Download Print this page

Haes MZAOV-1001A Installation, Commissioning & Operating Manual

Multizone automatically opening vent control panel

Advertisement

Quick Links

MZAOV CONTROL
PANEL INSTALLATION,
COMMISSIONING &
OPERATING MANUAL
This
manual
covers
the
installation,
programming
and
commissioning of the Multizone Automatically Opening Vent Control
Panel (MZAOV)

Advertisement

loading
Need help?

Need help?

Do you have a question about the MZAOV-1001A and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Haes MZAOV-1001A

  • Page 1 MZAOV CONTROL PANEL INSTALLATION, COMMISSIONING & OPERATING MANUAL This manual covers installation, programming commissioning of the Multizone Automatically Opening Vent Control Panel (MZAOV)
  • Page 2: Introduction

    Multizone AOV User Manual INTRODUCTION INTRODUCTION 1438 Haes Technologies Ltd, Unit 3, Horton Industrial Park, West Drayton, Uxbridge, UB7 8JD Model Number CPR Number MZAOV-1001A/1001/1002/1003 1438-CPR-0739 European Standard BS EN 12101-10:2005 Smoke and heat control systems – Part 10: Power supplies Haes Technologies Ltd declare that the products identified above conform to the essential requirements specified in the Construction Products Regulation CPR305/2011/EU.
  • Page 3: Safety

    Multizone AOV User Manual SAFETY SAFETY IMPORTANT NOTICE PLEASE READ THIS MANUAL CAREFULLY BEFORE HANDLING THE EQUIPMENT AND OBSERVE ALL ADVICE GIVEN WITHIN IT. THIS PARTICULARLY APPLIES TO THE PRECAUTIONS NECESSARY TO AVOID ELECTRO-STATIC DISCHARGE Important Safety Notes The panel is safe to operate provided it has been installed in compliance with the manufacturer’s instructions and used in accordance with this manual.
  • Page 4: Cautions

    Multizone AOV User Manual SAFETY Cautions Equipment Guarantee This product has been manufactured in conformance with the requirements of all applicable EU Council Directives and is not guaranteed unless the complete system is installed and commissioned in accordance with the laid down national standards by an approved and competent person or organisation.
  • Page 5: Table Of Contents

    TABLE OF CONTENTS .......................... 5 PRODUCT OVERVIEW .......................... 9 General Description of the Equipment ................9 Multi-AOV Cabinet ......................11 MZAOV-1001A/-1001/-1002 ..................11 MZAOV-1003 ......................11 Circuit Boards ....................... 12 PSU AOV Card – TPCA027 ..................12 MULTI AOV Card (2-Way) – TPCA028 ..............13 PIR/BMS (Plug-in) Card (2-Way) –...
  • Page 6 Multizone AOV User Manual TABLE OF CONTENTS Environment ......................... 32 Mounting the Cabinet....................32 Mains Connections ....................... 33 Connecting the Batteries ....................33 Battery Charging Voltage Checks ................. 34 Battery Charging Voltage Calibration ................34 Sounders/Output Circuits ....................35 Relay Outputs ....................... 35 OPERATING INSTRUCTIONS ......................
  • Page 7 Multizone AOV User Manual TABLE OF CONTENTS User Menu: TEST ......................51 TEST MODE: ON/OFF ....................51 TEST MODE: SETTINGS ..................52 User Menu: TIME & DATE .................... 52 User TIME & DATE Menu: TIME & DATE ..............52 User TIME & DATE Menu: Set DST ................53 User Menu: LAMP TEST ....................
  • Page 8 Multizone AOV User Manual TABLE OF CONTENTS Report Menu: COUNTER ..................... 83 Report Menu: Versions ....................84 Report Menu ......................... 86 ENG Menu ........................88 ENG Menu: OUTPUTS ....................88 ENG Menu ........................89 Summary of Menu Structure .................... 90 SERVICE &...
  • Page 9: Product Overview

    The panels are available with three output options, 3 Amp, 5 Amp and 10 Amp for controlling medium to large loads. The 3A (MZAOV-1001A/1001) and 5A panels (MZAOV-1002) can have between 1 and 4 Conventional and/or Twin Wire (sav-wire) detector zones and will control between 1 and 4 vents.
  • Page 10 Multizone AOV User Manual PRODUCT OVERVIEW The panel is fully configurable and uses an easy to navigate menu system, which utilizes a large 240 x 64-pixel graphical display and 5-button Up/Down/Left/Right/Enter (✓) curser control keys for menu navigation. The panel internal sounders and external alarm sounders are controlled by a 5-button keypad.
  • Page 11: Multi-Aov Cabinet

    Multizone AOV User Manual PRODUCT OVERVIEW Multi-AOV Cabinet MZAOV-1001A/-1001/-1002 MZAOV-1003 Approved Document Ref: UI-MZAOV-01 Issue 2.2...
  • Page 12: Circuit Boards

    Multizone AOV User Manual PRODUCT OVERVIEW Circuit Boards PSU AOV Card – TPCA027 Approved Document Ref: UI-MZAOV-01 Issue 2.2...
  • Page 13: Multi Aov Card (2-Way) - Tpca028

    Multizone AOV User Manual PRODUCT OVERVIEW MULTI AOV Card (2-Way) – TPCA028 Approved Document Ref: UI-MZAOV-01 Issue 2.2...
  • Page 14: Pir/Bms (Plug-In) Card (2-Way) - Tpca029 (Optional)

    Multizone AOV User Manual PRODUCT OVERVIEW PIR/BMS (Plug-in) Card (2-Way) – TPCA029 (Optional) Approved Document Ref: UI-MZAOV-01 Issue 2.2...
  • Page 15: Circuit Description/Function

    Multizone AOV User Manual PRODUCT OVERVIEW Circuit Description/Function PSU AOV Card – TPCA027 POWER IN A/POWER IN B (+ -) Two monitored 28VDC inputs from power supply module. Diode protected for reversal and independent short circuit. Maximum input current, 10 Amps. Input voltage 22 to 32VDC. Configurable for either one, or both, of the inputs to be used.
  • Page 16 Multizone AOV User Manual PRODUCT OVERVIEW Note: If a local vent control switch is configured as a local fireman switch, controlling one or more local vents, control of those vents by an external 3-way fireman’s switch is overridden. Note: If neither switch is closed, vents follow panel automatic control (AUTO) The diagram below shows how to wire a key or rocker switch to the switch inputs.
  • Page 17: Dual Zone Card (2-Way) - Tpca028

    Multizone AOV User Manual PRODUCT OVERVIEW Dual Zone Card (2-Way) – TPCA028 Between one and two (3A/5A box) or one and four (10A box) Dual Zone cards may be fitted, allowing for up to eight vent zones (two per card). ZONE 1/ZONE 2 (+ -) Conventional / Twin Wire fire alarm zone circuit.
  • Page 18 Multizone AOV User Manual PRODUCT OVERVIEW ACT 1/ACT 2 (+ -) Dual polarity reversal vent drive actuator outputs - 28VDC, max 8A, protected by a current trip circuit. Not normally powered. Operated during an alarm state or by the inputs from the main fireman switch or the local vent control switches, for a configurable time-period of 10 to 300 seconds.
  • Page 19 Multizone AOV User Manual PRODUCT OVERVIEW SWITCH 1/SWITCH 2 (OP C CL) Local vent control switch inputs, for manual operation of vents by local vent control switch(es). • OP - Open vents • C - Common reference for switching inputs •...
  • Page 20: Pir/Bms Plug-In Card (2-Way) - Tpca029 (Optional)

    Multizone AOV User Manual PRODUCT OVERVIEW PIR/BMS Plug-in Card (2-Way) – TPCA029 (Optional) One PIR card can be fitted to each of the dual zone cards mounted in the panel. This means up to eight PIRs can be fitted in the system. PIR 1/PIR 2 (+ -) The PIR input is available to monitor a typical security type PIR with N/C alarm and tamper contacts.
  • Page 21 Multizone AOV User Manual PRODUCT OVERVIEW RAIN (+ -) Signal input from wind/rain sensors. Typically, a wind/rain sensor will have a closing contact alarm signal and may require a 24V supply. The input requires a 2K7Ω resistance to trigger, with a 6K8Ω 5%0.25W EOL resistor. Monitoring current limit is 14mA, unfused. Up to 4 wind/rain sensors can be installed in the system;...
  • Page 22: Technical Specification

    Multizone AOV User Manual PRODUCT OVERVIEW Technical Specification General Specification Enclosure Steel IP30. Epoxy powder coated Interpon Radon, silver grey Temperature range: -5°C to +40°C Maximum Relative Humidity: 1 – 4 (3A/5A) or 1 – 8 (10A) Number of conventional/twin wire detection circuits Conventional/twin wire detector Apollo: S65, Orbis.
  • Page 23: Power Supply Specification - Psm3 - 24 (Mzaov-1001 (3 Amp))

    Multizone AOV User Manual PRODUCT OVERVIEW Power Supply Specification – PSM3 - 24 (MZAOV-1001 (3 Amp)) Mains supply 230VAC +10% / -15% 50Hz max current 1.2 Amp Mains supply fuse 3.15 Amp (F3.15A 250V) Not accessible for servicing. Internal to switched mode power unit Power supply rating 3 Amps total including battery Maximum load shared = 3 Amp...
  • Page 24: Power Supply Specification - Psm5 - 27 (Mzaov-1002 (5 Amp))

    Multizone AOV User Manual PRODUCT OVERVIEW Power Supply Specification – PSM5 - 27 (MZAOV-1002 (5 Amp)) Mains supply 230VAC +10% / -15% 50Hz max current 1.2 Amp Mains supply fuse 3.15 Amp (F3.15A 250V) Not accessible for servicing. Internal to switched mode power unit Power supply rating 5 Amps total including battery Maximum load shared = 5 Amp...
  • Page 25: Power Supply Specification - Psm10-27 (Mzaov-1003 (10 Amp))

    Multizone AOV User Manual PRODUCT OVERVIEW Power Supply Specification – PSM10-27 (MZAOV-1003 (10 Amp)) Mains supply 230VAC +10% / -15% 50Hz max current 1.5 Amp Mains supply fuse 6.3 Amp (F6.3A 250V) Not accessible for servicing. Internal to switched mode power unit Power supply rating 10 Amps total including battery Maximum load shared = 10 Amp...
  • Page 26: Electrical Specification - Inputs & Outputs - Tpca027 Psu Aov Card

    Multizone AOV User Manual PRODUCT OVERVIEW Electrical Specification - Inputs & Outputs - TPCA027 PSU AOV Card POWER IN A/POWER IN 28VDC supply input. Diode protected Max input current; 5 amps (5A card) B - + for reversal and independent short or 10 amps (10A card).
  • Page 27: Electrical Specification - Inputs & Outputs - Tpca028 Multi Aov Card

    Multizone AOV User Manual PRODUCT OVERVIEW Electrical Specification - Inputs & Outputs - TPCA028 MULTI AOV Card ZONE 1 / ZONE 2 + - Fire alarm zone circuit. Monitoring current limit is 50mA, fused Conventionally wired detection circuit at 500mA. Typical max load 22 or Twin wire combined detection / devices, at 18mA each, in each zone sounder circuit, monitored via a...
  • Page 28: Detector Circuit Conventional System Schematic

    Multizone AOV User Manual PRODUCT OVERVIEW Detector Circuit Conventional System Schematic Approved Document Ref: UI-MZAOV-01 Issue 2.2...
  • Page 29: Detector Circuit Twin Wire System Schematic

    Multizone AOV User Manual PRODUCT OVERVIEW Detector Circuit Twin Wire System Schematic Note: Dependency modes are not compatible with Twin Wire mode. Approved Document Ref: UI-MZAOV-01 Issue 2.2...
  • Page 30: Twin Wire Mode

    Multizone AOV User Manual PRODUCT OVERVIEW Twin Wire Mode Note: Dependency modes are not compatible with Twin Wire mode. Twin Wire, often referred to as sav wire, enables sounders and beacons to be connected to the same circuit as the detectors and call points. In Twin Wire configuration, the detector circuit reverses polarity, in alarm condition, to power the sounders and beacons.
  • Page 31: Installation

    Further copies of this User Instruction Manual are available from the website www.https://haes-tech.com. This equipment is designed to be operated from 230V AC 50/60 Hz mains supplies and is of Class I construction.
  • Page 32: Installing The System

    Multizone AOV User Manual INSTALLATION Installing the System General Take care to avoid mounting the cabinet near high voltage cables, or areas likely to induce electrical interference. Earth links should be maintained on all system cables and grounded in the control panel. Cabling for the detection and sounder circuits is classed as extra low voltage and must be segregated away from mains voltage.
  • Page 33: Mains Connections

    Multizone AOV User Manual INSTALLATION Mains Connections Note: All connections must be carried out in accordance with local requirements and regulations. Do not connect the mains supply to the panel until you are fully conversant with the layout and features of the equipment. A rating plate is attached to the power supply module, describing the nature of the supply permitted.
  • Page 34: Battery Charging Voltage Checks

    Multizone AOV User Manual INSTALLATION Battery Charging Voltage Checks ° The battery charging voltage is factory calibrated to 27.3VDC +/- 0.2V at 20 C. This should not normally require adjustment. Where battery problems are experienced, the following information should be considered: a) If a battery is disconnected from the charger, no voltage will appear on the output leads or terminals, due to intelligent battery controls.
  • Page 35: Sounders/Output Circuits

    Multizone AOV User Manual INSTALLATION BATTERY VOLTS: nn.nn CHARGE: nn.nn Current: n.nn DAC OUTPUT: nnn.nn VREF INT: nnnn CALIBRATION: n.nnnnnn • Place Multimeter probes onto battery input terminals and observe the Battery Volts reading • Using Up/Down arrow keys; adjust the calibration until the BATTERY VOLTS figure, shown on the panel LCD screen, matches the Battery Voltage as measured on the Multimeter •...
  • Page 36 Multizone AOV User Manual INSTALLATION The relays can be programmed to turn OFF or ON in Continuously Mode or in Pulsing Mode (1s ON and 1s OFF) and can be set to operate as General Alarm, Evacuation Alarm, Fails Safe, Fault and Can be Silenced. Approved Document Ref: UI-MZAOV-01 Issue 2.2...
  • Page 37: Operating Instructions

    Multizone AOV User Manual OPERATING INSTRUCTIONS OPERATING INSTRUCTIONS Panel Control and Indicators Control Panel The control panel contains: • LCD display screen • 5-button control keypad • Up/down/left/right arrow keys and enter (✓) key curser control keypad • Panel status LED indicators •...
  • Page 38: Keypads

    Multizone AOV User Manual OPERATING INSTRUCTIONS Keypads Use to resound the alarms after they have been silenced. Can also be used to invoke full evacuation. Resound Alarms Use to silence the sounders during an alarm condition. Silence Alarms Resets the panel back to standby mode. Reset System Mutes the panels internal fire and fault buzzer.
  • Page 39: Status Led Indicators

    Multizone AOV User Manual OPERATING INSTRUCTIONS Status LED Indicators LED Name LED - on steady LED - pulsing Indicates panel is in alarm Indicates panel is in the General Alarm unsilenced alarm condition. condition that has been silenced. Indicates rain/wind sensor Indicates a fault in the Rain Status has been disabled.
  • Page 40: Software Downloads

    The Haes Configuration panel software is available to be downloaded from the Haes website: www.https://haes-tech.com System Requirements The Haes Configuration Panel software is designed for use with Windows 7 and Windows 10 Operating System. It is not intended for use with Apple macOS, Android or Linux OS. The following are required: •...
  • Page 41: Authorized User Controls

    Multizone AOV User Manual OPERATING INSTRUCTIONS Authorized User Controls The Authorized User (Access level 2) controls can be accessed by: • Turning the Activate Controls key clockwise into the On position. The padlock symbol will show unlocked and all the buttons on the keypad will be operational. To deactivate the controls, turn the key back to the Off position.
  • Page 42: Engineer Controls

    Multizone AOV User Manual OPERATING INSTRUCTIONS • Engineer Controls The Engineer (Access level 3) controls can be accessed by: • From the Authorised User (Access level 2) MAIN MENU, use Left/Right arrow keys to move cursor to CONFIG menu icon •...
  • Page 43: Panel Alarm Conditions

    Multizone AOV User Manual OPERATING INSTRUCTIONS Panel Alarm Conditions Fire Alarm Condition The display shows location/origin of the fire alarm and the total number of vent zones in a fire alarm condition. If two or more vent zones enter the fire alarm condition, the display also shows the location of the last zone to enter a fire alarm condition.
  • Page 44 Multizone AOV User Manual OPERATING INSTRUCTIONS • Power Supply Board o System Fault LED pulsing o General Fault LED pulsing o Power Supply Fault LED pulsing o Fault relay activated o Mains or battery power will still operate the panel. Batteries will not be charging o Indications will remain until the fault is rectified and the panel is reset o Remote status units will cease to function.
  • Page 45: Configuring The System

    Multizone AOV User Manual CONFIGURING THE SYSTEM CONFIGURING THE SYSTEM When the system is installed and is ready to be commissioned, configure as follows: • Use the CONFIG PANEL menu LEARN option, to enable the panel to automatically learn what internal cards, external devices (detectors, sounders, etc.), and Peripheral BUS (P-BUS) Remote Control Call Points are connected in the system.
  • Page 46: Type C

    Multizone AOV User Manual CONFIGURING THE SYSTEM If no alarm is detected, the panel stays in an alert condition for 5 - 30 minutes (programmable, see CONFIG PANEL: OPTIONS, 6: INHIBIT TIME). Any new alarm from the same or a different zone within this time activates a full fire condition.
  • Page 47 Multizone AOV User Manual CONFIGURING THE SYSTEM To access the menu structure: • Turn Activate Controls key switch clockwise to On • use the keypad to enter Authorised User (Access level 2) code 1111: • Press ✓ key to select Access level 2. The digital display will show the following message: Enter Level 2 Access Code •...
  • Page 48: User Menu

    Multizone AOV User Manual CONFIGURING THE SYSTEM User Menu Accessible from the Main Menu (Access level 2); the User Menu, and its subsequent sub- menus, are used to set-up the panel ready for configuration. The sub-menus available are: • DISABLE o DISABLE Menu ▪...
  • Page 49: User Menu: Disable

    Multizone AOV User Manual CONFIGURING THE SYSTEM User Menu: DISABLE To enable/disable inputs, outputs, devices, zones and circuits, access the DISABLE sub-menu and its sub-menus: • On the Main Menu, use Left/Right arrow keys to move cursor box to User menu icon •...
  • Page 50: Disable Menu: General

    Multizone AOV User Manual CONFIGURING THE SYSTEM DISABLE Menu: GENERAL To enable or disable panel sounders, relays, outputs and switch inputs on the PSU card: • From the DISABLE sub-menu, use the Up/Down arrow keys to highlight the GENERAL option icon, and then press ✓ key to access it. •...
  • Page 51: User Menu: Test

    Multizone AOV User Manual CONFIGURING THE SYSTEM Note – If any of these options are set to DISABLED, the amber Disablement LED will be illuminated as steady. If the SOUNDERS option is set to DISABLED, the amber Sounder Status LED will also be illuminated. •...
  • Page 52: Test Mode: Settings

    Multizone AOV User Manual CONFIGURING THE SYSTEM TEST MODE: SETTINGS With this menu, the Zone(s) to be tested can be set. To select the TEST MODE settings: • On the TEST MODE sub-menu, highlight the SETTINGS sub-menu and then press ✓ key to access it.
  • Page 53: User Time & Date Menu: Set Dst

    Multizone AOV User Manual CONFIGURING THE SYSTEM • On the User Time & Date sub-menu, highlight the Time & Date option and press ✓ key to access it. • Adjust the time and date as required, using the Up/Down and Left/Right arrow keys. •...
  • Page 54: User Menu: Lamp Test

    Multizone AOV User Manual CONFIGURING THE SYSTEM User Menu: LAMP TEST To operate the Lamp Test menu, to test the panel LCD display and warning LEDs: • On the Main Menu, use Left/Right arrow keys to move cursor box to User menu •...
  • Page 55: User Menu: Contrast

    Multizone AOV User Manual CONFIGURING THE SYSTEM User Menu: CONTRAST To set the LCD screen contrast and backlight, operate the Contrast menu: • On the Main Menu, use Left/Right arrow keys to move cursor box to User menu • Press ✓ key to select the User menu. •...
  • Page 56: User Menu

    Multizone AOV User Manual CONFIGURING THE SYSTEM User Menu Approved Document Ref: UI-MZAOV-01 Issue 2.2...
  • Page 57 Multizone AOV User Manual CONFIGURING THE SYSTEM Approved Document Ref: UI-MZAOV-01 Issue 2.2...
  • Page 58 Multizone AOV User Manual CONFIGURING THE SYSTEM Approved Document Ref: UI-MZAOV-01 Issue 2.2...
  • Page 59: Config Menu

    Multizone AOV User Manual CONFIGURING THE SYSTEM CONFIG Menu Accessible from the Main Menu (Access level 2); the CONFIG Menu (Access level 3), and its subsequent sub-menus, are used to configure the panel and its attached devices. The sub- menus available are: •...
  • Page 60: Config Menu: Panel

    Multizone AOV User Manual CONFIGURING THE SYSTEM o When all 4 digits have been set to the code 3333 press ✓ key once again. The Access level 3 menu will become available for operation. Note: Access level 3 Menu will deactivate after 30 sec if not used. CONFIG Menu: PANEL To configure the Panel controls and outputs: CONFIG PANEL Menu: LEARN...
  • Page 61: Config Panel Menu: Options

    Multizone AOV User Manual CONFIGURING THE SYSTEM o P-BUS: The LEARN PANEL sub-menu will display a list containing all 32 of the possible RSUs that could be connected, using the P-BUS, and show if they are connected or not - indicated by PRESENT or NOT PRESENT: LEARN PANEL -P-BUS- 1: 1st RSU: PRESENT/NOT PRESENT...
  • Page 62: Config Panel Menu: Default

    Multizone AOV User Manual CONFIGURING THE SYSTEM • For options 5, 6 and 8; press enter ✓ key to enable changes, then use Up/Down arrow keys to toggle between the various time parameters, as required. Note: If SOUNDER ONE FARE and/or SOUNDER TWO FWRE (options 2 and 3) are set to YES, their status (NORMAL/ACTIVE) will be displayed on the LCD screen title display, and in place of the event counts (A nn F nn D nn T nn O nn) on any of the EVENT reports (ALARM, FAULT, DISABLE, TEST and OTHER).
  • Page 63: Config Panel Menu: Password

    Multizone AOV User Manual CONFIGURING THE SYSTEM • If YES value has been selected, then all current settings will be overwritten, and the system will return to original factory settings. Caution is recommended before choosing the YES value for the DEFAULT option! Choosing this option will remove ALL configuration that has been set and will return the panel to its factory default settings.
  • Page 64: Config Menu: Devices

    Multizone AOV User Manual CONFIGURING THE SYSTEM 7: 2nd MAINS INPUT: ENABLED, NOT USED • Use the Left/Right arrow keys to toggle between the circuit AREA (01 – 08, depending on the AOV Cards fitted), to select the required Area •...
  • Page 65 Multizone AOV User Manual CONFIGURING THE SYSTEM 1: ZONE ONE: OPEN VENT/CLOSE VENT/DISABLED 2: ZONE TWO: OPEN VENT/CLOSE VENT/DISABLED 8: ZONE EIGHT: OPEN VENT/CLOSE VENT/DISABLED 9: 1st RSU: DISABLED/ENABLED 40: 32nd RSU: DISABLED/ENABLED 4: INPUT CONTROL VENT 01 – 08 CONFIG CONTROL 1: INPUT ONE: OPEN VENT/CLOSE VENT/DISABLED 2: INPUT TWO: OPEN VENT/CLOSE VENT/DISABLED...
  • Page 66: Config Devices Menu: Zones

    Multizone AOV User Manual CONFIGURING THE SYSTEM • For options 3, 4 and 5; press enter ✓ key to access their CONFIG CONTROL sub- menus. • For option 1: OPENING TIME and option 2: CLOSING TIME; press ✓ key to access change time control.
  • Page 67: Config Devices Menu: Sounders

    Multizone AOV User Manual CONFIGURING THE SYSTEM • Use Up/Down arrow keys to move between options 1 – 8, as required • For each of the options 1 to 8, press enter ✓ key to cycle through parameters, as required •...
  • Page 68: Config Menu: Psu

    Multizone AOV User Manual CONFIGURING THE SYSTEM 4: FAIL SAFE: YES/NO 5: CAN BE SILENCED: YES/NO • Use Left/Right arrow keys to toggle between relays FIRE and FAULT • Use Up/Down arrow keys the move between options 1 – 5. •...
  • Page 69: Config Menu: P-Bus

    Multizone AOV User Manual CONFIGURING THE SYSTEM CONFIG Menu: P-BUS If RSU(s) have been added or removed from the P-BUS, since the last configuration learning routine, the RSUs on the P-BUS can be configured from the P-BUS menu: • From the CONFIG Menu, highlight P-BUS option and then press ✓ key in order to gain access to it.
  • Page 70: Config Menu

    Multizone AOV User Manual CONFIGURING THE SYSTEM CONFIG Menu Approved Document Ref: UI-MZAOV-01 Issue 2.2...
  • Page 71 Multizone AOV User Manual CONFIGURING THE SYSTEM Approved Document Ref: UI-MZAOV-01 Issue 2.2...
  • Page 72 Multizone AOV User Manual CONFIGURING THE SYSTEM 2.2 CIRCUIT (cont’d) 2.2 CONFIG CIRCUIT CONFIG CIRCUIT <AREA 01-08> 1: ZONE CIRCUIT: NORMAL, TWIN WIRE, NOT USED 2: INPUT CIRCUIT: ENABLED, NOT USED 3: VENT CIRCUIT: MONITORING, S/C NOT MON, NOT USED 4: SWITCH CIRCUIT: NORMAL, FIREMAN, NOT USED 5: PIR CIRCUIT: ENABLED, NOT USED 6: RAIN CIRCUIT: ENABLED, NOT USED...
  • Page 73 Multizone AOV User Manual CONFIGURING THE SYSTEM Approved Document Ref: UI-MZAOV-01 Issue 2.2...
  • Page 74 Multizone AOV User Manual CONFIGURING THE SYSTEM Approved Document Ref: UI-MZAOV-01 Issue 2.2...
  • Page 75 Multizone AOV User Manual CONFIGURING THE SYSTEM Approved Document Ref: UI-MZAOV-01 Issue 2.2...
  • Page 76 Multizone AOV User Manual CONFIGURING THE SYSTEM Approved Document Ref: UI-MZAOV-01 Issue 2.2...
  • Page 77: Report Menu

    Multizone AOV User Manual CONFIGURING THE SYSTEM Report Menu From the Report menu, on the Main Menu, the following sub-menus are available: • REPORT o EVENTS ▪ ALARM ▪ FAULT ▪ DISABLE ▪ TEST ▪ OTHER o STATUS ▪ ▪ PSU Card ▪...
  • Page 78: Report Menu: Events

    Multizone AOV User Manual CONFIGURING THE SYSTEM Report Menu: EVENTS From the Report Menu EVENTS sub-menu, report screens on the number and type of events (Alarm, Fault, Disablements, etc.) can be displayed: Report EVENTS Menu: ALARM To get ALARM events information: •...
  • Page 79: Report Events Menu: Disable

    Multizone AOV User Manual CONFIGURING THE SYSTEM • Fault info will be displayed in the following manner: FAULT A 00 F nn D 00 T 00 O 00 List of detected faults FAULT FWRE : NORMAL/ACTIVE and/or FARE : NORMAL/ACTIVE List of detected faults (Displayed if Sounder One FARE and/or Sounder Two FWRE are selected to YES, under CONFIG >...
  • Page 80: Report Events Menu: Test

    Multizone AOV User Manual CONFIGURING THE SYSTEM D means Disablement T means Test O means Other • key or ✓ key to return to the Main Menu display. Next, press return Report EVENTS Menu: TEST To open a report screen for TEST events information: •...
  • Page 81: Report Menu: Status

    Multizone AOV User Manual CONFIGURING THE SYSTEM • OTHER info will be displayed in the following manner: OTHER A 00 F 00 D 00 T 00 O nn List of detected events OTHER FWRE NORMAL/ACTIVE and/or FARE NORMAL/ACTIVE List of detected events (Displayed if Sounder One FARE and/or Sounder Two FWRE are selected to YES, under CONFIG >...
  • Page 82: Report Status Menu: Psu Card

    Multizone AOV User Manual CONFIGURING THE SYSTEM • Next, press return key to return to Report STATUS menu. Report STATUS Menu: PSU Card To get status information for the panel’s PSU card, access the PSU Card Status menu: • On the Main Menu, use Left/Right arrow keys to move cursor box to Report menu. •...
  • Page 83: Report Menu: History

    Multizone AOV User Manual CONFIGURING THE SYSTEM Report Menu: HISTORY To access EVENT HISTORY information: • On the Main Menu, use Left/Right arrow keys to move cursor box to Report menu icon. • Press ✓ key to select the Report menu. •...
  • Page 84: Report Menu: Versions

    Multizone AOV User Manual CONFIGURING THE SYSTEM • The ALARM COUNT sub-menu will open, and the following information will be available: ALARM COUNT: nnnn – number (n) of alarm events that have occurred LAST ALARM AT: dd-MMM-yy hh:mm:ss (date and time when the last event happened) HOLD DOWN SELECT TO RESET: press and hold down ✓...
  • Page 85 Multizone AOV User Manual CONFIGURING THE SYSTEM dd = day MMM = Month yy = year Note: The number of AREA versions displayed depends on the AOV Cards fitted. • key or ✓ key to return to the Report Menu. Next, press return Approved Document Ref: UI-MZAOV-01 Issue 2.2...
  • Page 86: Report Menu

    Multizone AOV User Manual CONFIGURING THE SYSTEM Report Menu Approved Document Ref: UI-MZAOV-01 Issue 2.2...
  • Page 87 Multizone AOV User Manual CONFIGURING THE SYSTEM Approved Document Ref: UI-MZAOV-01 Issue 2.2...
  • Page 88: Eng Menu

    Multizone AOV User Manual CONFIGURING THE SYSTEM ENG Menu From the ENG menu on the Main Menu, the following sub-menus are available: • OUTPUTS ENG Menu: OUTPUTS To set the test output for the external devices connected to the system, access the ENG menu OUTPUTS sub-menu: •...
  • Page 89: Eng Menu

    Multizone AOV User Manual CONFIGURING THE SYSTEM ENG Menu Approved Document Ref: UI-MZAOV-01 Issue 2.2...
  • Page 90: Summary Of Menu Structure

    Multizone AOV User Manual CONFIGURING THE SYSTEM Summary of Menu Structure Approved Document Ref: UI-MZAOV-01 Issue 2.2...
  • Page 91 Multizone AOV User Manual CONFIGURING THE SYSTEM Approved Document Ref: UI-MZAOV-01 Issue 2.2...
  • Page 92: Service & Maintenance

    Multizone AOV User Manual SERVICE & MAINTENANCE SERVICE & MAINTENANCE The product must be maintained for operation, including periodic checks, in accordance with applicable codes of practice, national standard regulations and local instructions for fire systems appropriate to the country and location of the installation. It is the responsibility of the system user to ensure it is regularly serviced and maintained in good working order.
  • Page 93: Schedule Of Testing

    Multizone AOV User Manual SCHEDULE OF TESTING SCHEDULE OF TESTING This section to be used to record ALL weekly tests of the fire alarm system. Date & Time Device Tested & Initials of Comments (if any) of Test Location Tester Approved Document Ref: UI-MZAOV-01 Issue 2.2...
  • Page 94 [Type here]...

This manual is also suitable for:

Mzaov-1001Mzaov-1002Mzaov-1003