Eastron SMART X96 Series User Manual
Eastron SMART X96 Series User Manual

Eastron SMART X96 Series User Manual

Multi-function power analyzer
Hide thumbs Also See for SMART X96 Series:

Advertisement

Quick Links

EASTRON SMART X96-5 F/G/H/I/J User Manual V2.2
SMART X96-5 -F/G/H/I/J
Multi-Function Power Analyzer
● Multi-parameter Measurements
● Up to 63
THD and IHD
rd
● RS485 Modbus RTU
● Ethernet TCP Gateway
● Multi-tariffs
● Digital Input/Output
● Accuracy Class 0.5s
● Bar Graph for Power Indication
● Backlit LCD Display for Full Viewing Angles
● Push-in Installation and Plug-in Connection
User Manual
V2.2
2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastrongroup.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SMART X96 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Eastron SMART X96 Series

  • Page 1 ● Multi-tariffs ● Digital Input/Output ● Accuracy Class 0.5s ● Bar Graph for Power Indication ● Backlit LCD Display for Full Viewing Angles ● Push-in Installation and Plug-in Connection User Manual V2.2 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastrongroup.com...
  • Page 2: Unit Characteristics

    EASTRON SMART X96-5 F/G/H/I/J User Manual V2.2 Introduction The multifunction energy analyzer SMART X96 series is a top new-generation intelligent panel meter, used not only in the electricity transmission and power distribution system, but also in the power consumption measurement and analysis in high voltage intelligent power grid.
  • Page 3: Ethernet Tcp/Ip

    4 lines, 4 digits per line to show electrical parameters line, 8 digits to show energy Bar graph for power indication Display update time: 1 sec. for all parameters Display scrolling: automatic or manual (Programmable) 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastrongroup.com...
  • Page 4: Start Up Screens

    The second screen indicates the software version of the unit. (the left picture is just for reference) The unit performs a self-test and the screen indicates if the test is passed. After a short delay, the default measurement screen appears. 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastrongroup.com...
  • Page 5: Buttons And Displays

    ➢ Down page or reduce value ➢ Tariff Information ➢ Display total / import / export active or ➢ Set-up mode entry reactive energy information ➢ Confirmation selected system type. ➢ Right side move 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastrongroup.com...
  • Page 6 THD% of Current L1 THD% of Current L1 THD% of Current L1 THD% of Current L2 THD% of Current L2 THD% of Current L3 THD% of Current L3 Phase Sequence Phase Sequence 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastrongroup.com...
  • Page 7 Min. VA Min. VA Min. VA Active Power L1 Active Power L2 Active Power L3 Reactive Power L1 Reactive Power L2 Reactive Power L3 Apparent Power L1 Apparent Power L2 Apparent Power L3 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastrongroup.com...
  • Page 8 Press the button for 2 seconds to check Harmonic distortion of Voltage 2~63 Harmonic Distortion of Voltage Press the button for 2 seconds to check Harmonic distortion of Current 2~63 Harmonic Distortion of Current 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastrongroup.com...
  • Page 9 EASTRON SMART X96-5 F/G/H/I/J User Manual V2.2 4. Setting-Up 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastrongroup.com...
  • Page 10 Modbus address range 001~247 Default 001 Long press to enter the selection routine, the address setting will flash. Use to set the address with the range 001~247. And long press for confirmation. 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastrongroup.com...
  • Page 11 Set Parity: EVEN *Note that Parity can only be changed to EVEN when the Stop Bits is set to 1. And long press for confirmation. Press to return the communication set up menu. 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastrongroup.com...
  • Page 12 Set Stop bit 2 And long press for confirmation. Press to return the Communication set up menu. 4.3 CT CT set up menu: From the main Set-up menu, Use to select the CT option. 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastrongroup.com...
  • Page 13 2s, the CT1 setting will flash. Use to choose CT1 with 1~9999. Example shows : Set CT1 100A And long press for confirmation. Press to return the CT set up menu. 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastrongroup.com...
  • Page 14 Then press to enter the PT1 routine. press for 2s, the PT1 setting will flash. Use to select PT1. And long press for confirmation. Press to return the PT set up menu. 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastrongroup.com...
  • Page 15 1 to 59minutes. The power meter displays the demand value for the last completed interval. Fixed Block: Select an interval from 1 to 60 minutes (in 1 minute increments). The power meter calculates an updates the demand at the end of each interval. 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastrongroup.com...
  • Page 16 Options. And long press confirmation. 4.5.3 Sliding time The screen will show the Sliding time for the sliding mode. The sliding time shall be set not bigger than the DIT. 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastrongroup.com...
  • Page 17: Backlight Time

    If it is seated as 5, the display will scroll every 5s. to select Display scroll time option. Press 2s, the setting will flash. Use to choose Options. And Long press for confirmation. Press to return to the time set up menu. 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastrongroup.com...
  • Page 18 Press to return to the time set up menu. 4.6.4 Tariff Time This option is to set the time segments with different tariffs. to enter the time segments and tariffs setting. 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastrongroup.com...
  • Page 19: System Type

    System type routine. Press for 2s, the setting will flash. Use to choose Options. And Long press for confirmation. Example shows: The screen shows the currently selected power supply is three phase three wire 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastrongroup.com...
  • Page 20: System Connect

    Options. And long press confirmation. Press enter Phase 3 correction. Press for 2s, the setting will flash. Use to choose Options. And long press confirmation. Press to return the System set up menu. 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastrongroup.com...
  • Page 21: Change Password

    2s, the setting will flash. Use choose options “On” or “Off”. And long press for confirmation. Escape the Setting menu. Long press for 2 secs. For example, the screen shows the currently selected Automatic Scroll display ON. 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastrongroup.com...
  • Page 22: Digital Input (Di)

    This is to set filtering time for a digital input signal. Left picture shows 100mS This screen is to check the counting number of each digital inputs. By pressing the , the user can see counting numbers. 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastrongroup.com...
  • Page 23 DO-1. By click the , the user can choose different Digital Output. This screen is to set the alarm information link to DO-1 For details , please refer to part 4.9.2 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastrongroup.com...
  • Page 24 PF1, PF2, PF3, PF-total F (frequency) Null means the Alarm is not linked to any parameter. This option is set the DO action delay time. The unit is mS. Left picture shows 200mS. 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastrongroup.com...
  • Page 25 This option is to set the Low value for DO-1 open. Left picture shows LO (Low value to Open) 170V, that means when the U1 returns to 170V, the DO-1 will open. 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastrongroup.com...
  • Page 26: Ethernet Communication

    , the user can get into sub-menu. This option is to set the IP address. This option is to set Subnet Mask This option is to set the default Gateway This option is to set the IP port 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastrongroup.com...
  • Page 27 Left picture shows No.1 event By click the , the user can check other events. By pressing the button , the user can find the date and time when the event happened. 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastrongroup.com...
  • Page 28 This option is to reset the demand information. It would reset current and power demand information. This option it to reset tsyshe Max. and Min. information This option is to reset the SOE information. 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastrongroup.com...
  • Page 29 EASTRON SMART X96-5 F/G/H/I/J User Manual V2.2 This option is to reset Digital input counting. This option is to reset all information. 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastrongroup.com...
  • Page 30: Specifications

    Maximum Frequency 1kHz Response Time 10 milliseconds Isolation 2.5 KVac 1min Mechanical Characteristics Weight 250g IP Degree of Protection IP51 front display (IEC 60529) Dimensions (WxHxD) 96x96x70.3 Mounting Position Vertical Panel Thickness 1~5mm 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastrongroup.com...
  • Page 31: Environmental Characteristics

    Communication address 1~247 Transmission mode Half duplex Data type Floating point Transmission distance 1000m Maximum Transmission speed 2400bps~38400bps Parity None (default), Odd, Even Stop bits 1 or 2 Response time <100 mS 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastrongroup.com...
  • Page 32 Three phase 3 wire ● ● ● ● ● Three phase 4 wire ● ● ● ● ● CT programmable ● ● ● ● ● PT programmable ● ● ● ● ● Inputs and Outputs 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastrongroup.com...
  • Page 33 When the battery voltage is lower than 2.4V DC, the meter LCD will shows warning symbol . The user needs to replace the battery with a new one. Battery model: CR2032 When you install/replace the battery, make sure the meter’s voltage input must be disconnected. 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastrongroup.com...
  • Page 34 The unit does not have internal fuses therefore external fuses must be used for  protection and safety under fault conditions. Never open-circuit the secondary winding of an energized current transformer.  This product should only be operated with CT secondary connections Earthed.  2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastrongroup.com...
  • Page 35 The connection at the remote end of such auxiliary circuits should not be accessible in normal use. Depending on application, equipment connected to auxiliary circuits may vary widely. 7.3 Dimensions Smart X96-5J Rear View Smart X96-5F Smart X96-5G Smart X96-5H Smart X96-5 I/J 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastrongroup.com...
  • Page 36 EASTRON SMART X96-5 F/G/H/I/J User Manual V2.2 7.4 Mounting 7.5 Wiring Diagram RS485 / DI / DO 1P2W(L+N) 1CT 1P2W(L+L) 1CT 1P3W(L+L+N) 2CTs 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastrongroup.com...
  • Page 37 EASTRON SMART X96-5 F/G/H/I/J User Manual V2.2 3P3W 2CTs 3P4W 3CTs 3P3W 2PT 2CTs 3P4W 3PT 3CTs 3P3W 1CT Balance load 3P4W 1CT Balance load 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastrongroup.com...
  • Page 38 EASTRON SMART X96-5 F/G/H/I/J User Manual V2.2 IF you have any question, please feel free to contact our sales team. No.52, Dongjin Rd. Nanhu, Jiaxing, Zhejiang, 314000, China Zhejiang Eastron Electronic Co., Ltd. Tel: +86-573-83698881 Email: sales@eastrongroup.com www.eastrongroup.com 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastrongroup.com...