Advertisement

DMP 714, 715 Manual

GET STARTED

714 and 715 zone expander modules allow you to increase the number of reporting zones available on DMP panels. The modules connect to the panel Keypad Bus or LX‑Bus and are set to an address that determines the reporting zone number.
The 714 provides four 5 VDC Class B zones for use with burglary and non‑powered fire devices.
The 715 provides four 12 VDC Class B zones for use with burglary, non‑powered, or powered fire devices.

What's Included

  • One 714 Zone Expansion Module or One 715 Zone Expansion Module
  • (714) Four 1K Ohm Resistors
  • (715) Four 3.3K Resistors
  • 12‑Wire Harness
  • Hardware Pack

INSTALLATION

Program the Panel

Program the zones on 714 or 715 zone expander modules with any of the panel's burglary or fire zone types.
You can also program zones as an Arming zone type when they are being used with key switches. For more information, refer to the appropriate panel programming guide.

Mount the Unit

The 714/715 comes in a high‑impact plastic housing that you can mount directly to a wall, backboard, or other flat surface. For easy installation, the housing base contains holes that allow you to mount the module on a single‑gang switch box or ring.

  1. Remove the housing fastener screws and separate the top housing from the base.
  2. Insert screws through the desired mounting holes on the housing base. Refer to Figure 1 for mounting hole locations.
    Mounting the Unit
  3. Tighten the screws into place.
  4. After wiring and addressing the module, attach the housing top to the mounted base with the housing fastener screws. Refer to Figure 2.

Wire the Unit

SPECIFICATIONS 714 MODULE 715 MODULE
Normal Operating Range 650‑2100 Ohms 1200‑6000 Ohms
Zone Resistors 1k Ohm EOL 3.3k Ohm EOL
Max Line Impedence 100 Ohms 100 Ohms
Zone Supervision All Zones All Zones

Table 1: 714 and 715 Modules Specifications

Unit Wiring

  1. 714 Module:
    Connect Red to LX-Bus Wire or Panel Terminal 7
    715 Module:
    Connect Red to Panel Terminal 11 or a regulated, power limited power supply listed for Fire Protective Signaling through a Model 716 relay
  2. To Keypad Bus or LX-Bus

See Figure 3.

Connect the 714 to the LX-Bus
To wire the 714, join the red, yellow, green, and black wires to a 4‑wire harness and connect it to the LX‑Bus.

Connect the 714 to the Keypad Bus

  1. Connect the red, yellow, green, and black wires to panel Terminals 7, 8, 9, and 10 respectively.
  2. Observe polarity and wire zones 1‑4.
  3. Install the included 1K Ohm EOL resistors.

Connect the 715 to the LX-Bus
To wire the 715, connect the red wire to panel Terminal 11 (Smoke power terminal). This allows Sensor Reset to drop power to the module and devices connected to its zones. Join the yellow, green, and black wires to a 4‑wire harness and connect it to the LX‑Bus.

Connect the 715 to the Keypad Bus

  1. Connect the red wire to panel Terminal 11 (Smoke power terminal). This allows Sensor Reset to drop power to the module and devices connected to its zones. Alternately, connect red to a regulated, power limited power supply listed for Fire Protective Signaling through a Model 716 relay. Use the Sensor Reset Output programming to drop power to the 715 module.
  2. Connect the yellow, green, and black wires to panel Terminals 8, 9, and 10 respectively.
  3. Observe polarity and wire zones 1‑4.
  4. Install the included 3.3K Ohm EOL resistors.

Set the Unit Address

714 and 715 Zone Expansion Modules use two rotary switches (TENS and ONES) to set the module address. For keypad bus addresses, set the switches to match the device address. For LX‑Bus addresses, set the switches to match the last two digits of the addresses. For example, for address 02 set the switches to TENS 0 and ONES 2 as shown in Figure 4. For more information, refer to Table 2 and Table 3.

Table 2: LX-Bus Addresses and Corresponding Zone Numbers
SWITCH XR SERIES, XF6 SERIES FIRE, AND XT75 CONTROL PANELS XR550 AND XF6-500 CONTROL PANELS
TENS ONES LX/LX500 LX600 LX700 LX800 LX900
0 0 500 600 700 800 900
0 1 501 601 701 801 901
0 2 502 602 702 802 902
0 3 503 603 703 803 903
0 4 504 604 704 804 904
... ... ... ... ... ... ...
9 5 595 695 795 895 995
9 6 596 696 796 896 996
9 7 597 697 797 897 997
9 8 598 698 798 898 998
9 9 599 699 799 899 999
Table 3: Keypad Bus Addresses and Corresponding Zone Numbers
KEYPAD BUS ADDRESS SWITCH ZONE NUMBERS
TENS ONES XT SERIES, XR150, AND XF6-100 PANELS XR550 AND XF6-500 PANELS
1 0 1 11 to 14 11 to 14
2 0 2 21 to 24 21 to 24
3 0 3 31 to 34 31 to 34
4 0 4 41 to 44 41 to 44
5 0 5 51 to 54 51 to 54
6 0 6 61 to 64 61 to 64
7 0 7 71 to 74 71 to 74
8 0 8 81 to 84 81 to 84
9 0 9 N/A 91 to 94
10 1 0 N/A 101 to 104
11 1 1 N/A 111 to 114
12 1 2 N/A 121 to 124
13 1 3 N/A 131 to 134
14 1 4 N/A 141 to 144
15 1 5 N/A 151 to 154
16 1 6 N/A 161 to 164

ADDITIONAL INFORMATION

Wiring Specifications

DMP recommends using 18 or 22 AWG for all LX‑Bus and Keypad Bus connections. The maximum wire distance between any module and the DMP Keypad Bus or LX‑Bus circuit is 1,000 feet. To increase the wiring distance, install an auxiliary power supply, such as a DMP Model 505‑12. Maximum voltage drop between a panel or auxiliary power supply and any device is 2.0 VDC. If the voltage at any device is less than the required level, add an auxiliary power supply at the end of the circuit.

To maintain auxiliary power integrity when using 22‑gauge wire on Keypad Bus circuits, do not exceed 500 feet. When using 18‑gauge wire, do not exceed 1,000 feet. Maximum distance for any bus circuit is 2,500 feet regardless of wire gauge. Each 2,500 foot bus circuit supports a maximum of 40 LX‑Bus devices.

For additional information refer to the following documents:

  • LX‑Bus/Keypad Bus Wiring Application Note (LT‑2031)
  • 710 Bus Splitter/Repeater Module Installation Guide (LT‑0310)

Optional Accessories

You can replace the standard wiring harness with the optional 718T Plug‑in Screw Terminal. The enclosure base can also accommodate the 719T Terminal Boards for the 714 or the 720T Terminal Boards for the 715, both of which pass through panel LX‑Bus wiring. The 719T includes 1k EOL resistors. The 720T includes 3.3k EOL resistors.

LED Operation

The LED on the zone expanders flashes each time the module responds to a poll from the panel. If there is a problem with the hardware, panel programming, or the green data wire between the panel and the zone expander module, the LED stops flashing and System Trouble appears in the keypad display.

SPECIFICATIONS

Operating Voltage 12 VDC
714 Operating Current 7 mA + 1.6 mA per zone
714 Zone Voltage 5 VDC, max 2 mA
715 Operating Current 7 mA + 4 mA per active zone
+ 30 mA per smoke in alarm
+ 58 mA per zone shorted
715 Zone Voltage 12 VDC, max 34 mA per test results
Zone Operating Range 9.7 to 14 VDC
Dimensions 4.50 W x 2.75 H x 1.75 D in
11.43 W x 6.99 H x 4.45 D cm
Zones 4 Supervised Class B Power Limited

COMPATIBILITY

  • XT Series Control Panels
  • XR Series Control Panels
  • XF6 Series Fire Control Panels

DMP
2500 North Partnership Boulevard
Springfield, Missouri 65803-8877
800.641.4282 | DMP.com

Documents / Resources

References

Download manual

Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.

Download DMP 714, 715 Manual

Advertisement

Need help?

Need help?

Do you have a question about the 714 and is the answer not in the manual?

Questions and answers

Table of Contents