Page 1
32 tri /3 High temperature, modulating Heat Pump Installation and User manual 32 tri /3 Ref. 151460 Made in France Manual ref. : 1898466 Edition n : 25.17 0082...
Page 2
32 kW TRI /3 HIGH TEMPERATURE HEAT PUMP INSTALLER MANUAL...
1 - PLEASE READ IMMEDIATELY The high temperature Heat Pump absorbs the 1.1 - Important information calories present in exterior air, and transforms These installation and operating instructions them into useful energy which is then transferred form part of the appliances which they refer to. to the heating water for your home.
• It is FORBIDDEN : The HRC Heat Pump uses R290 refrigerant fl uid. Given the flammable nature of the fluid, any - To operate the Heat Pump using air intake work on the refrigerant circuit must be done with containing solvents or explosive materials.
Manufacturer’s identity AUER 151460 Rue de la République Réf : Certifi cation agency 80210 Feuquières en Vimeu intuis reference of the appliance Pompe à chaleur Appliance type Ser.n° : 151460-242300000 Serial number of the appliance Protection rating 400 V 3N~ 50 Hz Appliance electric data PED cat.
1.5 - Delivery terms and conditions 2 - INTRODUCTION In general, the material is transported at the recipient’s own risk. 2.1 - Standard confi guration It is important to verify that all of the elements have been received and that no damage has been sustained during transport upon The unit consists of an outdoor module (high-temperature monobloc receipt of the appliance and before beginning the installation heat pump, preferably installed outdoors.
2.2 - Operation 3 - INSTALLATION The Heat Pump is a closed and pressurised system in which the refrigerant serves as the medium for transferring energy. 3.1 - Installing the Heat Pump A safety pressure switch is used on the refrigeration circuit, it is located on the high pressure part of the circuit at the output of the The Heat Pump must always be transported in a vertical position, compressors.
3.1.1.1 - Seaside installation Generally speaking, the components of our products are treated to resist corrosion, but traces may nevertheless appear, aff ecting the aesthetics without compromising the operation of the appliance. In areas close to the coast, the salty air, which is particularly corrosive and often laden with sand particles, can accelerate the degradation of materials, which is why, without being exhaustive, we recommend certain precautions:...
3.1.2 - Placement Always make sure the heat exchanger fi ns are The heat pump is designed to be installed preferably outdoors, with protected when handling the appliance. a clear space around the appliance, in an area free from excessive dust.
3.1.3 - Condensates drainage When the appliance is operating in frost protection mode, the condensed water must be drained off . In order for the condensates to drain properly, the drainage trough and hole must be clean and free of all debris (leaves, grass, etc...). If the condensates drainage pipe is connected to the rainwater run-off system, it is advised to use a siphon.
3.1.4 - Safe area The heat pump contains a fl ammable refrigerant. In case of leak, the refrigerant could accumulate near the ground (higher density than air). or spread through openings in the building. In order to limit the risk of a toxic, suff ocating, explosive or dangerous atmosphere, a safety perimeter must be established around the machine.
3.2.4 - Heat Pump water inlet fi lter (supplied) 3.2 - Hydraulic installation A 1’’1/4 fi lter must be installed on the water inlet piping on the Heat Pump: It is MANDATORY to read the additional • Respect the direction of fl ow on the fi lter (arrow on the document concerning the quality of valve) water used for fi lling the installation.
3.3 - Electrical control connections The Heat Pump is pre-equipped with a non-polarised, 2-core sheathed cable (communication bus). This 10 m cable is supplied with, and already connected to, the Heat Pump. It must be connected to the Pilot. If the connection needed is longer than 10 m replace this cable with a 20 m cable which is available to order (Ref. 753102). It is MANDATORY to connect the shielding of the connection cable on the terminal block «GND».
3.4 - Connecting to the power supply Note: The wires must be stripped to the following lengths : Ensure that the power supply is suffi cient to supply both the Heat - for the 2,5 mm² control terminals: between 10 and 12 mm; Pump and the electrical back-up if necessary, taking into account - for the mains power terminal between 18 and 20 mm.
Page 16
Make sure to strip the cable before placing it into the 3.4.3 - HRC Heat Pump: 400 V three-phase terminals, and make sure that the copper is in good connection condition. A method of disconnection must always be installed in compliance Ground Neutral with the installation rules.
3.4.4 - Electrical protection of the compressors 4 - MAINTENANCE AND The HRC Heat Pump is equipped with progressive starters to limit TROUBLESHOOTING the intensity of the current when the motor starts-up, in compliance with the limits set by the NF C 15 100 standard, which is: 60A per phase in three-phase.
4.3 - Maintenance on the Heat Pump The HRC Heat Pump contains R290 refrigerant fl uid. It is not subject to regulations concerning greenhouse gasses, and does not necessitate mandatory annual maintenance by a qualifi ed professional. However, it is still recommended to carry out periodic (at least once per year) cleaning of the evaporator fi ns if it is obstructed by dust or leaves : this should be done using a vacuum cleaner or by spraying with water.
Page 19
32 kW TRI /3 HIGH TEMPERATURE HEAT PUMP INSTALLER MANUAL...
6.1 - Limitations of warranty 6.1.2.4 - Electrical connections Cases (not limited) for exclusion from warranty: 6.1.1 - General information - Faulty electrical connection which does not conform to the national standards in eff ect. The warranty does not apply to defects or damage caused by - Not following the electrical connection diagrams provided in situations or events such as: the installer manual.
APPENDICES A1 - Dimensions A2 - Technical specifi cations A2.1 - General characteristics 32 kW tri /3 Maximum temperature 70°C R290 refrigerant fl uid 1.400 kg Air temperature Maximal pressure of the refrigerant Low pressure : 17 bar sensor High pressure : 31 bar circuit 2-core sheathed cable for Heat Pump / Pilot...
• For new installations : (less than 6 months old): A5 - Treatment of the water in the - Clean the installation with a universal cleaner to eliminate heating circuit the debris from the installation (copper, fi bres, soldering fl uxes) Example : SENTINEL X300 or SENTINEL X800. - Thoroughly rinse the installation until the water runs clear, It is MANDATORY to read the additional with no traces of impurities left.
Page 27
When using a concentrated protect which needs to be diluted with water, mix the water+anti-freeze+inhibitor mixture together prior to inserting it into the installation. RENDERING THE WARRANTY NULL AND VOID All deterioration of the appliance due to an inappropriate quality of water and/ or the presence of corrosion in the absence of treatment products as described above, and/or an improper purging of air of the installation will...
A6 - HRC 32 kW tri /3 Heat Pump INTERNAL WIRING DIAGRAM TsPAC : Water outlet temperature sensor TePAC : Water inlet temperature sensor Tdégiv : De-icing temperature sensor Tair : Air intake temperature sensor Tcomp1 : Compressor 1 temperature sensor Tcomp 2 : Compressor 2 temperature sensor : Compressor 1 high pressure switch : Compressor 2 high pressure switch...
Page 29
22-a 22-b 32 kW TRI /3 HIGH TEMPERATURE HEAT PUMP INSTALLER MANUAL...
5000 Coordonnées de contact / Contact details intuis, rue de la République 80210 Feuquières-en-Vimeu Les précautions particulières qui doivent être prises lors du montage, l'installation et l'entretien, sont décrites dans la notice d'installation et d'utilisation. All specific precautions for assembly, installation and maintenance are described in the operating and installation instructions. Read and follow the operating and installation instructions .
A8 - Electricity provider information form This form is to given to the electricity provider for all preliminary evaluation for the installation of an HRC Heat Pump in case of an insuffi cient power grid. This table contains information on both electrical and technical data about the HRC Heat Pump. This technical data is provided in the table §...
Page 32
NOTES : www.intuis.fr Industrial and development site Rue de la République CS 40029 80210 Feuquières-en-Vimeu Customer service 0)9 78 45 10 26 +33 ( service-consommateur@intuis.fr service-client@intuis.fr...
Need help?