PREFACE THIS MANUAL IS SUPPLIED AS AN INTEGRAL AND ESSENTIAL PART OF THE PRODUCT AND MUST BE DELIVERED TO THE USER. INFORMATION INCLUDED IN THIS SECTION ARE DEDICATED BOTH TO THE USER AND TO PERSONNEL FOLLOWING PRODUCT INSTALLATION AND MAINTENANCE. THE USER WILL FIND FURTHER INFORMATIONS ABOUT OPERATING AND USE RESTRICTIONS, IN THE SECOND SECTION OF THIS MANUAL.
3) GENERAL INSTRUCTIONS DEPENDING ON FUEL USED 3B) FIRING WITH GAS, GASOIL OR OTHER FUELS 3A) ELECTRICAL CONNECTION GENERAL * For safety reasons the unit must be efficiently earthed and * The burner shall be installed by qualified personnel and in installed as required by current safety regulations.
Page 6
MOUNTINGS AND CONNECTIONS The burners are despatched in cardboard packages. The packaging contains the following items: burner; flexible light oil tubes; light oil filter; gasket to be inserted between the burner and the boiler; this manual, the Guarantee Certificate and the test certificate. To get rid of the burner’s packing and in the event of scrapping of the latter, follow the procedures laid down by current laws on disposal of materials.
Page 8
SETTINGS Burners G18SP - PG25SP These burners are fitted with a double-regulation pump. The flame control device, a twin-stage one, after the pre-purgue stage, energized the valve EV1 and the burner starts up. After few seconds, the intervention of the second stage caused the energizing of the valve EV2, so the burner is feeded with a maximum pressure of about 18 bar.
Page 9
LIGHT OIL PUMPS SUNTEC AS57C Suction height: 0.5 bar Advised value to prevent air separation from oil: 0.35 bar Rated speed: max. 2850 rpm Operation viscosity: from 2 to 12 cSt Inlet pressure: max. 2 bar Fig. 7 DELTA VM2RL2 Suction height: 0.5 bar Advised value to prevent...
AIR FLOW ADJUSTMENT Burner G18SP Loose the screw VBS and rotate the air damper in the desired position, to set the air flow. At the end of settings, tight the screw VBS. Fig. 10 Fig. 10 Burners PG25SP - PG30TN Loose the screw VBS and set the air flow, working directly on the air damper.
Page 11
PART II: OPERATION MANUAL LIMITATIONS OF USE THE BURNER IS AN APPLIANCE DESIGNED AND CONSTRUCTED TO OPERATE ONLY AFTER BEING CORRECTLY CONNECTED TO A HEAT GENERATOR (E.G. BOILER, HOT AIR GENERATOR, FURNACE, ETC.), ANY OTHER USE IS TO BE CONSIDERED IMPROPER AND THEREFORE DANGEROUS. THE USER MUST GUARANTEE THE CORRECT FITTING OF THE APPLIANCE, ENTRUSTING THE INSTALLATION OF IT TO QUALIFIED PERSONNEL AND HAVING THE FIRST COMMISSIONING OF IT CARRIED OUT BY A SERVICE CENTRE AUTHORISED BY THE COMPANY MANUFACTURING THE BURNER.
PART III: MAINTENANCE At least once a year carry out the following maintenance procedures. If servicing is on a seasonal basis, it is recommended at the end of the season; routine sevice should be carried out every months. Note: Any operation on the burner must be carried out with the main electricity switched off. PERIODICAL SERVICING - Clean and examine the oil filter cartridge and replace it if necessary;...
Page 13
CHECK OF THE IONIZATION CURRENT TERMINAL BLOCK MC To check the detector signal follow the prcedure shown in fig. 14. If the signal is not within the prescribed range, check the electrical contacts; check also that the combustion head is clean and Scale µA DC the photoelectric sensor is correctly positioned.
Page 14
ELECTRICAL DIAGRAM code 01-369 BURNER G18SP Time counter EVG1 Light oil solenoid valve I st stage EVG2 Light oil solenoid valve II nd stage Fuse Photoresistor Main switch Phase Burner operation light Burner lockout light LOA24/BOA64 Flame monitor device Power supply terminal block Fan motor Neutral 1 - Electric supply 230V 50Hz 2N a.c.
Page 15
ELECTRICAL DIAGRAM code 04-574 BURNER PG30TN EVG1 Light oil solenoid valve I st stage 1 - Electric supply 230V 50Hz 2N a.c. EVG2 Light oil solenoid valve II nd stage 2 - Don't reverse Phase and Neutral 3 - Make sure that the burner is properly hearted Fuses Photoresistor Main switch...
Page 16
SPARE PARTS BURNER G18SP POS. DESCRIPTION CODE POS. DESCRIPTION CODE HOUSING 3010019 19 BLAST TUBE 3090055 CONDENSER 6030004 20 COMBUSTION HEAD 3060115 MOTOR 2180009 21 ELECTRODE SUPPORT 2280016 FLAME CONTROL DEVICE LOA24 2020445 22 GASKET 2110031 SOCKET FOR LOA24 2030409 23 FLANGE 2100011 SUPPORT BRACKET...
Page 17
SPARE PARTS BURNERS PG25SP - PG30TN POS. DESCRIPTION PG25SP PG30TN ELECTRIC BOARD 6100086 6100086 THERMAL RELAY SOCKET FOR FLAME CONTROL DEVICE 2030415 2030415 FLAME CONTROL DEVICE 2020445 2020445 CONTACTOR IGNITION TRANSFORMER 2170107 2170107 TOP COVER 2210103 2210103 LANDIS PHOTORESISTOR 2510003 2510003 GASKET 2110004...
APPENDIX: COMPONENTS CHARACTERISTICS FLAME CONTROL DEVICE LANDIS LOA24 Page 18 LIGHT OIL PUMPS Page 19 LANDIS AUTOMATIC CONTROLLER LOA24 Safety time Post-ignition time FOR LIGHT OIL BURNERS Interval between the flame lighting and energising of solenoid 2a at terminal 5 LOA...
DELTA “VM” PUMPS Technical characteristics Voltage 220V-15%..240V+10% or 100V In the VM series of DELTA pumps the pressurised flow of oil P is shut off by a built in solenoid and may therefore be switched -15%...110V+10% on for startup of the motor pre-purge) or off before the motor Frequency 50...60Hz +/- 6% itself switches off (flame goes out instantly when the spray from...
Page 20
Hydraulic data SUNTEC AS oil pumps Operational pressure range - Oil 7-14 bars adjustable - Flow up to 75 1/h (c.600,000 kcal/h - 700 kW) 9-15 bars adjustable (for AS67) - Twin-pipe system Calibration 9 bars at factory - Single-pipe system Viscosity at 20°C 2-12mm2/s (cSt) Technical data...
Page 21
Operation The gear-set draws oil from the tank through the built-in filter and transfers it to the valve that regulates the oil pressure or tne nozzle line. All oil which does not go through the nozzle line will be dumped through the valve back to the return line or, if it is a one-pipe installation, back to the suction port in the gear-set.
Page 22
Closed by-pass solenoid valve Return to suction Opened by-pass solenoid valve By-pass plug Opened cut-off solenoid valve Return (twin pipe installation) Closed cut-off solenoid valve Suction (twin pipe installation) Manometer plug Vacuum gauge plug To nozzle Gear Shaft seal Hi-pressure regulator with control screw Lo-pressure regulator with control screw Oil under suction Oil under pressure...
Page 24
Via C. Colombo, 9 - 35011 Campodarsego (PD) Italy Tel. +39-049-9200944 - Fax +39-049-9200945-9201269 Internet: www.cibunigas.it - E mail: cibunigas@cibunigas.it...
Need help?
Do you have a question about the G18 G SP Series and is the answer not in the manual?
Questions and answers