AERMEC ANL021 Technical Manual
AERMEC ANL021 Technical Manual

AERMEC ANL021 Technical Manual

Hide thumbs Also See for ANL021:
Table of Contents

Advertisement

Quick Links

2 3 . 0 5 – 5 5 2 3 4 3 6 _ 0 8
T r a n s l a t i o n o f O r i g i n a l i n s t r u c t i o n s
ANL 021-202
Technical manual
AIR-WATER CHILLER

C o o l i n g c a p a c i t y 5 , 7 0 ÷ 4 3 , 0 0 k W
w w w . a e r m e c . c o m

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ANL021 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for AERMEC ANL021

  • Page 1 2 3 . 0 5 – 5 5 2 3 4 3 6 _ 0 8 T r a n s l a t i o n o f O r i g i n a l i n s t r u c t i o n s ANL 021-202 Technical manual AIR-WATER CHILLER...
  • Page 3 Dear Customer, Thank you for wanting to learn about a product Aermec. This product is the result of many years of experience and in-depth engineering research, and it is built using top quality materials and advanced technologies. The manual you are about to read is meant to present the product and help you select the unit that best meets the needs of your system.
  • Page 4 All specifications are subject to change without prior notice. Although every effort has been made to ensure accuracy, Aermec shall not be held liable for any errors or...
  • Page 5: Ec Declaration Of Conformity

    This declaration of conformity has been released under the exclusive responsibility of the manufacturer. We also declare that, at the time this preloaded equipment was placed on the European market by Aermec S.p.A. (which imports or manufactures in the Union), the hydro- fluorocarbons contained therein are considered in the unit system of the Union referred to in Chapter IV of EU Regulation 517/2014 as they were placed on the market by a manufacturer or importer of hydrofluorocarbons to which Article 15 of EU Regulation 517/2014 applies.
  • Page 6 Conformity (doc. “List of components for Declaration of Conformity”). We also declare that, at the time this preloaded equipment was placed on the European market by Aermec S.p.A. (which imports or manufactures in the Union), the hydro- fluorocarbons contained therein are considered in the unit system of the Union referred to in Chapter IV of EU Regulation 517/2014 as they were placed on the market by a manufacturer or importer of hydrofluorocarbons to which Article 15 of EU Regulation 517/2014 applies.
  • Page 7 We, the undersigned, hereby declare under our own responsibility that the assembly in question, defined as follows: Name: ANL Type: Air-water chiller Models: ANL021, ANL026, ANL031, ANL041, ANL050, ANL070, ANL080, ANL090, ANL102, ANL152, ANL202 to which this declaration refers, complies with all the provisions related to the following directives: S.I. 2016 No.1101 S.I.
  • Page 8: Table Of Contents

    TABLE OF CONTENTS 1. Product description 9. Cleaning micro-channel coil ................p. 9 ............p. 19 2. Configurator 10. Performance specifications .....................p. 9 ............p. 20 12 °C / 7 °C ....................p. 20 3. Unit components description ............. p. 10 11. Energy data .................... p. 22 Refrigerant circuit ................... p. 10 Hydraulic circuit ..................
  • Page 9: Product Description

    PRODUCT DESCRIPTION ANL outdoor air-cooled chillers with R410A refrigerant have been designed and The units are characterised by an extremely low noise operation and a high effi- manufactured to meet heating and cooling requirements in medium to small-sized ciency and reliability, through the use of high efficiency heat exchangers and scroll residential, commercial or industrial buildings.
  • Page 10: Unit Components Description

    UNIT COMPONENTS DESCRIPTION REFRIGERANT CIRCUIT Air drain valve Mounted at the highest level of the hydraulic system. The air vent is used for the release of any air pockets from the hydraulic circuit. Compressors  Of automatic type in sizes 102-202 A and Q Crankcase heaters as standard, automatically activated when the unit stops, as long as power is maintained to the unit.
  • Page 11 — Inverse condensation check for the heat pump functioning mode also in sum- — Water inlet mer (with DCPX accessory) — Coil temperature (heat pump unit) — Pre-alarms with automatic reset: in case of alarms a number of restarts are per- —...
  • Page 12: Main Hydraulic Circuits

    MAIN HYDRAULIC CIRCUITS INTERNAL AND EXTERNAL HYDRAULIC CIRCUIT WITH ANL ° (STANDARD) Components as standard Components not provided and responsibility of the Pressure gauge installer Plate heat exchanger Storage tank Differential pressure switch Anti-vibration joints Pressure relief valve Water temperature sensors (IN/OUT) Flow shut-off valves Expansion vessel Water filter...
  • Page 13: Internal And External Hydraulic Circuit With Anl P/N

    INTERNAL AND EXTERNAL HYDRAULIC CIRCUIT WITH ANL P/N Components as standard Pressure relief valve Air drain valve Plate heat exchanger Water filter Pressure gauge Differential pressure switch (021÷090) - Flow Air drain valve Expansion vessel Components not provided and responsibility of switch (102÷202) Storage tank the installer...
  • Page 14: Internal And External Hydraulic Circuit With Anl A/Q

    INTERNAL AND EXTERNAL HYDRAULIC CIRCUIT WITH ANL A/Q Internal and external hydraulic circuit with ANL A (021÷041) * ATTENTION: Flooded heat exchanger inside the storage tank Internal and external hydraulic circuit with ANL A/Q (050÷202) Components as standard Components not provided and responsibility of Water filter the installer Plate heat exchanger...
  • Page 15: Main Cooling Refrigerant Layouts

    MAIN COOLING REFRIGERANT LAYOUTS ANL COOLING ONLY Components Finned coil Compressor Plate heat exchanger Mechanic thermostatic valve Filter drier ANL COOLING ONLY WITH DESUPERHEATER Components Finned coil / microchannel Desuperheater (optional) Compressor Plate heat exchanger Thermostatic expansion valve Solenoid valve Sight glass Filter drier  ANL 021-090 / 1 compressor and 1 coil...
  • Page 16: Accessories

    ACCESSORIES AERBAC-MODU: Ethernet communication Interface for protocols Bacnet/IP, Mod- for the chillers connected to the header, or it can be used for temperature moni- bus TCP/IP, SNMP toring AERLINK: Wifi Gateway with an RS485 serial port that can be installed on all ma- VMF-CRP: Accessory module for controlling boilers, heat recover units and pumps chines or on all controllers having an RS485 serial port themselves.
  • Page 17 KR: electric heater for the plate heat exchanger °,P KR100 KR100 KR100 KR100 KR100 KR100 KR100 KR100 KR100 A grey background indicates the accessory must be assembled in the factory RA: electric heater for the buffer tank RA100 RA100 RA100 RA100 RA100 RA100...
  • Page 18: Selection Criteria Of The Heat Exchangers According To The Place Of Installation Of The Unit

    SELECTION CRITERIA OF THE HEAT EXCHANGERS ACCORDING TO THE PLACE OF INSTALLATION OF THE UNIT The guide provides advice for applications. Although recommendations ing ship engine exhaust, industrial production, chemical treatment facilities (cool- are given, all the details about the real world application of our prod- ing towers in the vicinity) and fossil fuel power plants.
  • Page 19: Basic Principles On Microchannel Coil Corrosion

    BASIC PRINCIPLES ON MICROCHANNEL COIL CORROSION The main material in Aermec heat exchangers is aluminium. Temperature Aluminum is a very reactive metal, which is easily oxidized on its surface. As long Chemical reactions generally depend on the temperature, for reactions that involve...
  • Page 20: Performance Specifications

    10 PERFORMANCE SPECIFICATIONS 12 °C / 7 °C ANL - ° (400V 3N ~ 50Hz / 230V ~ 50Hz) Size POWER SUPPLY: ° Cooling performance 12 °C / 7 °C (1) Cooling capacity 13,4 16,4 20,4 22,2 26,5 32,9 42,8 Input power 10,2 13,5...
  • Page 21 ANL - P (400V 3N ~ 50Hz / 230V ~ 50Hz) Size POWER SUPPLY: ° Cooling performance 12 °C / 7 °C (1) Cooling capacity 13,5 16,6 20,6 22,4 26,8 33,2 43,2 Input power 10,5 13,8 Cooling total input current 10,0 13,0 13,0...
  • Page 22: Energy Data

    11 ENERGY DATA ENERGY INDICES (REG. 2016/2281 EU) Size SEER - 12/7 (EN14825:2018) with standard fans (1) ° - (2) - (2) - (2) - (2) - (2) - (2) - (2) - (2) - (2) - (2) - (2) 4,18 4,20 4,17...
  • Page 23: General Technical Data

    12 GENERAL TECHNICAL DATA Size Compressor Type °,A,N,P,Q type Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Compressor regulation °,A,N,P,Q Type On-Off On-Off On-Off On-Off On-Off On-Off On-Off On-Off On-Off On-Off On-Off °,A,N,P Number °,A,P Circuits °,A,N,P type R410A R410A...
  • Page 24: Electric Data

    Size °,A,P m³/h 2500 2500 3500 3500 7200 7200 7300 7200 14000 13500 13500 Air flow rate m³/h 14000 13500 13500 m³/h 7200 7200 7300 7200 14000 13500 13500 Sound data calculated in cooling mode (2) °,A,P dB(A) 61,0 61,0 68,0 68,0 69,0...
  • Page 25: Dimensions And Weights

    DIMENSIONS AND WEIGHTS Size Dimensions and weights °,P 1000 1000 1000 1000 1252 1252 1252 1252 1450 1450 1450 1015 1015 1015 1015 1281 1281 1281 1281 1450 1450 1450 1450 1450 1450 1281 1281 1281 1281 1450 1450 1450 °,P 1124 1124...
  • Page 26: Minimum Technical Spaces

    13 MINIMUM TECHNICAL SPACES ANL 021-041 ANL 050-090 ANL 102-202 Size Minimum technical spaces °,A,P 3000 3000 3000 3000 3000 3000 3000 3000 3000 °,A,P °,A,P 1100 1100 1100 1100 1100 1100 1100 1100 1100 °,A,P Free field Free field Free field Free field Free field...
  • Page 27: Operating Range

    14 OPERATING RANGE In their standard configuration, the units are not suitable for installation in salty environments. The values indicated in the table refer to the min. and max. temperature limits of the unit, for further information, refer to the tables of yields and consumptions different from the nominal ones, valid for ΔT = 5°C.
  • Page 28: Operating Range - Double Low Temperature Thermostatic Valve W

    OPERATING RANGE - DOUBLE LOW TEMPERATURE THERMOSTATIC VALVE W Using two electronic valves in parallel guarantees a precise and efficient control in a wide operating range. This allows them to produce chilled water from -10 °C to +18 °C.  The option is only available for sizes from 050 to 090 in the °-A-Q versions and from size 102 to 202 in all versions. °C °C Operation with glycol-water solution...
  • Page 29: Pressure Drops

    15 PRESSURE DROPS 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 12000 13000 14000 l/h Pressure drop (kPa) ANL 041 ANL 102 Water flow rate (l/h) ANL 050 ANL 152 ANL 021 ANL 070 ANL 202 ANL 026 ANL 080 ANL 031 ANL 090...
  • Page 30: Useful Head System

    16 USEFUL HEAD SYSTEM Useful head system (P/A) 2000 4000 6000 8000 10000 12000 Useful head system (kPa) ANL 041 ANL 102 Water flow rate (l/h) ANL 050 ANL 152 ANL 021 ANL 070 ANL 202 ANL 026 ANL 080 ANL 031 ANL 090 Useful head system (Q/N)
  • Page 31: System Water Content

    If you are in any doubt, please refer to the relevant technical documentation or contact the AERMEC Technical-Commercial Service. ATTENTION It is recommended to design systems with high water content (minimum recommended values shown in tab), in order to limit: —...
  • Page 32: Expansion Vessel Setting

    18 EXPANSION VESSEL SETTING The expansion tank volume is 24l. The standard value of the expansion tank pre-charge pressure is 1.5 bar, but this can be calibrated up to a maximum of 6 bar. The expansion tank pressure setting has to be adjusted based on the difference in height (H) of the installation (see figure) according to the formula: p (rating) [bar] = H [m] / 10.2 + 0.3.
  • Page 33: Correction Factors

    19 CORRECTION FACTORS CORRECTIVE FACTORS FOR AVERAGE WATER TEMPERATURES DIFFERENT FROM NOMINAL VALUES System side heat exchanger Cooling mode Heating mode or recovery Average water temperatures °C Correction factor 1,02 1,00 0,98 0,97 0,95 0,93 0,91 1,04 1,03 1,02 1,01 1,00 0,99 0,98...
  • Page 34: Sound Data

    (in compliance with UNI EN ISO 3744). Data 14511:2018 System water temperature 12/7 (in/out) Outside air temperature 35 °C Standard fans Note For operating conditions different to those declared refer to the selection program Magellano, available on www.aermec.com 23.05 – 5523436_08...
  • Page 36 A e r m e c S . p . A . V i a R o m a , 9 9 6 - 3 7 0 4 0 B e v i l a c q u a ( V R ) - I t a l i a T e l .