Page 1
Liebert® APM2 User Manual 10 kVA to 60 kVA, 208 V, 4-Wire, 60 Hz 20 kVA to 120 kVA, 480 V, 4-Wire/3-Wire, 60 Hz...
Page 2
The products covered by this instruction manual are manufactured and/or sold by Vertiv. This document is the property of Vertiv and contains confidential and proprietary information owned by Vertiv. Any copying, use, or disclosure of it without the written permission of Vertiv is strictly prohibited.
1 Important Safety Instructions Save These Instructions This manual contains important instructions that must be followed during installation of the Vertiv™ Liebert® APM2. Read this manual thoroughly, pay attention to the safety instructions in mechanical and electrical installation chapters. Retain this manual for use by installing personnel.
Page 11
If any difficulties are encountered, contact Vertiv. This device complies with part 15 of the FCC Rules. Operation is subject to the following conditions: This device may not cause harmful interference, and this device must accept any interference received, including interference that may cause undesired operation.
208 V, 400 V, and 480 V capability. The Liebert® APM2 operates with 60 Hz. When configured for scalability, the capacity of UPS can be set according to Table 2.1 below. Contact Vertiv Services about adding capacity.
AC voltage by the inverter to supply uninterrupted AC power to the loads. At the same time, the charger will use the DC voltage from the rectifier to charge the battery. For inverter overload protection, the Vertiv™ Liebert®...
2.4.8 Power Conditioner Mode In this mode the Vertiv™ Liebert® APM2 only performs to condition and filter the incoming AC power for a clean regulated AC output. For this mode, a DC battery source is not installed and the Liebert® APM2 is incapable of operating on Battery Mode.
Maximum battery discharge time: When the battery has small current discharge for a long time, the battery is over discharged and even has unrecoverable damage, thus setting a battery discharge time to protect the battery is essential. The limit of time setting must be configured by service engineer through the Vertiv setting software.
WARNING! The user must select an appropriate MCCB to protect against short circuit and overload for the battery. It is recommended to use the Vertiv battery to provide a better solution. The following battery protection functions are set by the service engineer through the Vertiv setting software. 2.6.1 Battery Low Pre-warning The battery low pre-warning occurs before the EOD.
NOTE: Professional installation required. Do not disassemble the package without permission of authorization from Vertiv. The UPS should be installed by an authorized engineer in accordance with the information provided in this chapter. NOTE: The UPS can be connected to IT, TN, and TT AC distribution systems (IEC60364-3), and must be a 3-phase, 5-wire (A, B, C, N, PE) system.
Before unpacking the UPS and battery, inspect for any visual damage or signs of mishandling. Under the guidance of authorized Vertiv personnel, follow the below steps to unpack the UPS and battery packages. Remove the packaging as shown in Figure 3.1 below.
2. Remove the fixing bolts, shown in Figure 3.2 below. 3. Vertiv™ Liebert® APM2 may be rolled on its casters for short distances only. For longer distances, move the UPS with a forklift or similar equipment to ease the relocation and to reduce vibration.
For the top fan airflow UPS, there are no perforated panels on the sides or back of the UPS. Leave a minimum of 24 in. (670 mm) between the top of the UPS frame and the ceiling to permit adequate air circulation above the unit. Vertiv does not recommend using air conditioning or other systems that blow across the top of the unit.
Characteristics on page 114 for weight of the UPS. Vertiv™ Liebert® APM2 rolled on its casters for short distances only. For longer distances, move the UPS with a forklift or similar equipment to ease the relocation and to reduce vibration. 3.7.3 Clearance Provide at least minimum clearance, as recommended by the NEC to the Liebert®...
Page 29
UPS. Leave a minimum of 24 in. (670 mm) between the top of the UPS frame and the ceiling to permit adequate air circulation above the unit. Vertiv do not recommend using air conditioning or other systems that blow air onto the top of the unit Figure 3.3 Clearances for Airflow (Rear)
UPS. 3.9 Cabinets Installation The Vertiv™ Liebert® APM2 10 kVA to 60 kVA 208V or 20 kVA to 120 kVA 480 V frame consists of a single cabinet housing the UPS components. including optional internal batteries VRLA and Lithium-ion.
Page 31
UPS cabinet, EBC. All cabinets used will be the same height and will be designed to be positioned side by side to form an aesthetically appealing equipment suite. Figure 3.6 Cabinet Arrangement for Vertiv™ Liebert® APM2 60 kVA 208 V and 120 kVA 480 V UPS Item...
NOTE: There must be an interval of 5 seconds between repeated remove or Insert of the power module on the device. Figure 3.7 Vertiv™ Liebert® Power Module Installation Indicators and Controls for Vertiv™ Liebert® APM2 60 kVA 208 V and 120 kVA UPS...
Page 34
NOTE: There must be an interval of 5 seconds between repeated remove or Insert of the power module on the device. Figure 3.8 Vertiv™ Liebert® Bypass Module Installation Indicators and Controls for Vertiv™ Liebert® APM2 60 kVA 208 V and 120 kVA UPS...
Vertiv™ Liebert® APM2 User Manual 3.10.3 Control Module The Control module has two Vertiv™ Liebert® IntelliSlot™ interface card bays and connections for optional ancillary cabinets and for other options. See Figure 4.7 on page 44 through Figure 4.10 on page 47 for more information. Control Modules should only be replaced by authorized Vertiv service personnel.
Vertiv™ Liebert® APM2 User Manual 4 Electrical Installation This chapter describes the electrical installation of the Vertiv™ Liebert® APM2 UPS. After completing the mechanical installation of the UPS, it is necessary to connect the power cable and signal cable of the UPS.
NOTE: The cables used must be in accordance with NEC ANSI/NFPA 70. Cable sizes should be suitable for operation at a maximum temperature of 104 °F (40 °C). Table 4.1 Maximum Steady State AC and DC Currents for Vertiv™ Liebert® APM2 60 kVA 208 V 4-Wire System Rated Current (A)
Page 39
The battery discharge current is calculated according to the battery cell number of 40, EOD voltage of 1.63 V and 100% load percentage. Table 4.3 Maximum Steady State AC and DC Currents for Vertiv™ Liebert® APM2 120 kVA 480 V 4-Wire/3-Wire...
Vertiv™ Liebert® APM2 User Manual 4.1.3 Recommended Cross-sectional Area of UPS Cable The recommended cross-sectional area (CSA) of the UPS cable is given in Table 4.4 below. Table 4.4 Recommended CSA for Vertiv™ Liebert® APM2 60 kVA 208 V 4-Wire System Input Output...
• • • All recommended breakers in the Table 4.7 below are based off of using 100% rated breakers. Table 4.7 Recommended OPD for Vertiv™ Liebert® APM2 60 kVA 208 V 4-Wire System Model (kVA) RIB (A) MIB (A) BIB and MBB (A)
Page 42
Vertiv™ Liebert® APM2 User Manual Table 4.7 Recommended OPD for Vertiv™ Liebert® APM2 60 kVA 208 V 4-Wire System Model (kVA) RIB (A) MIB (A) BIB and MBB (A) BCB (A) NOTE: These values are at Ambient Temperature: 77 °F (25 °C).
The Vertiv™ Liebert® APM2 series UPS supports top cable access. To route and connect the power cables, use the following procedure. WARNING! Risk of electric shock. Can cause equipment damage, personnel injury or death. Verify that all external and internal power switches of the UPS are turned off and locked out or tagged out before installing the cables or making any electrical connections.
Vertiv™ Liebert® APM2 User Manual 4.2 Signal Cable Wiring 4.2.1 Overview Based on the site’s specific requirements, the Vertiv™ Liebert® APM2 UPS can require: • Auxiliary connection. • Communicate with a computer. • Provide alarm signal to the external devices.
328.1 ft. (100 m) or less, use a shielded wire with both ends of the shielded wire properly grounded. If the length exceeds 328.1 ft. (100 m), the shielded wire must go through a metal conduit. NOTE: For Vertiv™ Liebert® APM2 with internal batteries the GHMI will remain online for 5 minutes unless the internal battery breakers are manually opened.
See Figure 4.4 on page 41 for the positions of the parallel and LBS communication port. 4.2.8 Vertiv™ Liebert® IntelliSlot™ Port The Vertiv™ Liebert® APM2 UPS consist of two Liebert® IntelliSlot™ ports which allows field installation of the optional communication cards, including Vertiv™ Liebert® IS-UNITY-DP card, Vertiv™ Liebert® IS-Relay card. Table 4.18 below describes the models and installation positions of the optional cards.
Vertiv™ Liebert® APM2 User Manual Figure 4.11 Signal Cables Wiring Route of Vertiv™ Liebert® APM2 60 kVA 208 V and 120 kVA 480 V UPS Item Description Connect them to corresponding terminals. Lead the signal cables into the cabinet through this cabling entry plate.
Most of the settings will depend on the UPS type and features. Other settings will be made during the UPS setup by Vertiv tech service personnel. The touchscreen control panel display Liebert® APM2 shows data either graphically or as text.
Vertiv™ Liebert® APM2 User Manual 5.2.1 Vertiv™ Liebert® APM2 Touchscreen Control Panel Components The main areas of the Liebert® APM2 touchscreen control panel are shown in Figure 5.1 below and Figure 5.2 on the facing page. The display arrangement and the information displayed can be changed. At login for all access levels, the Liebert®...
Service: Input wiring and breaker configuration, protocol used and battery charging method. Visible to Service 5.3 Operation 5.3.1 Login to the Vertiv™ Liebert® APM2 Touchscreen Control Panel The Liebert® APM2 touchscreen control panel provides security by limiting the authority to change how the UPS operates.
Page 62
Administrator or Service level access. The Vertiv™ Liebert® APM2 touchscreen control panel is On when the UPS has control power. It is inactive and appears dark, depending on its settings. Touch the touchscreen to turn it On.
Page 64
UPS is prepared for the inverter to start. When the operator access is shown, commands are the same for all access levels. The Vertiv™ Liebert® APM2 touchscreen control panel displays a message asking for confirmation. Touch On to confirm shown in Figure 5.5 below.
Vertiv™ Liebert® APM2 User Manual Figure 5.9 Energy Saving Mode Activation 5.4 Viewing UPS Status The Vertiv™ Liebert® APM2 Touchscreen displays the UPS status in two ways: graphic views and text views. Each view shows the same readings. 5.4.1 Status Bar Component The status bar indicates UPS status by: •...
Vertiv™ Liebert® APM2 User Manual 6 Single UPS Operation This chapter briefly describes the operating precautions and routine operations for the Vertiv™ Liebert® APM2 UPS single module. For the operating precautions and routine operating methods of UPS parallel system, see...
Vertiv™ Liebert® APM2 User Manual Figure 6.1 UPS Power Switch Four Switches for Vertiv™ Liebert® APM2 60 kVA 208 V and 120 kVA 480 V UPS Item Description Item Description 6.3 UPS Start-up Procedures The Liebert® APM2 UPS must be completely installed and commissioned before start-up by an authorized engineer. The external power supply switch must be closed.
The system is powered on, and the start-up screen activates. 3. If ECO mode is necessary, contact a Vertiv service engineer to activate it through the software setting. If you wish to activate it by yourself, you can enable it through the Energy Saving Mode Activation on the touchscreen. For...
WARNING! Start the UPS strictly following the above procedure. Failure to do so can cause the device to malfunction. Figure 6.7 Battery Cold Start Button for Vertiv™ Liebert® APM2 60 kVA 208 V and 120 kVA 480 V UPS Power Module Item...
Follow the procedure below to transfer the load from the bypass mode to the normal mode. Activate the system and login to the system. 2. Verify that the Vertiv™ Liebert® APM2 UPS is in bypass mode. 3. Touch the Operate tab.
The load has transferred to UPS normal mode. 6.5 Battery Test Procedures The battery test function is disabled by default. If you need this function, contact Vertiv's customer service. The battery self-test includes a periodic self-test and a manual maintenance self-test.
Page 83
The battery discharges 20% of total battery energy. The periodic self-test tests the battery activity. This test is regular and can be configured through the Vertiv setting software. During the periodic self-test, the system generates audible/visual alarm and corresponding records if the battery maintenance requirement is met.
10 minutes. During the automatic recovery delay, the UPS charges its batteries to provide a safety margin for equipment shutdown if input power fails again. NOTE: During the automatic restart process, manual start-up is disabled. Automatic restart must be set by Vertiv's authorized service engineer through Vertiv setting software.
IMPORTANT! Users must choose appropriate switching devices to protect the battery from short circuit and overload. It is recommended to use the Vertiv BCB to provide better battery protection. The battery is connected to the UPS through the BCB. The BCB is manually closed and has the electronic tripping device controlled by the UPS control circuit.
7.8 Internal Battery Vertiv™ Liebert® APM2 UPS supports the following internal modular VRLA batteries. Each Liebert® APM2 UPS supports up to sixteen integrated VRLA battery modules. Each individual battery module contains BCB, eight 9AH VRLA batteries connected in series, and communications to central UPS BMS.
If users wish to choose a battery system with a long backup time, they can choose modular external battery cabinet (EBC), which can carry more battery modules. For lead-acid batteries, up to 32 modules can be placed. For more details, refer Vertiv™...
Ensure that the selections of the parallel cables are correct, and that the modules are of the same rating, model, and use the same software and hardware release. IMPORTANT! Vertiv service personnel must configure each module separately using Vertiv setting software to achieve coordinated operation of the modules in the parallel system.
8.3.3 Procedures for Isolating One UPS Module from Parallel System IMPORTANT! The isolation procedures should be carried out only by Vertiv certified service personnel. NOTE: After isolating one UPS module, when the parallel system is not overload, then proceed with steps below.
8.3.4 Procedures for Inserting One isolated UPS Module in Parallel System IMPORTANT! These procedures must only be carried out by service personnel of Vertiv or under their guidance. The following procedures are used to reintegrate a UPS module that has been previously isolated from the parallel system: Confirm that the I/O cable, battery cable, and parallel cable of the single module are correctly connected.
Manual_SL-52645 Web, simple network management system (SNMP), Modbus, BACnet, and YDN23. NOTE: Preserve the screws and port cover for future use. Insert the UNITY card (along two sides of the Vertiv™ Liebert® IntelliSlot™ port) into the indicated position recommended in Table 1.1 on page 1, and then tighten the screws.
9.2.5 Vertiv™ Liebert® IS-Relay Card Vertiv™ Liebert® APM2 UPS has an optional Liebert® IS-Relay card to use the dry contact signal to monitor the UPS functionalities. The functions of the Liebert® IS-Relay card are listed in Table 9.3 on the facing page. See Figure 9.4 below for more information of IS-Relay card.
Closed if On Bypass Common-On Bypass For more information of the Liebert® IS-Relay card, refer to the Vertiv™ Liebert® IntelliSlot™ IS-Relay Card User Manual_SL- 52645 in accessory. The installation method of the Liebert® IS-Relay card is the same as that of the SIC card described in SIC card. See...
The LBS extender, as shown in Figure 9.5 below is designed to extend the LBS function up to 492.2 ft. (150 m) between the two UPS units or systems of a dual bus system, and it also enables an Vertiv™ Liebert® APM2 UPS to synchronize with other UPS models.
Using network management system through the SNMP function provided by the Liebert® IS-Unity-DP card. The Liebert® IS-Unity-DP card shall be installed at the Vertiv™ Liebert® IntelliSlot™ port. See Figure 4.4 on page 41 for more information of position of various communication card. And the installation and configuration can refer to Vertiv™ Liebert®...
Vertiv™ Liebert® APM2 User Manual 12 Specifications This chapter includes all the required UPS specifications. 12.1 Conformance and Standards The Vertiv™ Liebert® APM2 has been designed to conform to the following standards: • Safety UL 1778, 5th Edition, CSA 22.2 107.3-14. •...
12.5 Electrical Characteristics (Battery Bus) Table 12.4 Battery Rated Power (kVA) Item Unit Vertiv™ Liebert® APM2 60 kVA 208 V Liebert® APM2 120 kVA 480 V Max. charging current Quantity of lead- 30 to 50 (12 VDC). (40 to 50 full load, 40 derated to 95%, 36 16 to 24 jars for lead acid battery (208V).
12.7 Electrical Characteristics (Bypass Input) Table 12.6 Bypass Input Rated Power (kVA) Item Unit Vertiv™ Liebert® APM2 60 kVA 208 V Liebert® APM2 120 kVA 480 V 480 4-wire (3-phase + N +PE) Rated AC voltage 208/220 4-wire (3-phase + N +PE)
Vertiv™ Liebert® APM2 User Manual 12.8 Efficiency and Loss Table 12.7 Efficiency, Loss, and Air Exchange for Vertiv™ Liebert® APM2 60 kVA 208 V 4-Wire System AC/AC Efficiency Data Rated power, kVA 10 kVA to 60 kVA Dual conversion mode efficiency, % 95%±0.2%...
Need help?
Do you have a question about the Liebert APM2 and is the answer not in the manual?
Questions and answers