olympia electronics GR-1938/4P Quick Start Manual

Waterproof self testing maintained/non maintained emergency luminaire

Advertisement

Quick Links

Package Contents
1
Luminaire
Pictograms (R/L/D)
3
1
Mounting accessories
1
Manual
General
These devices are used in places where emergency light is needed. Each device must be
permanently connected to mains power supply. In normal operation the battery is charging.
In case of a mains power supply failure, the device enters emergency mode and the
illumination LED turns on. When the mains power supply is restored the device turns to
normal operation.
Manual Operational Test
An operational test is initiated by placing the test card beside the indicators and removing it
instantly. The light source and the emergency circuit of the device are tested. The manual test
can be conducted only if the mains power supply and the battery are connected. During this
test period, the light source turns on, and all indication LEDs are OFF. The battery must have
adequate charge. This test lasts for 3 seconds.
Automatic Operational Test
This test includes all the operations that are provided in Manual Operational Test and is
conducted automatically every 15 days and lasts 3 seconds.
Automatic Autonomy Test
The Automatic Autonomy Test is conducted every 6 months and measures the device's
backup operation and emergency duration. In order to be performed, the mains power
supply and the battery should be connected and fully charged. If the battery is not fully
charged, the test is postponed until the battery is completely charged. If during this test, the
autonomy is less than nominal, then the battery fault LED turns on continuously, and the
battery must be replaced.
Resetting Errors
Place the test card A-1900 beside the indicators (page 4) and remove it after the reset is
conducted (the indicators light in sequence) to clear all indicated LED errors. Then, the
luminaire enters regular operation mode.
ΑΤΤΕΝΤΙΟΝ!!!
1. Operations for installation, maintainance or testing must be done by authorized personnel
only.
2. Always use in any case round mains cable, with a diameter of 5-10mm (H05RN-F type
2x1mm² or any other type, at least equal to it's mechanical and electrical properties).
ATTENTION!! The cable must not be deformed in any way (This requirement is important to
ensure the ΙΡ rating).
3. The device must be connected to the mains power supply through a circuit breaker that is
depends on the total line's power load.
4. In case of battery replacement, it must be replaced by the same type, by the manufacturer
or a competent person.
5. In case of inactive use for a period greater than 2 months, disconnect the battery by pulling
out the battery's connector.
6. It is not allowed to discard batteries into common trash bins, they must be discarded
only in battery recycling points. Do not incinerate.
Indications LED Status
GREEN
RED
RED
Description
(charge)
(Lamp Fault)
(Bat. Fault)
Good charge condition
Mains off
(battery not connected or charger fault)
Autonomy or low battery problem
No charging current or disconnected battery
Light Source Fault (with light source off)
Problem in the light source (with light source on)
Note:
Permanently ON
1
Installation
To dismantle the luminaire, simply remove the difussor.
ATTENTION! If the 2 plastic latches (A) are clipped, carefully insert a flat-blade screwdriver to
unclip them. Then, gently lift the diffuser (B) upwards to detach it.
1
Place a flat blade screwdriver to the recesses (A) and pull up gently the reflector (B) to remove it.
2
Install the two rubber gaskets to the holes of the base. Make sure that they are not deformed.
3
Wall Plug
Install the plastic base (with the included mounting accessories).
WARNING!! To preserve the IP65 rating, fit the screws with the metallic washers and rubber
sealing rings.
4
Blink
Off
Non relevant
2
923193903_09_005
Α
Β
Α
Α
Α
Β
Rubber
Screw
Sealing Ring
Washer
Controlled operation of the lamp
N
L
External
N
Switch
L
L1
Make a hole in the center of the rubber gasket by using a small screwdriver. Pass the
round cable through the rubber gasket. Connect the mains cable according to the
connections diagrams above. Ν for neutral, L for live wire WARNING!! Isolate the mains
power supply before making the connections.
5
6
7
Refit the reflector and then the diffusor, which were removed in steps 1 & 2. Mind the
holes of the indications.
8
Β
The plastic latches (A) must be secured (click sound).
Fasten the 2 screws (B). (Tightening torque 1.2N*m)
9
NOTE!!
After finishing the installation you must power the luminaire for at least 24 hours in
order to completely charge the battery. The rated autonomy duration can be achieved
after that time.
3
923193903_09_005
Permanent maintained operation
N
L
N
L
Link
L1
Install the included tie-wrap to the
adhesive tether loop and fasten securely
the power cable in order to anchor it.
Place the battery's connector to the
corresponding connector on the PCB.
Α
Β
Α
923193903_09_005

Advertisement

loading
Need help?

Need help?

Do you have a question about the GR-1938/4P and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for olympia electronics GR-1938/4P

  • Page 1 Package Contents Installation Luminaire Pictograms (R/L/D) Mounting accessories Manual General Α These devices are used in places where emergency light is needed. Each device must be permanently connected to mains power supply. In normal operation the battery is charging. Β Controlled operation of the lamp Permanent maintained operation In case of a mains power supply failure, the device enters emergency mode and the...
  • Page 2 X: Self contained replacement, as long as the warranty period is valid. 1: Maintained/Non maintained operation (*) Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the A: Including test device MAINTAINED/NON MAINTAINED buyer depending on the reason of defection.

This manual is also suitable for:

Gr-1939/4pGr-1938/6pGr-1939/6p