Three Phase Multifunction Din Rail Meter
SDM530Y
User Manual V1.1
Eastron Europe Limited

Advertisement

Table of Contents
loading

Summary of Contents for Eastron SDM530Y

  • Page 1 Three Phase Multifunction Din Rail Meter SDM530Y User Manual V1.1 Eastron Europe Limited...
  • Page 2 EASTRON SDM530Y User Manual 06-2018 V1.0 Statement All rights reserved. Without the written permission of the company, no paragraphs or chapters in this manual can be extracted, copied or reproduced in any form. Otherwise, the violator shall bear all consequences.
  • Page 3: Table Of Contents

    EASTRON SDM530Y User Manual 06-2018 V1.0 Catalogue Chapter One. Product Overview 1.1 Product Introduction 1.2 Product Feature 1.3 Application Scenarios Chapter Two. Technical Specification Parameters 2.1 Technical Parameters 2.2 Measurement Accuracy 2.3 RS485 Communication 2.4 Performance Standard 2.5 Outline and Dimension 2.6 Wiring Diagram...
  • Page 4: Chapter One. Product Overview

    The reactive power, apparent power can be read by Modbus. SDM530Y is easy to install with nice appearance, small and light. With battery installed inside the meter, the value on the meter still can be read when grid power off.
  • Page 5: Measurement Accuracy

    EASTRON SDM530Y User Manual 06-2018 V1.0 Operating Voltage Range:±20%Basic Value Measurement Form: Valid Values  Input Current: Basic Value:5A Max.Current:100A Over Current Withstand: 20 Imax for 0.5s  Input Frequency: Basic Value:50/60Hz Input Frequency Range:45-65 Hz  Insulation Capabilities: - AC voltage withstand 4KV/1min Impulse Voltage Withstand 6kV –...
  • Page 6: Performance Standard

    EASTRON SDM530Y User Manual 06-2018 V1.0  Data Bit:8  Stop Bit:1 2.4 performance standard  Operating Humidity:≤90%  Storage Humidity:≤95%  Operating Temperature:-25℃~+55℃  Storage Temperature:-40℃~+70℃  International Standard:GB-T 17215/ IEC62053-22/ EN50470-1/3  Accuracy Class:Class 0.5S  Installation Category:CATII ...
  • Page 7: Wiring Diagram

    EASTRON SDM530Y User Manual 06-2018 V1.0 2.6 Wiring diagram 2018 EASTRON All Rights Reserved. www.eastroneurope.com...
  • Page 8: Chapter Three. Operating Instructions

    EASTRON SDM530Y User Manual 06-2018 V1.0 Chapter Three. Operating instructions 3.1 Panel Instructions and Key Operation Instructions 3.1.1 Panel Instructions After the correct connection, it will enter the normal measurement state, and the screen is displayed as follows: 1st Screen...
  • Page 9: 2.1 Electricity Purchase

    EASTRON SDM530Y User Manual 06-2018 V1.0 used emergency amount will be deducted first, and the remaining electricity charge will be charged to the meter. Turn off this function when the emergency amount is set to 0. 3.2.1 Electricity Purchase: The user goes to the administrative department of selling electricity to deal with the electricity purchase business.
  • Page 10 EASTRON SDM530Y User Manual 06-2018 V1.0 Accumulated Used Electricity Example: 120.00kWh Total Active Power Example: 120.00kWh recharge amount Example: 120.00$ Communication Address Example: 001 Communication Baud Rate Example: 9600 Communication Parity Bit Example: None Explanation: Parity Bit “N” stands none; “E” stands even; “O” stands...
  • Page 11: Basic Setting

    EASTRON SDM530Y User Manual 06-2018 V1.0 Software Version Example: 12 01.00 fault code Example: Err-01 3.4 Basic Setting Long press " " for three seconds to enter the setting mode (It will exit the setting interface if there is no operation in the next minute andreturn the remaining amount interface) :...
  • Page 12 EASTRON SDM530Y User Manual 06-2018 V1.0 Communication Address Default Communication Address : Communication address range: 001~247 Long press into the communication address setting interface, current character flashing. Then, pre ss select communication address. Finally, long press to confirm Settings. Baud Rate...
  • Page 13 EASTRON SDM530Y User Manual 06-2018 V1.0 Long press into the constant setting interface, current character flashing. Then, press select the new constant. Finally, long press confirm Settings. pulse width Default: 35ms Optional:200, 100,60. If the pulse constant is equal to...
  • Page 14: Chapter Four. Communication Introduction 4.1 Input Register, Function Code (Hex)

    EASTRON SDM530Y User Manual 06-2018 V1.0 10-1 Long press into the backlit time setting interface, the current character flashing. Then, press select the new backlight lighting time. Finally, long press confirm Settings. User Password Default :1000 Optional : 0 ~ 9999...
  • Page 15 EASTRON SDM530Y User Manual 06-2018 V1.0 Register start Register address(Hex) Patter Serial Parameter The value description High Number Byte Byte Set range:60, 100, 200,Unit:ms,Default:35. Note: If the pulse constant of pulse 1 =1000imp/kWh, Then Pulse 1 output Read/ 40013 the automatic fixation is 35ms,can’t be set.
  • Page 16 EASTRON SDM530Y User Manual 06-2018 V1.0 Set range 0 ~ 121,unit:minute,Default60. 0 Stands for Backlight normally on;121 Stands for Read/ 40061 Backlight time Backlight normally off. Write Data length : 4 byte Data type : Float Recharge amount,length:4byte,data format: 1)...
  • Page 17 EASTRON SDM530Y User Manual 06-2018 V1.0 Recharge amount,length:4byte,data format: 1) Float The time recharge occurs,length:6byte,data 2) The last four format:BCD, Only 41321 recharge Year-Month-Date-Hour-Minute-Second read information example(Hex):42 C8 00 00 18 07 16 13 12 20, C8 00 00 Stands for recharge amount(100), 18 07 16 Stands for 2018.7.16,13 12 20 Stands for 13:12:20...
  • Page 18 EASTRON SDM530Y User Manual 06-2018 V1.0 Recharge amount,length:4byte,data format: 1) Float The time recharge occurs,length:6byte,data 2) The last eight format:BCD, Only 41361 recharge Year-Month-Date-Hour-Minute-Second read information example(Hex):42 C8 00 00 18 07 16 13 12 20, C8 00 00 Stands for recharge amount(100), 18 07 16 Stands for 2018.7.16,13 12 20 Stands for 13:12:20...
  • Page 19 EASTRON SDM530Y User Manual 06-2018 V1.0 Recharge amount,length:4byte,data format: 1) Float The time recharge occurs,length:6byte,data 2) The last twelve format:BCD, Only 41401 recharge Year-Month-Date-Hour-Minute-Second read information example(Hex):42 C8 00 00 18 07 16 13 12 20, C8 00 00 Stands for recharge amount(100), 18 07 16 Stands for 2018.7.16,13 12 20 Stands for 13:12:20...
  • Page 20 EASTRON SDM530Y User Manual 06-2018 V1.0 Recharge amount,length:4byte,data format: 1) Float The time recharge occurs,length:6byte,data 2) The last sixteen format:BCD, Only 41441 recharge Year-Month-Date-Hour-Minute-Second read information example(Hex):42 C8 00 00 18 07 16 13 12 20, C8 00 00 Stands for recharge amount(100), 18 07 16 Stands for 2018.7.16,13 12 20 Stands for 13:12:20...
  • Page 21 EASTRON SDM530Y User Manual 06-2018 V1.0 Recharge amount,length:4byte,data format: 1) Float The time recharge occurs,length:6byte,data 2) The last twenty format:BCD, Only 41481 recharge Year-Month-Date-Hour-Minute-Second read information example(Hex):42 C8 00 00 18 07 16 13 12 20, C8 00 00 Stands for recharge amount(100), 18 07 16 Stands for 2018.7.16,13 12 20 Stands for 13:12:20...
  • Page 22 EASTRON SDM530Y User Manual 06-2018 V1.0 Recharge amount,length:4byte,data format: 1) Float The time recharge occurs,length:6byte,data 2) The last format:BCD, twenty-four Only 41521 Year-Month-Date-Hour-Minute-Second recharge read example(Hex):42 C8 00 00 18 07 16 13 12 20, information C8 00 00 Stands for recharge amount(100), 18 07 16 Stands for 2018.7.16,13 12 20 Stands for 13:12:20...
  • Page 23 EASTRON SDM530Y User Manual 06-2018 V1.0 Recharge amount,length:4byte,data format: 1) Float The time recharge occurs,length:6byte,data 2) The last format:BCD, twenty-eight Only 41561 Year-Month-Date-Hour-Minute-Second recharge read example(Hex):42 C8 00 00 18 07 16 13 12 20, information C8 00 00 Stands for recharge amount(100), 18 07 16 Stands for 2018.7.16,13 12 20 Stands for 13:12:20...
  • Page 24 EASTRON SDM530Y User Manual 06-2018 V1.0 Recharge amount,length:4byte,data format: 1) Float The time recharge occurs,length:6byte,data 2) The last format:BCD, thirty-two Only 41601 Year-Month-Date-Hour-Minute-Second recharge read example(Hex):42 C8 00 00 18 07 16 13 12 20, information C8 00 00 Stands for recharge amount(100), 18 07 16 Stands for 2018.7.16,13 12 20 Stands for 13:12:20...
  • Page 25 EASTRON SDM530Y User Manual 06-2018 V1.0 Recharge amount,length:4byte,data format: 1) Float The time recharge occurs,length:6byte,data 2) The last format:BCD, thirty-six Only 41641 Year-Month-Date-Hour-Minute-Second recharge read example(Hex):42 C8 00 00 18 07 16 13 12 20, information C8 00 00 Stands for recharge amount(100), 18 07 16 Stands for 2018.7.16,13 12 20 Stands for 13:12:20...
  • Page 26 EASTRON SDM530Y User Manual 06-2018 V1.0 Recharge amount,length:4byte,data format: 1) Float The time recharge occurs,length:6byte,data 2) The last forty format:BCD, Only 41681 recharge Year-Month-Date-Hour-Minute-Second read information example(Hex):42 C8 00 00 18 07 16 13 12 20, C8 00 00 Stands for recharge amount(100), 18 07 16 Stands for 2018.7.16,13 12 20 Stands for 13:12:20...
  • Page 27 EASTRON SDM530Y User Manual 06-2018 V1.0 Recharge amount,length:4byte,data format: 1) Float The time recharge occurs,length:6byte,data 2) The last format:BCD, forty-four Only 41721 Year-Month-Date-Hour-Minute-Second recharge read example(Hex):42 C8 00 00 18 07 16 13 12 20, information C8 00 00 Stands for recharge amount(100), 18 07 16 Stands for 2018.7.16,13 12 20 Stands for 13:12:20...
  • Page 28 EASTRON SDM530Y User Manual 06-2018 V1.0 Recharge amount,length:4byte,data format: 1) Float The time recharge occurs,length:6byte,data 2) The last format:BCD, forty-eight Only 41761 Year-Month-Date-Hour-Minute-Second recharge read example(Hex):42 C8 00 00 18 07 16 13 12 20, information C8 00 00 Stands for recharge amount(100), 18 07 16 Stands for 2018.7.16,13 12 20 Stands for 13:12:20...
  • Page 29 EASTRON SDM530Y User Manual 06-2018 V1.0 Relay action record,length:2byte,data format: 1) Hex; FF 00 Stands for relay off;00 00 Stands for relay open; The last two The time of relay operation,length:6byte,data 2) Only 41809 relay control format:BCD, read record Year-Month-Date-Hour-Minute-Second example(Hex):FF 00...
  • Page 30 EASTRON SDM530Y User Manual 06-2018 V1.0 Relay action record,length:2byte,data format: 1) Hex; FF 00 Stands for relay off;00 00 Stands for relay open; The last five The time of relay operation,length:6byte,data 2) Only 71833 relay control format:BCD, read record Year-Month-Date-Hour-Minute-Second example(Hex):FF 00...
  • Page 31 EASTRON SDM530Y User Manual 06-2018 V1.0 Relay action record,length:2byte,data format: 1) Hex; FF 00 Stands for relay off;00 00 Stands for relay open; The last eight The time of relay operation,length:6byte,data 2) Only 41857 relay control format:BCD, read record Year-Month-Date-Hour-Minute-Second example(Hex):FF 00...
  • Page 32 EASTRON SDM530Y User Manual 06-2018 V1.0 Relay action record,length:2byte,data format: 1) Hex; FF 00 Stands for relay off;00 00 Stands for relay open; The last eleven The time of relay operation,length:6byte,data 2) Only 41881 relay control format:BCD, read record Year-Month-Date-Hour-Minute-Second example(Hex):FF 00...
  • Page 33 EASTRON SDM530Y User Manual 06-2018 V1.0 Relay action record,length:2byte,data format: 1) Hex; FF 00 Stands for relay off;00 00 Stands for relay open; The last The time of relay operation,length:6byte,data 2) Only 41905 fourteen relay format:BCD, read control record Year-Month-Date-Hour-Minute-Second example(Hex):FF 00...
  • Page 34 EASTRON SDM530Y User Manual 06-2018 V1.0 Relay action record,length:2byte,data format: 1) Hex; FF 00 Stands for relay off;00 00 Stands for relay open; The last The time of relay operation,length:6byte,data 2) Only 41929 seventeen relay format:BCD, read control record Year-Month-Date-Hour-Minute-Second example(Hex):FF 00...
  • Page 35 EASTRON SDM530Y User Manual 06-2018 V1.0 Relay action record,length:2byte,data format: 1) Hex; FF 00 Stands for relay off;00 00 Stands for relay open; The last twenty The time of relay operation,length:6byte,data 2) Only 41953 relay control format:BCD, read record Year-Month-Date-Hour-Minute-Second example(Hex):FF 00...
  • Page 36 EASTRON SDM530Y User Manual 06-2018 V1.0 Relay action record,length:2byte,data format: 1) Hex; FF 00 Stands for relay off;00 00 Stands for relay open; The last The time of relay operation,length:6byte,data 2) twenty-three Only 41977 format:BCD, relay control read Year-Month-Date-Hour-Minute-Second record example(Hex):FF 00...
  • Page 37 EASTRON SDM530Y User Manual 06-2018 V1.0 Relay action record,length:2byte,data format: 1) Hex; FF 00 Stands for relay off;00 00 Stands for relay open; The last The time of relay operation,length:6byte,data 2) Only 42001 twenty-six relay format:BCD, read control record Year-Month-Date-Hour-Minute-Second example(Hex):FF 00...
  • Page 38 EASTRON SDM530Y User Manual 06-2018 V1.0 Relay action record,length:2byte,data format: 1) Hex; FF 00 Stands for relay off;00 00 Stands for relay open; The last The time of relay operation,length:6byte,data 2) twenty-nine Only 42025 format:BCD, relay control read Year-Month-Date-Hour-Minute-Second record example(Hex):FF 00...
  • Page 39 EASTRON SDM530Y User Manual 06-2018 V1.0 Relay action record,length:2byte,data format: 1) Hex; FF 00 Stands for relay off;00 00 Stands for relay open; The last The time of relay operation,length:6byte,data 2) thirty-two Only 42049 format:BCD, relay control read Year-Month-Date-Hour-Minute-Second record example(Hex):FF 00...
  • Page 40 EASTRON SDM530Y User Manual 06-2018 V1.0 Relay action record,length:2byte,data format: 1) Hex; FF 00 Stands for relay off;00 00 Stands for relay open; The last The time of relay operation,length:6byte,data 2) Only 42073 thirty-five relay format:BCD, read control record Year-Month-Date-Hour-Minute-Second example(Hex):FF 00...
  • Page 41 EASTRON SDM530Y User Manual 06-2018 V1.0 Relay action record,length:2byte,data format: 1) Hex; FF 00 Stands for relay off;00 00 Stands for relay open; The last The time of relay operation,length:6byte,data 2) thirty-eight Only 42097 format:BCD, relay control read Year-Month-Date-Hour-Minute-Second record example(Hex):FF 00...
  • Page 42 EASTRON SDM530Y User Manual 06-2018 V1.0 Relay action record,length:2byte,data format: 1) Hex; FF 00 Stands for relay off;00 00 Stands for relay open; The last The time of relay operation,length:6byte,data 2) Only 42121 forty-one relay format:BCD, read control record Year-Month-Date-Hour-Minute-Second example(Hex):FF 00...
  • Page 43 EASTRON SDM530Y User Manual 06-2018 V1.0 Relay action record,length:2byte,data format: 1) Hex; FF 00 Stands for relay off;00 00 Stands for relay open; The last The time of relay operation,length:6byte,data 2) Only 42145 forty-four relay format:BCD, read control record Year-Month-Date-Hour-Minute-Second example(Hex):FF 00...
  • Page 44 EASTRON SDM530Y User Manual 06-2018 V1.0 Relay action record,length:2byte,data format: 1) Hex; FF 00Stands for relay off;00 00 Stands for relay open; The last The time of relay operation,length:6byte,data 2) forty-seven Only 42169 format:BCD, relay control read Year-Month-Date-Hour-Minute-Second record example(Hex):FF 00...
  • Page 45 EASTRON SDM530Y User Manual 06-2018 V1.0 Read the threshold value of the meter two - level alarm ,unit RMB Alarm value 1,Alarm value 2 Meter alarm Only example:41 20 00 00 40 A0 00 00,41 20 00 00 464535 amount read Stands for Alarm threshold1(RMB 10),40 A0 00 00...
  • Page 46 EASTRON SDM530Y User Manual 06-2018 V1.0 0C = Low byte of register start address 00 = High bytes of register number 02 = Low bytes of register number 04 = CRC Low byte of the parity code 08 = CRC High byte of the parity code...
  • Page 47 EASTRON SDM530Y User Manual 06-2018 V1.0 IF you have any question, please feel free to contact our sales team. Eastron Europe Limited 12 Brunel Road, Manor Trading Estate, Benfleet, SS7 4PS, UK Tel: +44 0203 758 3494 Email: sales@eastroneurope.com www.eastroneurope.com 2018 EASTRON All Rights Reserved.

Table of Contents