The data above is based on the Evo heat pump only, it does not include auxiliary devices. Product specification information provided above is correct at the date of printing, this data may change without notice. Please speak with an EvoHeat Specialist for the most current product specifications.
Page 3 Evo Dynamic-i Pro Manual 2. Dimensions Water Outlet Water Inlet Dynamic-i Pro A (L) B (W) C (H) 1101 96.1 60 & 703 1265 96.2 info@evoheat.com.au 1300 859 933 www.evoheat.com.au...
3. Quick Start Guide BEFORE YOU START Register Your Warranty Registering your EvoHeat product protects your investment by safeguarding your warranty for future reference. This enables our team to retrieve the relevant information regarding your purchase quickly and efficiently, to fulfil any service requirements.
NOTE: The water pump must be running and water circulating through the heat pump for the system to operate. 1. Turn on your water filter pump and check for water leaks and verify flow to and from the pool. 2. Turn on the electrical power supply to the EvoHeat unit 3. Press the ON/OFF button of the controller to be green for on (off is white), it will start within 60 seconds 4.
Do not use any means to accelerate the defrosting processor or to clean The unit is equipped with other than those recommended by EvoHeat. an over-load protection The unit must be stored in a room without any continuously operating system.
5.1 System Installation Upon receiving the unit, check the packaging for any obvious signs of damage. Inform EvoHeat immediately if there is any evidence of rough handling. When the heater has been removed from the packaging check the refrigerant gauge on the front panel of the unit.
5.4 Adequate Water Flow All EvoHeat heat pumps have a factory pre-set internal water flow switch. If there is insufficient water flow the unit will not operate. It is VITAL that that there is sufficient water flow to the unit. Incorrect water flow can cause a loss of efficiency and possible damage to the unit.
5.12 Initial Start-Up Refer to the Quick Start Guide in this manual for instructions on the initial start-up and commissioning of the unit. info@evoheat.com.au 1300 859 933 www.evoheat.com.au...
Lock or unlock the screen (password: 022) 6.2 Operating Functions EvoHeat have developed a YouTube Channel with video walkthroughs of the different controller functions. Scan the QR code or head to our channel to view the videos we have available https://www.youtube.com/@evoheatpumps 6.2.1 Startup &...
4:00. Click ‘OFF’ to turn off the timing silent manually, however the value can be precise to the hour digit. unit will turn off this setting once it reaches the end time. info@evoheat.com.au 1300 859 933 www.evoheat.com.au...
6.2.9 Unlocking & Locking the Controller To lock or unlock the controller, access the main menu and select the lock symbol button. When prompted for a password, simply enter 022, this is the default password and cannot be changed. info@evoheat.com.au 1300 859 933 www.evoheat.com.au...
For the full instruction manual for the Solar Smart function, please scan the QR Code or access the manual on our website. info@evoheat.com.au 1300 859 933 www.evoheat.com.au...
1. Change a new fan motor 2. The wire connection between DC-fan Fan Motor2 Fault F032 2. Check the wire connection and make sure they motor module and fan motor is in bad are in good contact contact info@evoheat.com.au 1300 859 933 www.evoheat.com.au...
Check and adjust the current measurement EEPROM Error Warn MCU error Check whether the chip is damaged Replace the chip V15V over/undervoltage The V15C is overload or undervoltage Check the V15V input voltage in range 13.5v~16.5v or not fault info@evoheat.com.au 1300 859 933 www.evoheat.com.au...
2 x 35mm 3 x 35mm 35mm 160A 123~148A 2 x 50mm 3 x 50mm 50mm 225A 148~186A 2 x 70mm 3 x 70mm 70mm 250A 186~224A 2 x 95mm 3 x 95mm 95mm 280A info@evoheat.com.au 1300 859 933 www.evoheat.com.au...
DO I NEED TO GET MY UNIT SERVICED? It is recommended that you get your EvoHeat unit serviced every two years by your local certified air conditioning or refrigeration technician. If your unit is located in a coastal area, more frequent maintenance may be necessary.
Prior to recharging the system, it shall be pressure tested with OFN. The system shall be leak tested on completion of charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving the site. The safety wire model is 5*20_5A/250VAC, and must meet the explosion-proof requirements. info@evoheat.com.au 1300 859 933 www.evoheat.com.au...
Page 23
(by means of shut off valves) in a part of the system remote from the leak. Oxygen free nitrogen (OFN) shall then be purged through the system both before and during the brazing process. info@evoheat.com.au 1300 859 933 www.evoheat.com.au...
Page 24
Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked. info@evoheat.com.au 1300 859 933 www.evoheat.com.au...
When a unit is installed by an unqualified person. When failure occurs due to improper or incorrect installation. g) Where failure occurs due to failure of any other equipment connected in relation with the EvoHeat unit (e.g. power supply, water pump etc.).