Three phase multifunction din rail meter (47 pages)
Summary of Contents for Eastron SMART X96-RC
Page 1
EASTRON SMART X96-RC User Manual __________________________________________________________________________________________________ ___06-2018 V1.0 SMART X96-RC MULTIFUNCTION POWER ANALYSER WITH ROGOWSKI COIL ● No need external integrator ● Multi-parameter Measurements ● 3 selectable current scales ● RS485 Modbus RTU ● Accuracy Class 0.5s ● Bar Graph for Power Indication ●...
Built-in interfaces provides RS485 Modbus RTU. SMART X96-RC series is a top new-generation intelligent panel meter with , used not only in the electricity transmission and power distribution system, but also in the power consumption measurement and analysis in high voltage intelligent power grid.
Page 3
EASTRON SMART X96-RC User Manual __________________________________________________________________________________________________ ___06-2018 V1.0 This unit uses a RS485 serial port with Modbus RTU protocol to provide a means of remote monitoring and controlling. Please check the Part 4.2 for the details of setting. 1.5 Display...
EASTRON SMART X96-RC User Manual __________________________________________________________________________________________________ ___06-2018 V1.0 2.Start up screens The first screen lights all LED segments and can be used as a display LED check The second screen indicates the software version of the unit. (the left picture is just for reference) The unit performs a self-test and the screen indicates if the test is passed.
EASTRON SMART X96-RC User Manual __________________________________________________________________________________________________ ___06-2018 V1.0 3. Buttons and Displays 3.1 Buttons Function Buttons Click Press 2S ➢ ➢ Displays power, voltage, current and Automatic Scroll display ON / OFF energy information of each phase ➢ Exit from the menu ➢...
Page 7
EASTRON SMART X96-RC User Manual __________________________________________________________________________________________________ ___06-2018 V1.0 Max. DMD of Current Max. DMD of Current Max. DMD of Current Max. DMD of Current Max. DMD of Current Max. DMD of Current Max. DMD of Current Max. DMD of W Max.
Page 8
EASTRON SMART X96-RC User Manual __________________________________________________________________________________________________ ___06-2018 V1.0 4. Setting-Up ____________________________________________________________________________________________________________________ 2018 EASTRON Electronic. All Rights Reserved. www.eastron.com.cn...
EASTRON SMART X96-RC User Manual __________________________________________________________________________________________________ ___06-2018 V1.0 4.1 Password Entry Setting-up mode is password protected, so you must enter the correct password. By firmly press the button for 2 seconds, the password screen appears. The default password is 1000. If an incorrect password is entered, the display shows ERR.
Page 10
EASTRON SMART X96-RC User Manual __________________________________________________________________________________________________ ___06-2018 V1.0 Baud rate options: 2400 4800 9600 19200 38400 (bps). Default: 9600bps From the Set-up menu, Use to select the Baud rate options. Long press to enter the selection routine. The Baud Rate setting will flash.
Page 11
EASTRON SMART X96-RC User Manual __________________________________________________________________________________________________ ___06-2018 V1.0 Example shows: Set Parity: Odd And long press for confirmation. Press to return the main set up menu. ____________________________________________________________________________________________________________________ 2018 EASTRON Electronic. All Rights Reserved. www.eastron.com.cn...
Page 12
EASTRON SMART X96-RC User Manual __________________________________________________________________________________________________ ___06-2018 V1.0 4.2.4 Stop bit Stop Bit options: 1 or 2. Default Stop Bit : 1 Note that if parity is set to ODD or EVEN, Stop Bits will be set to 1 and cannot be changed.
Page 13
EASTRON SMART X96-RC User Manual __________________________________________________________________________________________________ ___06-2018 V1.0 Example shows : Set CT1 5kA And long press for confirmation. 4.4 PT The PT option sets the secondary voltage of the voltage transformer (PT) that give into the meter and the PT rate between the primary voltage to the secondary voltage.
Page 14
EASTRON SMART X96-RC User Manual __________________________________________________________________________________________________ ___06-2018 V1.0 4.4.1 PT2 Set secondary voltage input the meter Range: 100V ~ 480V Default: 230V And long press for confirmation. 4.4.2 PT1 Set primary voltage input the meter Range: 100V ~ 500000V Default: 230V Then press to enter the PT2 routine.
Page 15
EASTRON SMART X96-RC User Manual __________________________________________________________________________________________________ ___06-2018 V1.0 Fixed Block: Select an interval from 1 to 60 minutes (in 1 minute increments). The power meter calculates an updates the demand at the end of each interval. 4.5.1 Demand method The screen shows the Demand calculation method: Slid Options: Fix and Slid to enter Demand calculation method.
Page 16
EASTRON SMART X96-RC User Manual __________________________________________________________________________________________________ ___06-2018 V1.0 4.5.2 Demand interval time/ Block time (DIT) The screen will show the currently selected integration time. Default is 60 minutes. range from 1 to 60. Off means function closed. Long press to enter the DIT routine. Press for 2s, the setting will flash.
EASTRON SMART X96-RC User Manual __________________________________________________________________________________________________ ___06-2018 V1.0 4.6.1 Backlight time The meter provides a function to set the backlit lasting time. Options: ON/OFF/5/10/30/60/120 minutes. Default: 60 If it is seated as 5, the backlit will be off in 5 minutes.
Page 18
EASTRON SMART X96-RC User Manual __________________________________________________________________________________________________ ___06-2018 V1.0 Set the time of RTC Left picture shows 16:20:58 The format is HH-MM-SS 4.7 System The Unit has a default setting of 3 phase 4 wire ( 3p4w). Use this section to set the type of electrical system.
EASTRON SMART X96-RC User Manual __________________________________________________________________________________________________ ___06-2018 V1.0 Example shows: The screen shows the currently selected power supply is single phase two wire 4.7.2 System connect This unit provides a function with Reverse connected current inputs correction setting. to select the correction option.
EASTRON SMART X96-RC User Manual __________________________________________________________________________________________________ ___06-2018 V1.0 Press enter Phase 3 correction. Press for 2s, the setting will flash. Use to choose Options. And long press for confirmation. Press to return the System set up menu. 4.7.3 Change password This unit provides a function with password setting.
Page 21
EASTRON SMART X96-RC User Manual __________________________________________________________________________________________________ ___06-2018 V1.0 Escape the Setting menu. Long press for 2 secs. For example, the screen shows the currently selected Automatic Scroll display ON. Long press for 2 secs, then the screen shows the currently selected Automatic Scroll display OFF.
Page 22
EASTRON SMART X96-RC User Manual __________________________________________________________________________________________________ ___06-2018 V1.0 This option is to reset the demand information. It would reset current and power demand information. This option it to reset the Max. and Min. information This option is to reset the SOE information.
EASTRON SMART X96-RC User Manual __________________________________________________________________________________________________ ___06-2018 V1.0 5. Specifications Table 1 Electrical characteristics Type of measurement RMS including harmonics on three phase AC system (3P, 3P+N) 128 samples per cycle Measurement Power IEC 61557-12 Class 0.5 accuracy Active Energy IEC 62053-22 Class 0.5S, IEC 61557-12 Class 0.5...
Page 24
EASTRON SMART X96-RC User Manual __________________________________________________________________________________________________ ___06-2018 V1.0 Immunity to Impulse Waves IEC 61000-4-5 Conducted Immunity IEC 61000-4-6 Immunity to Magnetic Fields IEC 61000-4-8 Immunity to Voltage Dips IEC 61000-4-11 Radiated Emissions EN55011 Class A Conducted Emissions EN55011 Class A...
Page 25
EASTRON SMART X96-RC User Manual __________________________________________________________________________________________________ ___06-2018 V1.0 Table 2 Features X96-3F Instantaneous Measurements Current ● Voltage L-N ● ● Frequency ● Active power ● Reactive power ● Apparent power ● Power factor ● Energy Values Active energy ● Reactive energy ●...
Page 26
EASTRON SMART X96-RC User Manual __________________________________________________________________________________________________ ___06-2018 V1.0 Communications RS485 ● M-Bus Lora Accuracy Active energy Cl. 0.5s Reactive energy Current 0.5% Voltage 0.5% Power 0.5% 0.2% Number of measurement points per circle Auxiliary power supply ● Note: ● = included * = optional —...
Page 27
EASTRON SMART X96-RC User Manual __________________________________________________________________________________________________ ___06-2018 V1.0 7.1 Safety The unit is designed in accordance with IEC 61010-1:2010 – Permanently connected use, Normal condition. Installation category III, pollution degree 2, basic insulation for rated voltage. 7.2 EMC Installation Requirements...
Page 28
EASTRON SMART X96-RC User Manual __________________________________________________________________________________________________ ___06-2018 V1.0 7.4 Mounting 7.5 Wiring Diagram ____________________________________________________________________________________________________________________ 2018 EASTRON Electronic. All Rights Reserved. www.eastron.com.cn...