Summary of Contents for Trox Technik ROOMAIR-B-ZAB+SEK
Page 1
Installation and Operating Manual GB/en Decentralised ventilation units ROOMAIR-B-ZAB+SEK Supply and extract air unit with secondary air admixture with control FSL-CONTROL III (optional) Read the instructions prior to performing any task!
7.2 Control of the ventilation unit ....28 7.3 X-TAIRMINAL .......... 28 Operation ............31 8.1 Control panel ........... 31 8.1.1 Overview of control panels ....31 8.1.2 Digital room operating unit settings ..33 8.1.3 Analogue control panel settings ... Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
Project-specific documents (if any) Product data sheet ENVIRONMENT! Environmental pollution hazard. Tips and recommendations Useful tips and recommendations as well as informa- tion for efficient and fault-free operation. Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
Product name TROX order number and line number Delivery date Brief description of fault or issue Please refer to your local TROX website for the latest contact information. Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
Switch off the supply voltage before you carry out – Operation outdoors maintenance or cleaning. – Use for enforced ventilation – Ensure that live parts do not come into contact – Operation without air filters with moisture. Moisture can cause a short circuit. Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
(by others) to protect the unit from being each type of work. tampered with by unauthorised individuals. – The unit must remain accessible for maintenance and cleaning. Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
Page 8
Protective gloves Protective gloves protect hands from friction, abrasions, punctures, deep cuts, and direct contact with hot sur- faces. Safety shoes Safety shoes protect the feet from crushing, falling parts and prevent slipping on a slippery floor. Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
Fig. 1: Type plate (example) Device type Year of manufacture Commission no. Serial number Supply voltage Max. power consumption Protection level Weight Max. water temperature 10 Max. operating pressure 11 Supply air filter class 12 Extract air filter class Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
Parts and function Ventilation unit overview Parts and function 4.1 Ventilation unit overview Fig. 2: ROOMAIR-B-ZAB+SEK ventilation unit ① Casing ⑪ Connection options for control system by others Heat recovery unit inspection access panel Levelling feet ② ⑫ Inspection access panel for extract air filter ISO Fixing brackets ③...
Page 11
Parts and function Ventilation unit overview Schematic illustration of the airflows Fig. 3: Ventilation diagram for ROOMAIR-B-ZAB+SEK Outdoor air temperature sensor (optional) Supply air temperature sensor (optional) Volume flow limiter Bypass damper with actuator (modulating) Non-return damper sensor (optional) Shut-off damper with actuator (outdoor air and...
The appliance is supplied fully assembled. It is packed on pallets. The packaging is suitable for transport to the intended destination. Accessories are packed and enclosed separately if nec- essary. Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
If storing the units for more than 3 months, refer to the information on functional integrity. Note! If there are storage instructions on the packaging, these instructions must be followed as well. 5.6 Handling packaging materials Properly dispose of packaging material. Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
The outer casing must prevent unauthorised indi- viduals from reaching into the unit and from being injured (e.g. by electric shock). Make sure that the air can circulate around the unit even with the outer casing. Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
Page 15
Cover all openings of the unit, e.g. with plastic, to prevent the ingress of dust. – Remove the filters and store them in a dry place, protected from dust; cover the filter openings. – Switch off the power supply to the unit. Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
Flexible hoses FSL‑CON- (accessory) TROL III control Fig. 5: Tightening the connection system Tighten threaded connections, including valves Flexible hoses Pipe socket Hose (by others) and lockshields, with a spanner. (accessory) DN10 or DN13 Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
The connection data can be found on the rating plate or in the wiring diagrams. Protect any connecting cables from physical damage. Feed cables through the cable glands on the ventila- tion unit. Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
Seal the end of the conduit in the junction box as other- Attention: For A- and B+, always use a twisted wire wise a draught could occur in the conduit and affect the pair measurement results. Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
Page 19
Control panel without selector switch and without setpoint value adjuster, for flush mounting, suitable for Gira E2 switch range, type WRF06 TD NTC 20k, TROX order no. A00000081503 LiYCY 5 x 0.5 mm² shielded (provided by the client) Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
Fig. 15: FSL CONTROL III Communication with 2 devices Fig. 16: FSL CONTROL III Communication with 3 devices The master device must be installed on one of the two ends of the network (as the first or last device). Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
Page 22
Count up the terminal position from the grey end plate (direction of arrow) Recommended network cable (by others): e.g., Uni- tronic BUS LD 2 x 2 x 0.22 mm² or equivalent, Attention: For A- and B+, always use a twisted wire pair Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
Page 23
MCE/BACS to slave device with Modbus RTU/ BACnet IP Fig. 20: Connection of MCE / BACS to slave device with Modbus TCP Network cable at least Cat. 5e with connector RJ45 (by others) Interface X7 in terminal box Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
Page 24
2) The push button on the control panel can either be used to switch between Occupied / Unoccupied or activate the overtime function or Occupied/Unoccupied/Occupied + L. The configuration is carried out using the web browser and can be performed by personnel from TROX GmbH or TROX HGI Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
Page 25
Control zones can be networked using one of four existing network protocols (Modbus RTU, Modbus TCP, BACnet MS/TP or BACnet IP). This requires a bus interface card to be connected to the FSL CONTROL III master controller in the factory. Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
Page 26
When integrated into an on-site management and control equipment / building automation and control system, the master controller acts as a slave in the bus network, but serves as a master within the FSL CONTROL III network! Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
Page 27
Installation Making electrical connections > Communication FSL-CONTROL III Fig. 23: FSL CONTROL III Network building, Modbus TCP; BACnet IP Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
The dif- ferent menu levels are selected by pressing the respec- Operating mode tive objects displayed. Operating mode Source of operating mode Consolidated alarm Category A Consolidated alarm Category B Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
Page 29
If the slave device is connected to the master, the supply air temperature and the valve positions are displayed. Fig. 27: Room1 Display of operating status Display of alarms Category A Display of alarms Category B Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
Page 30
The page ‘Web visualisation’ can be accessed via the main menu. All device parameters can be accessed here. Fig. 29: Web visualisation room selection page Select the relevant room here and the corresponding device page will appear. Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
Fig. 32: Control panel with selector switch, for surface A00000079778 mounting, type: WRF04 PSTD NTC20k 5k FS5 gn 5V ② Push button SA, part number: A00000082515 ③ LED ① Selector switch ④ Setpoint value adjuster ② Push button ③ LED ④ Setpoint value adjuster Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
Page 32
Berker Q.3 switch range, type: able for Gira E2 switch range, type WRF06-TD-NTC20k WRF07 PTD NTC20k BType6 5k gn, part number: SA, part no. A00000081503 A00000081579 ② Push button ② Push button ③ LED ③ LED ④ Setpoint value adjuster Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
Display of the indoor air quality in various gradations (CO - traffic light). green = very good air quality orange = sufficient air quality red = poor air quality The display can be configured via the settings. Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
Page 34
The Messages menu displays all existing A and B alarms in plain text. A maximum of 5 different alarm messages can be displayed at the same time. Time (8) 19:09 The top line of the display shows the time. The display can be configured via the settings. Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
Page 35
Display of the activated fume cupboard switching (forced fan control). The stage corresponds to the fan stage of the supply air (configurable). Activation takes place via DI or via BACS/MCE. When the fume cupboard switching is active, operation via the control panel is not possible. Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
Page 36
‘Standby’ will only be displayed here. Activation by means of Real Time Clock or by selector switch ‘Standby’ is selected if the room is not occupied (stage 0). and the ventilation units are not used to maintain the temperature, e.g. at night. Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
2) The push button on the control panel can either be used to switch between Occupied / Unoccupied or activate the overtime function or Occupied/Unoccupied/Occupied + L. The configuration is carried out using the web browser and can be performed by personnel from TROX GmbH or TROX HGI Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
Use only common household cleaners, do not The ventilation unit has been protected by an use any caustic, scouring or otherwise aggressive outer casing (by others). Access to the outer cleaning agents. casing has to be provided for any work. Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
Page 39
If the filter operating hours counter in FSL‑CON- TROL III has been used, reset it after a filter change Ä Installation and configuration manual FSL‑CONTROL III. ð Filter checking or filter change is complete. Dispose of used filters with residual waste. Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
The ventilation unit has been protected by an outer casing (by others). Access to the casing has to be provided for cleaning. Disconnect the protective conductor ( Fig. 40 /1) from the heat exchanger ( Fig. 40 /2). Loosen the holder of the supply air temperature sensor ( Fig. 40 /3). Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
– Only skilled qualified electricians are allowed to work on the electrical system. Switch off the supply voltage and secure it against being switched on accidentally before working on the unit. Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
Page 42
Place the heat recovery unit onto the rails and push it back into the opening. Fix the inspection access panel. NOTICE! Be sure to insert the protective earth conductor when you fix the cover plate. Switch on the power supply. Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
Handle all open, sharp-edged components with care. – Disassemble components professionally. Be aware that some components are very heavy. Use lifting gear if necessary. – Secure components to prevent them from falling or toppling. – When in doubt, contact the manufacturer. Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
Micro fuse 2 A / 50 V A00000075499 Micro fuse 4 A / 50 V A00000075500 Micro fuse 3.15 A / 250 V A00000075494 SKM module for controlling the outdoor air dampers M536EC0 Lockshield M431AQ4 Thermoelectric valve actuator NO A00000036448 Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
Page 46
2-pipe or 4-pipe heat exchanger See no. on the heat exchanger – Replacement part bag of quick release fasteners (10x) A0000072484 Price list for replacement parts A price list for spare parts is available on our website, www.trox.de. Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
Checking the control panel Check switching function, setpoint ☐ ☐ (random check) shift Checking control units (random Check circuits, control signals; ☐ ☐ check) adjust them if necessary 1) if condensation has formed Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
Page 50
Commissioning report/Maintenance report Comment: Next maintenance scheduled for: Signature: (Maintenance per- sonnel) Company: (Stamp) Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
Ergonomics of the thermal environment - Methods for the assessment of human responses to contact with surfaces - Part 1: Hot surfaces (ISO 13732-1:2008) Neukirchen-Vluyn, 1 January 2024 Dipl.-Ing. Jan Heymann Head of Quality Management 01/2024 – DE/en Fig. 42: ROOMAIR-B-ZAB+SEK-EU Declaration of Conformity Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
Page 52
This is to confirm that the products meet the hygiene requirements stipulated in the specified standards and guidelines. Neukirchen-Vluyn, 01.05.2024 Dipl.-Ing. Jan Heymann Dipl.-Ing. Dirk Scherder Manager quality management VDI-certified engineer for room air quality HC – 05/2024 – DE/en Fig. 43: RA-B-ZAB+SEK-Declaration of hygiene conformity Decentralised ventilation units ROOMAIR-B-ZAB+SEK...
Only valid when using a TROX control system for decentralised ventilation units. Note 2: ErP - 03/2024 - DE/en 1 / 1 Fig. 44: RA-B-ZAB+SEK product information Decentralised ventilation units ROOMAIR-B-ZAB+SEK...