after
the horns sound. Check all the other units similarly. (Note:
Ionisation and Heat alarms signal to other interconnected
alarms, about 4 seconds after their own horn sounds. Optical
alarms signal within about a second).
11

Advertisement

loading

Summary of Contents for Ei Electronics Ei186

  • Page 1 Figure 6 shows the chances are that it wouldn’t wake a person. interconnect wiring. If a Smoke Alarm is too far away for it to wake a person, it is best to interconnect to another Smoke Alarm or Heat Alarm UNIT 1...
  • Page 2 Clean the alarm as described in this booklet. (4) If the problem persists, resiting of the unit should be considered. Alternatively, replace the unit with an Optical unit (EI186/185), assuming that the problem is with an Ionisation type alarm (EI181/180). 2. ALARM SOUNDS FOR NO APPARENT REASON: (1) Identify the alarm source.

This manual is also suitable for:

Ei181Ei180Ei184Ei183Ei185