24SP200 SAFETY INTERLOCK SYSTEM (P/N 950-2420)
(For Millivolt and 24 Volt Control Systems only)
This Safety Interlock System may be used on conventional chimney or Power Vented appliances
equipped with a draft hood, draft diverter or draft control.
To provide a means for appliance shut-down in the event of flue blockage or down drafts.
The Spill Switch circuits are "normally closed" and will not affect normal appliance operation. When con-
centrated spillage of combustion gases occurs from the draft hood, diverter or barometric control, the
Spill Switch circuit will open preventing burner operation.
QUANTITY
DESCRIPTION
(2)
Spill Switches with manual reset, 200
(1)
Wire routing packet
(1)
8" jumper wire
(1)
6' 16/2 jacketed cable
1.
Shut off fuel supply to the appliance.
2.
Attach Spill Switches to draft hood (A1), diverter (A2) or barometric control (A3), see respective
diagram.
IMPORTANT:
Sensing area on underside of Spillage Switch should not come in direct contact with
metal surfaces. Sensing Switches should be mounted so they will sample temperature
of gas spilling from vent or chimney, not temperature of metal surface.
3.
Attach 8" jumper wire to inside terminals of draft spillage sensing switches.
4.
Attach leads of jacketed cable to outside terminals of spillage switches.
5a.
WATER HEATERS:
Millivolt water heaters require the Tjernlund Model JA-1 (P/N 950-0470), Thermocouple
Junction Adapter (ordered separately). Connect ends of six foot cable to spade connections on
Thermocouple Adapter, (See Diagram B1).
5b.
FURNACES AND BOILERS:
Splice ends of six foot cable in a series circuit between the thermostat and gas valve or burner
control, (See Diagram B2).
Using cable routing tabs from wire routing packet, attach 6' cable to appliance maintaining a
safe distance from hot surfaces, e.g. appliance vent pipe and hot water pipes.

PURPOSE

OPERATION

PARTS LIST

F set point
o

INSTALLATION

DIAGRAM A1
DIAGRAM A2
DIAGRAM A3
DIAGRAM B1
Spill Switch
Cables
DIAGRAM B2

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 950-2420 24SP200 SPILLAGE KIT 8504056 REV 1 0397 and is the answer not in the manual?

Questions and answers

Summary of Contents for TJERNLUND 950-2420 24SP200 SPILLAGE KIT 8504056 REV 1 0397

  • Page 1 Attach leads of jacketed cable to outside terminals of spillage switches. DIAGRAM B2 WATER HEATERS: Millivolt water heaters require the Tjernlund Model JA-1 (P/N 950-0470), Thermocouple Junction Adapter (ordered separately). Connect ends of six foot cable to spade connections on Thermocouple Adapter, (See Diagram B1).
  • Page 2 SERVICE PERSONNEL. Return all windows, doors and fans to their previous conditions of use. NOTE: For further assistance contact the Tjernlund Products, Inc. Customer Service Department at 1-800-255-4208. 7:30 AM-4:30 PM CST. OWNERS INSTRUCTIONS THESE INSTRUCTIONS MUST REMAIN WITH EQUIPMENT DO NOT DESTROY REV.

This manual is also suitable for:

950-2420

Table of Contents