D(M)S-70 Series Installation, Operation & Maintenance Manual Technical Specifications - D(M)S-70 Series Actuator DS24-70-(A) DS24-70-T-(A) DMS24-70-(A) DS120-70-(A) Spring Return Spring Return Spring Return Spring Return Actuator Models On/Off On/Off & Floating Modulating On/Off with optional Auxiliary with optional Auxiliary with optional Auxiliary with optional Auxiliary Switches (-A) Switches (-A)
Page 3
To avoid excessive wear or drive time on the motor, use a controller and/or software that provides a time-out function to remove the signal at the end of rotation (stall). Disclaimer - The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the nearest Bray office.
Page 4
D(M)S-70 Series Installation, Operation & Maintenance Manual Continued Applications IMPORTANT: The D(M)S24-70 Series On/Off, Modulating and Use this D(M)S24-70 Series Electric Spring Return Floating Point Electric Spring Return Actuators are Actuator only to control equipment under normal direct-mount actuators that operate on AC/DC 24 V operating conditions.
D(M)S-70 Series Installation, Operation & Maintenance Manual Continued Installation: The D(M)S24-70 Series Electric Spring Return Actuators mount directly to the surface in any convenient orientation using two No. M3.5 x 9.5 mm self-drilling sheet metal screws and the anti-rotation bracket (parts included with the actuator). No additional linkages or couplers are required.
D(M)S-70 Series Installation, Operation & Maintenance Manual Continued Manual Override: Use only the supplied manual override crank to reposition the actuator hub when using the manual override feature. IMPORTANT: Applying excessive torque to the manual override or operating the manual override with a power tool may damage the internal components of the Figure 4: Positioning the Anti-Rotation Bracket actuator and cause premature failure.
Page 7
D(M)S-70 Series Installation, Operation & Maintenance Manual Continued 10. Apply power long enough for the actuator to travel a full stroke. Verify that the actuator 3-9/32 rotates freely throughout the range. 2-1/4 (83.5) (57.5) NOTE: If electric power is not available, complete this verification by reinserting the manual override crank and turning it in the direction indicated to rotate Self-Drilling Sheet...
D(M)S-70 Series Installation, Operation & Maintenance Manual Continued IMPORTANT: Careful workmanship is required to secure flexible metal conduit. Cut the conduit end perpendicular to its axis. Insert the cut end into the bottom of the holes in the actuator and hold the conduit in place while securing it with the screws provided.
Insulate and secure each unused wire lead before operate within its specifications, contact the applying power to the actuator. Failure to insulate nearest Bray Commercial representative and secure each unused wire lead may result in property damage, electric shock, and severe personal injury or death.
<52 dBA at 70 lb·in. (8 N·m) Load - (All at a Distance of 39-13/32 in. (1 m)) All DS-70 Series actuators are designed for use only in conjunction with operating controls. Where an operating control failure would result in personal 22 Seconds Nominal at Full Rated Load, 94 Seconds Maximum with 70 lb·in (8 N·m) Load, at -40°F (-40°C...