1. General Information 1.1 Overview Thanks for choosing Jinko Solar PV modules. In order to ensure the PV modules are installed correctly, please read the following installation instructions carefully before modules are installed and used. Please remember that these products generate electricity and certain safety measures need to be taken to avoid danger.
Page 4
All instructions should be read and understood before attempting to install, wire, operate and maintain the module. Don’t lift up PV modules using the attached cables or the junction box. Do not touch live terminals with bare hands. Use insulated tools for electrical connections. ...
to the product. Do not clean the glass with chemicals. Only use tap water. Make sure the module surface temperature is cool to the touch. Cleaning modules with cool water when module surface temp is high may result in glass breakage. Do not brush paint or corrosive substances on the surface of the modules.
Page 6
Keep the PV module packed in the carton until installation. Once the modules are removed from the packing box, they should be installed and connected to the bus box in time. If they are not installed immediately, protective measures (such as adding rubber joint cover, etc.) should be taken on the connection head.
2.2 Installation Condition 2.2.1 Climate Condition Please install the modules in the following conditions: a) Operating temperature: within –40° C(-40℉) to 85° C (185℉) b) Humidity: < 85RH% ﹡Note: The mechanical load bearing (include wind and snow loads) of the module is based on the approved mounting methods.
For standalone systems with batteries where the PV modules are attached to a permanent structure, the tilt angle of the PV modules should be selected to optimize the performance based on seasonal load and sunlight. In general, if the PV output is adequate when irradiance is low (e.g., winter), then the angle chosen should be adequate during the rest of the year.
Page 9
The frame of each module has 8 mounting holes (Length* Width: 14mm*9mm) used to secure the modules to support structure. Always use all the eight mounting holes to secure the modules. The module frame must be attached to a mounting rail using M8 corrosion-proof bolts together with spring washers and flat washers in eight symmetrical locations on the PV module.
Page 10
Height of the frame(mm) Group 1 1650*992 & 1665*1002 Group 2 1665*992 & 1684*1002 Group 3 1650*992 & 1665*1002 Group 4 1665*992 & 1684*1002 Group 5 1650*992 & 1665*1002 Group 6 1665*992 & 1684*1002 Group 7 1650*992 & 1665*1002 Group 8 1665*992 &...
Page 11
Height of the frame(mm) 2096*1039 & 2090*1039 & Group 63 2090*1038 Height of the frame(mm) Group 24 1796*995 & 1796*998 Group 26 1822*1008 Group 28 1822*1008 1840*998 & 1841*1002 Group 32 1868*1008 & 1865*1005 Group 34 1868*1008 & 1865*1005 Group 36 1840*998 &...
Page 12
2.3.1.2 Mounting with Bolts(four mounting holes) Figure 3: PV module installed with bolt fitting method(four mounting holes) Max. Design Pressure: 3600Pa (positive ) &1600Pa (negative) mechanical load Module type Module dimensions(mm) Height of the frame(mm) Group 1 1650*992 & 1665*1002 Group 2 1665*992 &...
Page 13
Group 19 2031*1008 Group 21 2008*1002 Group 29 2031*1008 Group 45 2008*1002 Group 55 2008*1002 2250*1122 & 2260*1130 & Group 71 & 80 2271*1132 & 2274*1134 2209*1130 & 2206*1122 & Group 72 & 81 2227*1132 & 2230*1134 Height of the frame(mm) Group 24 1796*995 &...
Page 14
Group 53 2166*1002 2393*1130 & 2385*1122 & Group 73 & 82 2408*1132 & 2411*1134 Table 2: Mechanical dimensions for bolt fitting method(four mounting holes) Note: The installation method of bolt fitting (four mounting holes) is based on the internal results in Jinko. According to IEC 61215 for a maximum positive design loading of below 3600Pa, and negative design loading 1600Pa, with 1.5 times safety factor.
Group 27 2130*1002 & 2139*1008 Group 31 2163*995 & 2167*997 & 2167*998 & 2166*1002 Group 33 2194*1008 & 2190*1005 Group 35 2194*1008 & 2190*1005 Group 37 2163*995 & 2167*997 & 2167*998 & 2166*1002 Group 39 2168*1021 & 2168*1024 & 2182*1029 & 2182*1032 Group 41 2194*1034 &...
Page 16
Middle modules installation Fringe modules installation Figure 5: PV module installed at the side with Clamp fitting method Composition Clamp type Dimension(mm) material End Clamp 39 x 50 x 42 (40 mm thickness) 39 x 60 x 42(For 1.5mm thickness frame) End Clamp 41.5 x 50 x 40 (35 mm thickness)
Page 17
types and installation locations are shown in figure 8 and table 7. When installing modules using clamps on the long side of the frame, the applicable product types and installation locations (The without C transparent backsheet series module) are shown in figure 9 and table 8.
Page 18
Group 22 1684*1002 Group 30 1704*1008 Group 46 1684*1002 Group 57 1693*1029 Group 58 1693*1029 Group 59 1716*1032 Group 60 1716*1032 Group 56 1684*1002 1756*1039 & 1750*1039 & Group 64 1750*1038 Group 61 1693*1029 & 1692*1029 Group 62 1693*1029 & 1692*1029 1884*1122 &...
Page 19
Group 42 1868*1034 & 1878*1032 Group 44 1868*1034 & 1878*1032 1842*1021 & 1842*1024 & Group 48 1855*1029 & 1855*1032 1842*1021 & 1842*1024 Group 50 & 1855*1029 & 1855*1032 1842*1021 & 1842*1024 Group 52 & 1855*1029 & 1855*1032 1840*998*35(NP) Group 54 1841*1002*30(CDF)...
Page 20
2.3.2.2 Clamp Mounting on Short Sides of the Frames Figure 7: Installation of clamps on short side of frames 1067Pa (positive ) 1067Pa (positive ) Max. Design Pressure: &1067Pa (negative) &1067Pa (negative) mechanical load mechanical load Module type Module dimensions(mm) Height of the frame(mm)...
Page 21
Group 17 1987*992 & 2008*1002 1987*992 & 2008*1002 & Group 18 2031*1008 Group 19 2031*1008 Group 21 2008*1002 Group 29 2031*1008 Group 45 2008*1002 Height of the frame(mm) Group 24 1796*995 & 1796*998 Group 26 1822*1008 Group 28 1822*1008 1840*998 & 1841*1002 Group 32 1868*1008 &...
Page 22
Max. Design 1600Pa (positive ) &1600Pa 1600Pa (positive ) &1600Pa (negative) Pressure: (negative) mechanical load mechanical load Module type Module dimensions(mm) Height of the frame(mm) 1650*992 & Group 1 1665*1002 1665*992 & Group 2 1684*1002 1650*992 & Group 3 1665*1002 1665*992 &...
Page 23
Group 19 2031*1008 Group 21 2008*1002 Group 29 2031*1008 Group 45 2008*1002 Height of the frame(mm) 1796*995 & Group 24 1796*998 Group 26 1822*1008 Group 28 1822*1008 1840*998 & Group 32 1841*1002 1868*1008 & Group 34 1865*1005 1868*1008 & Group 36 1865*1005 L/4±...
Page 24
2194*1034 & Group 41 2205*1032 2194*1034 & Group 43 2205*1032 2168*1021 & 2168*1024 & Group 47 2182*1029 & 2182*1032 Table 7: Mechanical dimensions of modules installed with clamps on short side of frame Note:The installation method of clamps on long and short sides is based on the internal results in Jinko. According to IEC 61215 for a maximum positive design loading of below 1600Pa, and negative design loading 1600Pa, with 1.5 times safety factor.
2194*1008 & 2190*1005 Group 33 2194*1008 & 2190*1005 Group 35 Group 41 2194*1034 & 2205*1032 Group 43 2194*1034 & 2205*1032 Table 8: Mechanical dimensions when modules installed at long side with Clamp fitting method According to IEC 61215 for a maximum positive design loading of below 3600Pa, and negative design loading 1600Pa, with 1.5 times safety factor.
Page 26
Figure 10:Ground installation of PV modules f) Follow the requirements of applicable local and national electrical codes. g) These modules contain factory installed by pass diode .If these modules are incorrectly connected to each other, the bypass diodes, cable or junction box may be damaged. h) The cable of the junction box is defined as L, as showed below in Figure 11.
i) It is recommend to use negatively grounded inverters to avoid the PID effect for non-PID free modules. j) If modules are connected in series, the total voltage is equal to the sum of individual voltages. The recommended as below, System voltage≥N*Voc[1+TCVoc* (Tmin-25)] Where module numbers in series...
c) In order to reduce the potential for electrical and thermal shock, Jinko recommends cleaning PV modules during early morning or late afternoon hours when solar radiation is low and the modules are cooler, especially in regions with hotter temperatures. d) Never attempt to clean a PV module with broken glass or other signs of exposed wiring, as this presents a shock hazard.
Appendix 1: Applicable Products This document is applicable to the series of solar modules as listed below: With 6” poly and mono c-Si: Group 1 JKMxxxPP ① JKMxxxPP-60(Plus) ② JKMS ③ xxxPP-60 JKMSxxxPP-60-J ④ JKMxxxPP-60-V JKMxxxPP-60(Plus) -V JKMSxxxPP-60-V JKMSxxxPP-60-V-J JKMxxxPP-60B (xxx=260~290,in increment of 5) Group 2 JKMxxxPP-60H...
Page 30
Group 8 JKMSxxxM-60H-V-MX3 JKMSxxxM-60HB-V-MX3 JKMSxxxM-60H-MX3 JKMSxxxM-60HB-MX3 JKMSxxxM-60HL-V-MX3 JKMSxxxM-60HBL-V-MX3 JKMSxxxM-60HL-MX3 JKMSxxxM-60HBL-MX3 (xxx =270~340,in increment of 5) Group 9 JKMxxxM-60H-TV JKMxxxM-60HL-TV JKMxxxM-60H-T JKMxxxM-60HL-T (xxx =315~355,in increment of 5) JKMxxxN-60H-TV JKMxxxN-60HL-TV JKMxxxN-60H-T JKMxxxN-60HL-T (xxx =315~355,in increment of 5) Group 10 JKMxxxPP-72 JKMxxxPP-72(Plus) JKMSxxxPP-72 JKMSxxxPP-72-J JKMxxxPP-72-V JKMxxxPP-72(Plus)-V...
Page 31
JKMSxxxM-72-V-MX3 JKMSxxxM-72B-V-MX3 JKMSxxxM-72-MX3 JKMSxxxM-72B-MX JKMSxxxM-72L-V-MX3 JKMSxxxM-72BL-V-MX3 JKMSxxxM-72L-MX3 JKMSxxxM-72BL-MX3 (xxx =335~395,in increment of 5) Group 17 JKMSxxxM-72H-V-MX3 JKMSxxxM-72HB-V-MX3 JKMSxxxM-72H-MX3 JKMSxxxM-72HB-MX3 JKMSxxxM-72HL-V-MX3 JKMSxxxM-72HBL-V-MX3 JKMSxxxM-72HL-MX3 JKMSxxxM-72HBL-MX3 (xxx =335~395,in increment of 5) Group 18 JKMxxxM-72H-TV JKMxxxM-72HL-TV JKMxxxM-72H-T JKMxxxM-72HL-T (xxx =375~425,in increment of 5) JKMxxxN-72H-TV JKMxxxN-72HL-TV JKMxxxN-72H-T JKMxxxN-72HL-T...
Page 32
(xxx =345~370,in increment of 5) Group 29 JKMxxxM-72H-MBB-TV JKMxxxM-72H-MBB-T (xxx =385~405,in increment of 5) Group 30 JKMxxxM-60H-MBB-TV JKMxxxM-60H-MBB-T (xxx =320~335,in increment of 5) Group 31 JKMxxxM-78H-V JKMxxxM-78H JKMSxxxM-78H-V-TI JKMSxxxM-78H-TI (xxx =405-465,in increment of 5) Group 32 JKMxxxM-66H-V JKMxxxM-66H JKMSxxxM-66H-V-TI JKMSxxxM-66H-TI (xxx =340-390,in increment of 5) Group 33 JKMxxxM-78H-TV...
Page 33
(xxx = 420~475,in increment of 5) Group 42 JKMxxxM-6RL3-T JKMxxxM-6RL3-TV-J JKMxxxM-6RL3-T-J JKMxxxM-6RL3-TV (xxx = 355~400,in increment of 5) Group 43 JKMxxxN-7RL3-T JKMxxxN-7RL3-TV-J JKMxxxN-7RL3-T-J JKMxxxN-7RL3-TV (xxx = 425~475,in increment of 5) Group 44 JKMxxxN-6RL3-TV JKMxxxN-6RL3-T JKMxxxN-6RL3-TV-J JKMxxxN-6RL3-T-J (xxx = 355~400,in increment of 5) Group 45 JKMxxxN-72H-MBB-V JKMSxxxN-72H-MBB-TI...
Page 34
Group 54 JKMxxxM-66H-MBB JKMxxxM-66H-MBB-V JKMSxxxM-66H-MBB-TI JKMSxxxM-66H-MBB-V-TI JKMSxxxM-66H-MBB-V- (xxx = 370~390,in increment of 5) Group 55 JKMxxxN-72H-MBB-B JKMxxxN-72H-MBB-B-V JKMxxxN-72H-MBB-B-TI JKMxxxN-72H-MBB-B-V- TI (xxx = 380-400,in increment of 5) Group 56 JKMxxxN-60H-MBB-B JKMxxxN-60H-MBB-B-V JKMxxxN-60H-MBB-B-TI JKMxxxN-60H-MBB-B-V-TI (xxx = 315-330,in increment of 5) Group 57 JKMxxxM-6TL3-V JKMxxxM-6TL3 JKMSxxxM-6TL3-V-TI...
Page 35
JKMxxxM-60HLM-B-V JKMSxxxM-60HLM-B-V-MX3 (xxx =350-370,in increment of 5) JKMxxxM-60HLM-TV (xxx = 355-380 ,in increment of 5) Group 65 JKMxxxM-54HL4-V JKMxxxM-54HL4 (xxx = 360-415,in increment of 5) JKMxxxM-54HL4-B-V JKMxxxM-54HL4-B (xxx = 380-400,in increment of 5) JKMxxxM-54HL4-TV (xxx = 360-410,in increment of 5) Group 66 JKMxxxM-5RL4-V JKMxxxM-5RL4...
Page 36
Group 70 JKMxxxM-6RL4-V JKMxxxM-6RL4 (xxx = 455-495,in increment of 5) JKMxxxM-6RL4-B-V JKMxxxM-6RL4-B (xxx = 455-485,in increment of 5) JKMxxxM-6RL4-TV (xxx = 445-495,in increment of 5) Group 71 JKMxxxM-72HL4-V-J JKMxxxM-72HL4-J JKMxxxM-72HL4-V JKMxxxM-72HL4 (xxx = 475-555,in increment of 5) JKMxxxM-72HL4-B-V JKMxxxM-72HL4-B (xxx = 510-535,in increment of 5) JKMxxxM-72HL4-TV JKMxxxM-72HL4-TV-J (xxx = 475-550,in increment of 5)
Page 37
(xxx = 375-395,in increment of 5) JKMxxxN-5RL4-TV (xxx = 365-405,in increment of 5) Group 76 JKMxxxN-60HL4-V JKMxxxN-60HL4 (xxx = 405-460,in increment of 5) JKMxxxN-60HL4-B-V JKMxxxN-60HL4-B (xxx = 425-445,in increment of 5) JKMxxxN-60HL4-TV (xxx = 400-450,in increment of 5) Group 77 JKMxxxN-6TL4-V JKMxxxN-6TL4 (xxx = 415-450,in increment of 5)
Page 38
JKMxxxN-7TL4-V JKMxxxN-7TL4 JKMxxxN-7TL4-V-J JKMxxxN-7TL4-J (xxx = 495-570,in increment of 5) JKMxxxN-7TL4-B-V JKMxxxN-7TL4-B (xxx = 495-530,in increment of 5) JKMxxxN-7TL4-TV JKMxxxN-7TL4-TV-J (xxx = 480-570,in increment of 5) Group 82 JKMxxxN-7RL4-V JKMxxxN-7RL4 JKMxxxN-7RL4-V-J JKMxxxN-7RL4-J (xxx = 535-590,in increment of 5) JKMxxxN-7RL4-B-V JKMxxxN-7 RL4-B (xxx = 540-575,in increment of 5) JKMxxxN-7RL4-TV JKMxxxN-7RL4-TV-J...
Appendix 2:Electrical Specifications Rated Rated Max. Maximum Maximum Maximum Open- Short- Max. output Module Power at Power Power circuit circuit output current Type STC (Pmax, Voltage(Vmp Current(I Voltage(Vo Current(Is voltage (Optimized mp, A) c,V) c,A) (Optimize ) [A]: d) [V]: 31.1 8.37 37.9...