Summary of Contents for Eaton 93T-120kVA

  • Page 1 Eaton ® 93T UPS 100-200 kVA Installation and Operation Manual...
  • Page 3 Thank you for choosing Eaton products! Please adhere to the warnings and instructions specified in the manual and on the equipment, and keep the manual properly for future reference. Do not try to operate the equipment before reading all the safety information...
  • Page 4: All Rights Reserved

    The contents of this manual are the copyright of the publisher and may not be reproduced (even extracts) without the written approval of Eaton Corporation. Every care has been taken to ensure the accuracy of the information contained in this manual, but no liability can be accepted for any errors or omission. The right to make design...
  • Page 5 一旦您使用产品软件,即表示您同意本协议的条款。 您使用产品软件的权利明确以您接受本协议为前提条件。 INFORMATION ABOUT US 关于我们的信息 1.1 EATON POWER QUALITY (SHANGHAI) CO., LTD. is registered in PRC and has its registered address at [B5, No. 76, Ribin Road, China (Shanghai) Pilot Free Trade Zone] (the “Contracting Entity”). 伊顿电源(上海)有限公司在中国注册(公司注册号[310115400090977]) ,其注册地址为[中国(上海)自由贸易试验区日滨 路76号B5部位](“缔约主体”)。...
  • Page 6 Product Software solely for your own internal business purposes; 指仅为您自身内部业务之目的,产品软件附带的或与产品软件一起提供的任何教程、用户指南和其他文 “文件” 件; “Eaton Hardware” means the Eaton product provided by Eaton to you, which may include Product Software within it; “伊顿硬件” 指由伊顿提供给您的伊顿产品,其中可能包括产品软件; “Eaton Open Source has the meaning as defined in Clause 10.1;...
  • Page 7 GRANT AND SCOPE OF LICENSE 许可的授予与范围 In consideration of you agreeing to abide by the terms of this Agreement, Eaton hereby grants to you, a limited, non-exclusive, non-transferable, non-sub-licensable, and revocable license to access and use the Product Software with the Eaton Hardware, which is provided to you for your own internal business purposes, solely for your use as permitted in these terms.
  • Page 8 和国际法律,包括与网络安全和盗版、数据保护、隐私、国际通信和技术或个人数据的传输有关的法律。 Eaton may make services available to you that are provided, in whole or in part, by other parties. Although Eaton may offer this opportunity, you acknowledge that any third party services that you use in connection with the Product Software are not part of the Product Software.
  • Page 9: Location Data

    必要设备 Full use of the Product Software is dependent upon your use of a device with Internet access and the purchase of Eaton Hardware in which it is installed or to which the Product Software pertains as described in the Documentation.
  • Page 10 司,复制、分发或以其他方式转让产品软件。 You may transfer the Product Software directly to a third party only in connection with the sale of the Eaton product in which it is installed or to which the Product Software pertains as described by Eaton in the Documentation. In the event of such a sale, you may not keep any copies of the Product Software or any portion thereof and you undertake to ensure the third party to whom you transfer the Product Software is made aware of, agrees to and complies with all of the provisions of this Agreement.
  • Page 11 Product Software in any way that is unlawful, fraudulent or deceptive, or has any unlawful, fraudulent or deceptive purpose or effect; 不以任何非法的、欺诈性的或欺骗性的方式使用产品软件,或具有任何非法的、欺诈性的或欺骗性的目的或效果; not use the Product Software except in conjunction with the operation of Eaton products to which the Product Software pertains or other products described by Eaton in the Documentation; 不使用该产品软件,除非与该产品软件相关的伊顿产品或伊顿在文件中描述的其他产品的操作相结合;...
  • Page 12 Eaton. Eaton shall not be liable for any costs, expenses or liabilities resulting from your failure to cooperate or to provide such information;...
  • Page 13: Third Party Software

    Third Party Licensor components or additional obligations by such Third Party Licensors that are not set forth in this Agreement, the terms of the license arrangement between Eaton and any such Third Party Licensor or the corresponding open source license will prevail.
  • Page 14: Open Source Software

    11.1 Where applicable, Eaton may charge you fees for access to the Product Software, as provided in Appendix 2. You agree to pay all fees and charges, within the agreed upon billing period, including taxes, incurred through your account at the rates in effect...
  • Page 15: Limitation Of Liability

    In no event shall Eaton nor any of its officers or other representatives be liable for any loss or damages...
  • Page 16 (whether arising out of liability under breach of contract, tort (including but not limited to negligence), misrepresentation, breach of statutory duty, breach of warranty or claims by third parties arising from any breach of this agreement) of Eaton or its...
  • Page 17 18.1 Eaton are not obligated to monitor the access or use of the Product Software, but Eaton reserves the right to do so for the purpose of operating the Product Software, to ensure compliance with these terms, and to comply with applicable law or other legal requirements.
  • Page 18 Agreement. You agree not to otherwise disclose such information to any third party without the prior written consent of Eaton. You shall be liable to Eaton for any breach of the confidentiality obligations in this Clause 20 of this Agreement by your employees.
  • Page 19 Eaton reserves the right, in its sole discretion and without notice to you, to suspend, terminate, modify or delete an account or access to the Product Software or parts thereof, if you are, or Eaton reasonably suspects that you are, failing to comply with any of the provisions of this Agreement or for any actual or suspected illegal or improper use of the Product Software.
  • Page 20 (together, “Third Party Links and Ads”). Such Third Party Links and Ads are not under Eaton’s control. Eaton disclaims all liability and responsibility for any Third Party Links and Ads and you acknowledge and agree that Eaton is not responsible or liable for: (a) the availability or accuracy of such Third Party Links and Ads;...
  • Page 21: Force Majeure

    You acknowledge and agree that Eaton is not liable for any loss or damage which may be incurred as a result of the availability of those external sites or resources, or as a result of any reliance placed by you on the completeness, accuracy or existence of any advertising, products or other materials on, or available from, such web sites or resources.
  • Page 22 Eaton’s failure to enforce a term of this Agreement is not a waiver of its right to do so later. No failure or delay by Eaton or its affiliates to exercise any right or enforce any obligation shall impair or be construed as a waiver or ongoing waiver of that or any other right or power.
  • Page 23 26.3 Eaton may terminate this Agreement with thirty (30) days’ prior written notice if Eaton may not deliver or grant access to the Product Software, Documentation and Materials to you due to an embargo or other comparable trade sanction, which is expected to be in place for six (6) months or longer.
  • Page 24 This Agreement (and any associated order form or other agreements referenced herein) constitutes the entire and exclusive agreement between you and Eaton with respect to the subject matter of this Agreement, and supersedes and replaces any other prior or contemporaneous agreements, or terms and conditions applicable to the subject matter of this Agreement. No provisions in your purchase orders, or in any other business forms employed by you, will supersede the terms and conditions of this Agreement.
  • Page 25 Eaton 93T 100-200 kVA UPS Installation and Operation Manual 30. CONTACT US 联系我们 Any questions regarding this Agreement should be directed to Eaton at: 关于本协议的任何问题,应向伊顿提出,地址是: Eaton 伊顿 Attn: IP Law Group 收件人:知识产权法组 1000 Eaton Boulevard 1000 Eaton Boulevard Mail Code 4N 邮件代码:4N...
  • Page 26 APPENDIX 1A 附录 1A Not applicable Third Party Software 不适用 第三方软件 APPENDIX 1B 附录 1B Not applicable Eaton Open Source Components 不适用 伊顿开源组件 Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 27: Table Of Contents

    Supported battery configurations ......................38 4.5. Wiring of the UPS Parallel System .........................38 4.5.1. Overview of power cables ........................38 4.5.2. Control signal overview ........................40 4.5.3. Installation of the parallel control wiring ....................41 Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 28 Monthly maintenance .........................76 7.2.3. Regular maintenance .........................78 7.2.4. Annual maintenance ...........................78 7.2.5. Battery maintenance ...........................78 7.3. Installation of Battery ............................78 7.4. Maintenance Training .............................79 Chapter 8 TECHNICAL INDICATORS OF PRODUCT ......................80 Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 29 8.2. Technical Indicators ............................80 8.2.1. Standard .............................80 8.2.2. UPS input ............................81 8.2.3. UPS output ............................81 8.2.4. Battery specifications ..........................82 8.2.5. Environment ............................82 Chapter 9 WARRANTY ................................84 Chapter 10 INSTALLATION CHECKLIST ...........................85 Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 30 Figure 6-14: History Log interface ............................56 Figure 6-15: Clear Log interface ..............................57 Figure 6-16: Info. interface 1 ..............................57 Figure 6-17: Info. interface 2 ..............................58 Figure 6-18: Password verification setting interface ........................59 Figure 6-19: Setting interface ..............................59 Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 31 Figure 6-37: Switch status in Maintenance Bypass Mode .......................74 Figure 6-38: Switch status in online mode..........................74 Figure 7-1: Location of 100–120k air filter screen ........................77 Figure 7-2: Location of 160–200k air filter screen ........................77 Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 32 Table 8-1: Gas concentrations recommended in Table B1 of ANSI/ISA-71.04-2013 for G1 equipment environment ..... 83 Table 8-2: Requirements on the environment for transportation and storage within 1 year ............83 Table 10-1: User Settings .................................87 Table 10-2: Configuration Settings ............................87 Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 33: Chapter 1 Safety Instructions Tions

    3) Do not place tools or metal parts on top of batteries; 4) Wear a rubber jacket and a pair of rubber boots. • Electrical energy is dangerous. Do not attempt to alter any battery wiring or other connecting wiring, as this may result in injury. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 34 Make sure that the forklift fork is inserted into the forklift slot at the horizontal position. Do not tilt the fork upwards. • Insert the forks all the way through the base. Damage to the wiring channels and wiring may be caused by failure to comply with these instructions. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 35: Certification

    The product has received EMC Directive 2004/108/EC certification: UPS EN 62040-1 (Safety) and EN 62040-2(EMC) standard declaration can be obtained via the website (http://powerquality.Eaton.com) or the local office of Eaton and licensed partners. 1.2. User Precautions The only user operations permitted are: •...
  • Page 36: Conventions Used In This Manual

    This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 37: Table 1-1: Acronyms And Abbreviations

    Emergency Power Off switch Maintenance Bypass Switch REPO Remote Emergency Power Off Advanced Battery Management HotSync HotSync wireless parallel technology Energy Saver System Input relay Battery relay Inverter relay Terminal block VRLA Valve-regulated lead-acid Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 38: Environment

    Obtaining information about regional service locations and their numbers. • For questions about anything in this manual. • For issues not covered in this manual. Please contact customer service via our 24-hour service hotline at 400-889-3938 Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 39: Chapter 2 Introduction

    The system was meticulously created by Eaton’s global team based on full consideration of the features of user loads, the environment of use, as well as the advanced technologies and abundant experience in power supply system design that Eaton has accumulated over the past five decades.
  • Page 40: Figure 2-2: Structure Of 100-120K Product

    Communication Interface Power (See Chapter 5 for details) module Door lock Dust net LOGO Power terminal block (See Chapter 3.3 for details) Bypass module Figure 2-2: Structure of 100-120K product Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 41: Figure 2-3: Structure Of 160K Product

    Interface (See Chapter 5 control panel for details) Power module Dust net door lock Logo Power terminal block (See Chapter 3.3 for details) Bypass module Figure 2-3: Structure of 160K product Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 42: Figure 2-4: Structure Of 200K Product

    Dust net door lock Power module Logo Power terminal block (See Chapter 3.3 for details) Bypass module Figure 2-4: Structure of 200K product WARNING Please wear insulating gloves when moving the switch. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 43: Internal Structure Of Ups System

    MBS. The UPS contains no internal battery. Please see Figure 2-5 .for the structure of the UPS cabinet. The power module includes rectifier, battery converter, inverter. Figure 2-5: 100K-120K Wiring Diagram Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 44: Figure 2-6: 160K-200K Wiring Diagram

    AC power supply recovers. In the case of long-time interruption of power supply, the UPS will allow switching to another power system (e.g., generator) or shut down the loads in sequence. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 45: Operation Modes Of The Ups

    AC power is within the acceptable voltage and frequency range. Online Mode Figure 2-7 indicates the route that the electric energy runs through the UPS system in Online mode. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 46: Figure 2-7: Route Of The Electric Energy Running Through The Ups In Online Mode

    UPS turns normal. In an external parallel redundant system, each UPS can be isolated from the system to facilitate maintenance, while other UPSs continue to supply power to the load in Online mode. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 47: Figure 2-8: Route Of The Electric Energy Running Through The Ups In Ess Mode

    Within 20–100% of the rated load, the system efficiency is as high as 99% in ESS mode. Internal relay contacts Figure 2-8: Route of the electric energy running through the UPS in ESS mode Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 48: Battery Mode

    Whenever AC power recovers again during the battery discharge, K1 will be closed, and the UPS will return to online operation mode. The UPS will start charging the battery to recover its capacity. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 49: Bypass Mode

    The static bypass is composed of a SCR and a SSW. When the inverter cannot support the load, the static switch will work continuously. As an electronic controller unit, the static switch can be enabled immediately to replace the inverter in supplying uninterrupted power to the load. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 50: Features Of The Ups

    2.3. Features of the UPS Eaton UPS has a variety of features to ensure cost effectiveness, and consistent and reliable power supply protection. This section will provide a brief summary about the standard features of the UPS. 2.3.1. Advanced Battery Management(ABM)
  • Page 51: Power Supply Management Software

    UPS power ratings. UPS cabinets can be connected in parallel to form a larger system. Parallel connection of 4 cabinets is supported. In the case of more than 4 cabinets, please contact Eaton’s solution team for a power distribution design.
  • Page 52: Chapter 3 Ups Installation Plan

    Installation Checklist). 7. Eaton customer service engineers will carry out preliminary operational inspections and startup. NOTE Commissioning must be carried out by the customer service engineers of Eaton, otherwise, the warranty provisions in Chapter 9 will become invalid. Provision of this service is part of the sales contract on the UPS.
  • Page 53: Site Preparations

    • The UPS shall normally operate at an altitude lower than 1,000m (3,300ft.). If it is to be used at an altitude over 2,000m (6,600ft.), please call at Eaton’s hotline for more information. • The warranty shall be invalid for failure to follow this guideline.
  • Page 54: Table 3-1: Dimensions And Weights

    When ignored, either one of these aspects can create an undesirable microclimate at the UPS location. If the environment created by this microclimate exceeds the Eaton UPS operating specification, the UPS reliability, over time, will be reduced. These same environmental extremes will also create reliability concerns for any servers that are exposed to them.
  • Page 55: Figure 3-1: Clearance For The Ups Cabinet

    * Wiring might need larger space. The picture takes a 120kW cabinet as an example Figure 3-1: Clearance for the UPS cabinet. • If D3 clearance available is smaller than 600mm, please contact Eaton service team. • Refer to Table 3-2 Figure 3-1 for clearance details.
  • Page 56: Figure 3-2: Ups Dimensions (100-120K)

    . . . 忐 i 志 志 - 850 - Right View Left View Front View 16.2 厂 — — 芒 467,6 Bottom View Figure 3-2: UPS dimensions (100–120k) Unit: mm Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 57: Figure 3-3: Ups Dimensions (160-200K)

    Eaton 93T 100-200 kVA UPS Installation and Operation Manual Top View Right View Front View Left View Bottom View Figure 3-3: UPS dimensions (160–200k) Unit: mm Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 58: Power Supply And Wiring Preparation Of The Ups System

    • When the N wire is disconnected, all phase lines shall be disconnected as well. The wire with appropriate size shall be used to facilitate future upgrade. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 59 A, B, C) (quantity and size) 1×120 1×150 1×185 1×240 Grounding 1.7 time Neutral wire (N) (AC/load) 1.7 times (nonlinear load) Electrical clearance upon breaking of contact: ≧2.0mm Backfeed protection device Break time: ≦15s Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 60: Table 3-4: Requirements On 100-120K Connecting Terminals And Torques

    15 (133) 60 mm²(M8) Battery (+) 15 (133) 60 mm²(M8) DC input Battery (-) 15 (133) 60 mm²(M8) Battery (N) 15 (133) 60 mm²(M8) User grounding Grounding 15 (133) 60 mm²(M8) Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 61: Table 3-5: Requirements On 160-200K Connecting Terminals And Torques

    The overcurrent protection switches for the bypass and output shall be provided by the customer. • For wiring diagram of the UPS, see Section Internal structure of UPS system. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 62: Preparation For Ups Interface Wiring

    The external alarm relay needs to connect with a switch with a rated current of 5A, a rated voltage of 30VAC (RMS)/30VDC. • The wire size of the external alarm relay shall not be smaller than 0.75 mm². Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 63: Chapter 4 Ups System Installation

    UPS and AC mains shall be provided by customers. The installation inspection and initial startup of the UPS shall be carried out by Eaton customer service engineers. Battery cabinets can be performed by qualified service personnel of the equipment manufacturer or agent.
  • Page 64 During the installation waiting period, the unpacked cabinet shall be protected against moisture, dust and other contaminants. The warranty does not cover any damages caused by failure to properly store or protect the UPS. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 65: Figure 4-1: 100-120K Unpacking Diagram

    3. Remove buffer material the ramp plate. loosen the anchor screws. Figure 4-1: 100–120k unpacking diagram Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 66: Figure 4-2: 160-200K Unpacking Diagram

    5. Install the ramp plate and angle iron fixed to the front push the cabinet down along and rear of the cabinet and the ramp plate. loosen the anchor screws. Figure 4-2: 160–200k unpacking diagram Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 67: System Installation

    Installation of external battery cabinet. WARNING Remember to lay the wires on both sides of the cabinet to prevent it from blocking the hot air venting area in the rear part. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 68: Bypass Input

    Bypass Input Output Main Input IP/OP/BAT N Figure 4-3: Gland Plate and Connector Locations (100–120k) Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 69: Figure 4-4: Locations Of Cover Plate And Connecting Terminals (160-200K)

    Eaton 93T 100-200 kVA UPS Installation and Operation Manual Bypass Input IP/OP/BAT N Output Main input Figure 4-4: Locations of cover plate and connecting terminals (160–200k) Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 70: Installation Of External Battery Cabinet

    5. Please see the instructions of the manufacturer regarding the battery cabinet. WARNING Ensure correct connection of the positive and negative poles of the battery! Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 71: Supported Battery Configurations

    4.5. Wiring of the UPS Parallel System The rated power of each UPS must be identical, and the rated power of each equipment’s static bypass shall also be identical. If exceeding the specified quantity, please contact Eaton’s solution team for a power distribution design.
  • Page 72: Battery Connection

    Ensure that the static bypass input of each UPS in the parallel system is the same common point, like an external bypass circuit breaker. If the rectifier input of each UPS in the parallel system is a separate power source, please consult Eaton engineers to ensure the compatibility of power distribution.
  • Page 73: Control Signal Overview

    Each UPS bears 3 sets of signal inputs which can configure the functions. These functions may affect the UPS in every system. Wiring of the parallel EPO switch It’s recommended that each parallel unit uses a separate EPO circuit. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 74: Installation Of The Parallel Control Wiring

    Figure 4-6 represents the parallel wiring diagram and not the physical layout plan. UPS can be arranged in any physical order. • The connection cables used among parallel UPS units shall be of shielded twisted-pair cables. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 75: Chapter 5 Communication Interfaces

    ④ : CN12 - This standard function can be used to connect the external alarm signal to the corresponding termi- nals of the UPS, e.g., smoke alarm or overheat alarm signal. Please use twisted-pair wires to connect the alarm device and the corresponding UPS terminals. For external alarm signal configuration, please consult Eaton’s ser- vice personnel.
  • Page 76 ⑧ : 1. Upon a slight touch of the button, the auxiliary battery power supply will be activated. 2. If the output of the UPS is hot(online mode/ESS mode), press the button for 10s, the UPS will transfer to bypass. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 77: Mini-Slots

    2 additional digital inputs. Warning limits for temperature and humidity can be configured in the network card and monitored in a real-time manner with Eaton’s IPM and IPP software. Temperature compensation for lead-acid battery can be achieved as well.
  • Page 78: Figure 5-4: Industrial Gateway Card

    • Industrial Gateway Card Eaton Industrial Gateway Card is integrated with many functions of SNMP card, for example, the functions of SNMP agent, HTTP/Web server, and Modbus card. Combined with Building Management System (BMS), it can provide continuous, reliable and accurate remote monitoring service to the UPS system. The user can define remote power-off, uninstallation and other tasks, and receive the system alerts from the UPS in real-time and remotely.
  • Page 79: Intelligent Power Manager (Ipm) Software

    IPM can perform remote monitoring and manage the UPS. IPM allows the user to check the power equipment within an international enterprise through a PC. The software supports monitoring of single and multiple (if web-based) Eaton UPS systems or other brands, intelligent power distribution units (ePDUs), other power and environment devices, and supports virtual environments.
  • Page 80: Chapter 6 Ups Operating Instructions

    Before UPS startup, please make sure that all installation work has been completed, and that the initial startup has been performed by Eaton’s customer service engineers. Before the initial startup, check all electrical connections to ensure successful installation and normal operation of the system.
  • Page 81: Figure 6-1: Ups Controls And Indicators

    Installation and Operation Manual The picture takes a 100kW cabinet as an example 二 UPS status indicator lamp Control panel 、93T 召A节忙] Figure 6-1: UPS Controls and Indicators 。 bl!, 上:3 Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 82: Use Of Lcd Control Panel

    System status indicator lamps: The status indicator lamps on the UPS control panel inform the operator of the current status of the UPS in the form of lights, similar to the event buzzer Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 83: Use Of Touch Screen

    Those areas will be discussed in the following sections. Figure 6-2: Components of the touch screen (Home interface) A. In the UPS status area, the model of the Eaton equipment, current date, time, and active log information are displayed.
  • Page 84: Meters

    (per phase), input power (per phase), and total frequency as well as total kVA, total kW, and power factor measurements of the bypass. The “Battery” screen displays the battery voltage, cell voltage, battery current, and Battery more. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 85: Figure 6-4: Input Interface

    Eaton 93T 100-200 kVA UPS Installation and Operation Manual Figure 6-4: Input interface Figure 6-5: Output interface Figure 6-6: Bypass interface Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 86: System Control Instructions

    ESS, or disable ESS disable. When the button is gray, it indicates that this button is currently null. On the top of the interface, you can view the UPS status and battery Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 87: Figure 6-9: System Interface

    Click “OK” button to switch to the bypass mode, as shown in Figure 6-10 . It is the same for other button functions. Figure 6-9: System interface Figure 6-10: Switch to bypass interface Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 88: Figure 6-11: Confirmation Interface

    For the operating methods of the function buttons on this interface, please refer to the method for switching to the bypass mode. Figure 6-12: UPS interface Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 89: Use Of Log Menu

    On the “Clear Log” screen, you can clear all the alert information on the “Active Log” Clear Log interface. Figure 6-13: Active Log interface Figure 6-14: History Log interface Click “Clear All Active Logs” button on the interface, then all active logs will be removed. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 90: Use Of Info. Menu

    Click the Info. button on the menu to enter the Info. interface. On the Info. interface, you can view the UPS name, serial No., UPM version, HMI version, and other information. The interfaces of Figure 6-16 Figure 6-17 Info. are shown in Figure 6-16: Info. interface 1 Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 91: Use Of Setting Menu

    Control password The initial password is “11111111”, which can be used to enter the control interface. Setting password The initial password is “01010101”, which can be used to enter the Setting interface. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 92: Figure 6-18: Password Verification Setting Interface

    Figure 6-18: Password verification setting interface Figure 6-19: Setting interface Figure 6-20: Setting - General interface Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 93: Figure 6-21: Setting - General - Time Interface

    Save button. Click the Cancel button to return to the “General” interface. The method can be used to set other parameters. Figure 6-21: Setting - General - Time interface Figure 6-22: Setting - Output interface Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 94: Figure 6-23: Setting - Meters Interface

    Figure 6-27 . If a wrong password is entered, “Wrong password” will be prompted on the interface, which means that you need to Figure 6-28 re-enter a password, as shown in Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 95: Figure 6-25: Control Password Modification Interface

    Eaton 93T 100-200 kVA UPS Installation and Operation Manual Figure 6-25: Control password modification interface Figure 6-26: Control password modification interface Figure 6-27: Control password modification interface Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 96: Use Of Service Reminder Function

    Figure 6-29: Setting password modification interface 6.2.10. Use of service reminder function When a service expires, the “Service Maintenance Reminder” button will pop up on the Home Figure 6-30 interface, as shown in Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 97: Figure 6-30: Service Maintenance Reminder Interface

    Click the “Learn more” button to see the detail tips. Figure 6-31: Service maintenance reminder setting interface Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 98: Figure 6-32: Location Of Service Reminder Function

    When the setting is completed and the “Save” button is clicked, the reminder date and enable/disable status will appear on the interface. The operation method is the same for the other three service reminder pages. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 99: System Operation

    9. Press the “Start” button on the “System Control” page. If automatic bypass is enabled, the power will be supplied to the critical load via the bypass immediately, the UPS will run Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 100: Start The Ups In "Bypass" Mode

    When the UPS is in “Bypass” mode, the critical load is not protected if any bypass interruption or exception occurs. 1. Click the “Control” button on the main page to switch to the “System Control” page. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 101: Switch From "Bypass" Mode To "Online" Mode

    Tip: "ESS" is displayed only if the Advanced Energy Saving Solution (ESS) mode feature is enabled by the facility or service personnel. The load switches to “Online” mode: 1. Select “Control” on the menu, and enter the password to access the control interface; Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 102: System Shutdown

    7. Turn off the UPS maintenance bypass switch; 8. Turn off the UPS input and bypass distribution switch; 9. If any external battery box is mounted, please turn off all battery switches (including battery Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 103: Single-Ups Operation

    1. Click the “Control” button on the main page to switch to the “System Control” page; 2. Press the “UPS Control” button on the “System Control” page; 3. Click “Shutdown” on the “UPS Control” page. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 104 1. Click the “Control” button on the main page to switch to the “System Control” page; 2. Press the “UPS Control” button on the “System Control” page; 3. Press “Charger On” or “Charger Off” on the “UPS Control” page. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 105: Use Of Remote Emergency Power Off (Repo) Switch

    UPS output. NOTE Below are the instructions about Eaton REPO switch. In the case of REPO switch provided by the customer, the activation method might be different. Please see the operation instructions delivered together with the switch.
  • Page 106: Transfer The Ups From Double Conversion Mode To Maintenance Bypass Mode

    Maintenance bypass switch (MBS) Output switch Maintenance bypass input Figure 6-36: Switch status in maintenance bypass mode Static bypass input Maintenance bypass switch (MBS) Output Maintenance bypass input Copyright © 2024 Eaton Corporation plc. All rights reserved. Static bypass input...
  • Page 107: Switch From "Maintenance Bypass" Mode To "Online" Mode

    Rectifier input UPS operation in “Online Mode” Output switch Maintenance bypass switch (MBS) Maintenance bypass input Static bypass input Output Rectifier input Output switch Figure 6-38: Switch status in online mode Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 108: Chapter 7 Ups Maintenance

    UPS module. WARNING • The maintenance shall be performed by Eaton customer service engineers. • The voltage is lethal. Stop using the UPS when the cabinet door is opened or the protective plate is removed.
  • Page 109: Carry Out Preventive Maintenance

    Remove the filter screen from the front panel and clean it, or replace it with a new one. d. Install front plate and lock screws. 3. Log the results of the check and any corrections. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 110: Figure 7-1: Location Of 100-120K Air Filter Screen

    Air filter screen Figure 7-1: Location of 100–120k air filter screen Air filter screen Figure 7-2: Location of 160–200k air filter screen Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 111: Regular Maintenance

    Pay special attention to the wire crimping terminals, and fasten them during maintenance. 7.2.4. Annual maintenance The annual preventive maintenance shall only be performed by Eaton customer service engineers who are familiar with UPS system maintenance. For more information about maintenance items, please contact your customer service representative. 7.2.5.
  • Page 112: Maintenance Training

    7.4. Maintenance Training Eaton provides basic training courses to help users grasp UPS operation knowledge and the method for preliminary corrective maintenance. Please contact the customer service representative for detailed information of training and other services.
  • Page 113: Chapter 8 Technical Indicators Of Product

    IEC 61000-4-8 (Power frequency magnetic field) IEC 61000-4-11(Voltage dips and Voltage interruptions) Performance & Tests IEC 62040-3 2011 Environmental IEC 62430 RoHS 2002/95/EC WEEE 2002/96/EC ECO Design Directive 2009/125/EC Batteries 2006/66/EC Packing: 94/62/EC Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 114: Ups Input

    126–150% load 1min; >151% load 150ms. Output current See Table 3-3 : Rated current at rated power and voltage Rated load power factor Load power factor (allowed) Lag 0.5 to lead 0.7 Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 115: Battery Specifications

    , and meet the requirements (see ) on the transportation and storage environment for 1 year. • Please do not place the equipment in environment with extreme humidity and temperature Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 116: Table 8-2: Requirements On The Environment For Transportation And Storage Within 1 Year

    Stored with initial packaging Others If the actual storage conditions of the machine do not meet the above storage environment, re- evaluate the storage time according to the actual storage environment. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 117: Chapter 9 Warranty

    WARRANTY Commitment of Eaton: Eaton provides 24 months of warranty starting from the date of startup of the equipment (which shall be performed by Eaton or the engineer authorized by Eaton within 3 months after delivery), or subject to the agreement.
  • Page 118: Chapter 10 Installation Checklist

    The air-conditioning device has been installed and its operation is normal.  The surrounding area of the UPS’ installation site shall be clean and free of dust. (Eaton recommends that the UPS is  installed on a level floor suitable for computer or electronic equipment).
  • Page 119: Parallel System Installation Checklist

     There is adequate workspace around the UPS and other cabinets.  The startup and operational inspection of the parallel system or accessory case shall be performed by Eaton customer  service engineers. The positive, negative and neutral wires of the battery shall be installed correctly and properly.
  • Page 120: Table 10-1: User Settings

    1 disabled NTP clock setting. Screen saver interval 10min, non-configurable. HMI backlight Adjust the backlight brightness. Configuration of “setting password” The default password is 01010101. Configuration of “control password” The default password is 11111111. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 121 . . Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 123 614-40277-00...