Eastron SMART X96-5A-MT User Manual
Eastron SMART X96-5A-MT User Manual

Eastron SMART X96-5A-MT User Manual

Smart energy analyzer for single and three phase electrical systems

Advertisement

Quick Links

SMART X96-5A-MT
Smart Energy Analyzer for Single and Three Phase Electrical Systems
Measures kWh, kVarh, kW, kVar, kVA, P,
F, PF, Hz, dmd, V, A, etc.
Bi-directional Measurement IMP & EXP
Energy Information of Each Phase
Two Pulse Outputs
RS485 Modbus RTU
Total Harmonic Distortion of Voltage and Current
2nd~63rd Individual Harmonic Distortion
Backlit LCD Display for Full Viewing Angles
Class B , Class C
Bar Graph for Power Indication
Dimension 96x96mm
5A CT connection
Multi-tariff
EASTRON SMART X96-5A-MT User Manual V1.5

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SMART X96-5A-MT and is the answer not in the manual?

Questions and answers

Summary of Contents for Eastron SMART X96-5A-MT

  • Page 1 EASTRON SMART X96-5A-MT User Manual V1.5 SMART X96-5A-MT Smart Energy Analyzer for Single and Three Phase Electrical Systems ● Measures kWh, kVarh, kW, kVar, kVA, P, F, PF, Hz, dmd, V, A, etc. ● Bi-directional Measurement IMP & EXP ●...
  • Page 2: Unit Characteristics

    This document provides operating, maintenance and installation instructions for the Eastron SMART X96 series. The unit measures and displays the characteristics of single phase two wire, three phase three wire and three phase four wire supplies, including voltage, frequency, current, power and active and reactive energy, imported or exported, Harmonic, Power factor, Max.
  • Page 3: Pulse Output

    EASTRON SMART X96-5A-MT User Manual V1.5 1.4 RS485 Serial-Modbus RTU This unit uses a RS485 serial port with Modbus RTU protocol to provide a means of remote monitoring and controlling. Please check the Part 4.2 for the details of setting.
  • Page 4: Buttons And Displays

    EASTRON SMART X96-5A-MT User Manual V1.5 3. Buttons and Displays 3.1 Buttons Function Buttons Click Press 2S ➢ ➢ Displays power, voltage, current and energy Automatic Scroll display ON / OFF information of each phase ➢ Escape the menu ➢...
  • Page 5 EASTRON SMART X96-5A-MT User Manual V1.5 Phase 1 – Power Phase 1 – Power Phase 1 – Power Voltage Voltage Voltage Current Current Current kVarh kVarh kVarh Phase 2 – Power Phase 2 – Power Voltage Voltage Current Current kVarh kVarh Phase 3 –...
  • Page 6 EASTRON SMART X96-5A-MT User Manual V1.5 Reactive Power L1 Reactive Power L1 Reactive Power L2 Reactive Power L2 Reactive Power L3 Reactive Power L3 Apparent Power L1 Apparent Power L1 Apparent Power L2 Apparent Power L2 Apparent Power L3 Apparent Power L3...
  • Page 7 EASTRON SMART X96-5A-MT User Manual V1.5 4. Setting-Up...
  • Page 8: Password Entry

    EASTRON SMART X96-5A-MT User Manual V1.5 4.1 Password Entry Setting-up mode is password protected, so you must enter the correct password. By firmly press the button for 2 seconds, the password screen appears. The default password is 1000. If an incorrect password is entered, the display shows ERR.
  • Page 9 EASTRON SMART X96-5A-MT User Manual V1.5 Example shows: SET Baud rate 19200 (bps) And long press for confirmation. 4.2.3 Parity Parity Options: NONE, EVEN, ODD. Default Parity : NONE Note that if parity is set to ODD or EVEN, Stop Bits will be set to 1 and cannot be changed.
  • Page 10 EASTRON SMART X96-5A-MT User Manual V1.5 4.2.4 Stop bit Stop Bit options: 1 or 2. Default Stop Bit : 1 Note that if parity is set to ODD or EVEN, Stop Bits will be set to 1 and cannot be changed.
  • Page 11 EASTRON SMART X96-5A-MT User Manual V1.5 Example shows : Set CT2 1A And long press for confirmation. 4.3.2 CT1 Set primary current input the meter Options: 1~9999 Default CT1: 5A Long press to enter the CT1 routine. Press for 2s, the CT1 setting will flash.
  • Page 12 EASTRON SMART X96-5A-MT User Manual V1.5 4.4.1 PT2 Set secondary voltage input the meter Range: 100V ~ 480V Default: 230V And long press for confirmation. 4.4.2 PT1 Set primary voltage input the meter Range: 174V ~ 500000V Default: 400V Then press to enter the PT2 routine.
  • Page 13 EASTRON SMART X96-5A-MT User Manual V1.5 4.5.1 Pulse output1 Pulse output 1 setting Output type options: total kwh, import kwh, export kwh, total kVarh, import kVarh, Export kVarh. Default: total kWh Long press to enter the PT Pulse Output 1 routine.
  • Page 14: Pulse Duration

    EASTRON SMART X96-5A-MT User Manual V1.5 4.5.3 Pulse Duration Pulse Duration time option 200, 100, 60mS Default : 100mS to enter Pulse duration routine. Long press , the setting will flash. Use to choose Options. And long press confirmation. Press to return the Pulse Duration set up menu.
  • Page 15 EASTRON SMART X96-5A-MT User Manual V1.5 4.6.1 Demand interval time The screen will show the currently selected integration time. Default is 60 Long press to enter the DIT routine. Press for 2s, the setting will flash. Use to choose Options. And long press confirmation.
  • Page 16: Backlight Time

    EASTRON SMART X96-5A-MT User Manual V1.5 4.7.1 Backlight time The meter provides a function to set the backlit lasting time. Options: ON/OFF/5/10/30/60/120 minutes. Default: 60 If it is seated as 5, the backlit will be off in 5 minutes. Note: if it is set as ON, the backlit will always be on.
  • Page 17 EASTRON SMART X96-5A-MT User Manual V1.5 Set the time of RTC Left picture shows 16:20:58 The format is HH-MM-SS 4.7.4 Tariff Time This option is to set the time segments with different tariffs. By pressing the , to get into the time segments and tariffs setting.
  • Page 18: System Connect

    EASTRON SMART X96-5A-MT User Manual V1.5 4.8.1 System type The screen shows the currently selected power supply is three phase four wire Long press to enter the System type routine. Press for 2s, the setting will flash. Use to choose Options.
  • Page 19: Change Password

    EASTRON SMART X96-5A-MT User Manual V1.5 Options: Frd ( forward ) and rEv ( reverse) The default is FRD ( forward ) Long press to enter the Phase 1 correction. Press for 2s, the setting will flash. Use to choose Options. And long press for confirmation.
  • Page 20 EASTRON SMART X96-5A-MT User Manual V1.5 4.8.4 Automatic display scroll This unit provides a function with automatic display scroll setting. Options: on and off There are two ways: ① Use to select the automatic display scroll option. Press for 2s, the setting will flash. Use to choose options “On”...
  • Page 21: Specification

    EASTRON SMART X96-5A-MT User Manual V1.5 Long press to enter the Energy routine. Press for 2s, the setting will flash, then long press to confirm the reset. Then press enter Demand Reset routine. Press for 2s, the setting will flash, then long press to confirm the reset.
  • Page 22 EASTRON SMART X96-5A-MT User Manual V1.5 Volt-amps 0 to 9999 MVA Maximum demanded power since last Demand reset Power factor Maximum demand current, since the last Demand reset (three phase supplies only) 5.1.3 Energy Measurements Imported active energy 0 to 9999999.9 kWh Exported active energy 0 to 9999999.9 kWh...
  • Page 23 EASTRON SMART X96-5A-MT User Manual V1.5 5.4.2 Modbus RTU Interface standard and protocol: RS485 and MODBUS RTU Communication address: 1~247 Transmission mode: Half duplex Data type: Floating point Transmission distance: 1000m Maximum Transmission speed: 2400bps~38400bps Parity: None (default), Odd, Even Stop bits: 1 or 2 Response time: <100 mS...
  • Page 24: Emc Installation Requirements

    EASTRON SMART X96-5A-MT User Manual V1.5 7 Installation The unit may be mounted in a panel of any thickness up to a maximum of 3 mm. Leave enough space behind the instrument to allow for bends in the connection cables. The unit is intended for use in a reasonably stable ambient temperature within the range -25°C to +55°C.
  • Page 25 EASTRON SMART X96-5A-MT User Manual V1.5 for such auxiliary circuits must be rated for the highest voltage connected to the instrument and suitable for single fault condition. The connection at the remote end of such auxiliary circuits should not be accessible in normal use. Depending on application, equipment connected to auxiliary circuits may vary widely.
  • Page 26 EASTRON SMART X96-5A-MT User Manual V1.5 9. Wiring Diagram (3 phase 4 wires)
  • Page 27 EASTRON SMART X96-5A-MT User Manual V1.5 (3 phase 3 wires) (1 phase 2 wires)
  • Page 28 EASTRON SMART X96-5A-MT User Manual V1.5 Zhejiang Eastron Electronic Co.,Ltd. No.1369,Chengnan Rd. Jiaxing, Zhejiang, 314001, China Tel: +86-573-83698881 83698882 Fax: +86-573-83698883 Email: sales@eastrongroup.com www.eastron.com.cn www.eastrongroup.com...