Page 2
The products covered by this instruction manual are manufactured and/or sold by Vertiv. This document is the property of Vertiv and contains confidential and proprietary information owned by Vertiv. Any copying, use, or disclosure of it without the written permission of Vertiv is strictly prohibited.
1 Important Safety Instructions 1.1 Personnel Safety A Vertiv authorized engineer must install and commission the UPS. Failure to do so can cause product malfunction or personal safety risk. Read the UPS manual and safety precaution carefully, failure to do so can cause product malfunction or personal safety risk.
Page 6
Liebert® APM2 lithium battery modules must be commissioned and maintained by Vertiv engineer or its agent. Failure to do so may cause risk of personal safety and lead to equipment failure, and the resulting damage to the equipment is not covered by the warranty.
Page 7
WARNING! Power cables must be routed in a metal raceway or metal floor trough to prevent cable damage and reduce electromagnetic radiation. WARNING! Prohibit wiring inside the Vertiv™ Liebert® APM2 lithium battery module cabinet that is not related to this equipment.
Page 8
Battery products are not permitted to be near sources of ignition or water, not even a small sporadic fire or water droplets. • Vertiv™ Liebert® APM2 lithium battery modules and their battery modules are not waterproof or dustproof. IMPORTANT! Dispose the batteries in accordance with local laws and regulations. NOTICE The lithium battery deployment room needs to be equipped with fire protection facilities.
Vertiv™ Liebert® APM2 Lithium Battery Module Installer/User Guide 2 Overview This chapter describes the features, product introduction, system design, and key component functions of the Vertiv™ Liebert® APM2 lithium battery module. 2.1 Product Features Liebert® APM2 lithium battery module is a ternary lithium battery product, which is used with the APM2 120k UPS to provide backup energy storage.
Vertiv™ Liebert® APM2 Lithium Battery Module Installer/User Guide 2.4 Working Principle The Vertiv™ Liebert® APM2 lithium battery modules, along with UPS equipment, provide uninterruptible power supplies for communications, and data processing equipment, as a backup energy storage system for critical equipment.
Pre-charge resistance 2.4.2 Module status Resting state The Vertiv™ Liebert® APM2 lithium battery module system is in a non-charging and non-discharging state, the BMS is active and the main circuit is ON. Charging state When the Liebert® APM2 lithium battery module is in the charging state, the UPS is allowed to charge the battery cluster. The charging current is sent by the lithium battery module, and the UPS controls the charger to output the current.
Vertiv™ Liebert® APM2 Lithium Battery Module Installer/User Guide Figure 2.5 Structure Diagram of Vertiv™ Liebert® APM2 Lithium Battery Module 2.5.2 Electrical control components The key components of the electrical control of the Liebert® APM2 lithium battery module are specified as below: •...
3.1 Prerequisites The Liebert® APM2 lithium battery module must work with the Vertiv™ Liebert® APM2 120 kVA UPS. The UPS must meet the operating environment requirements of the lithium battery module. Because each site has its particularity, this section provides installation personnel with general installation procedures and methods, which are handled according to the specific site conditions.
Vertiv, with the optimal storage temperature being 20°C to 25°C. NOTE: The indoor environment where the Vertiv™ Liebert® APM2 lithium battery module is installed must be equipped with constant temperature and humidity precision air conditioners.
Vertiv immediately for assistance. Unpack the battery under the guidance of a Vertiv authorized service engineer as follows: Use an electric forklift to carry the lithium battery module boxes to the installed UPS rack.
Vertiv customer service center in time. 3.4 Lithium Battery Module Installation Vertiv™ Liebert® APM2 lithium battery modules are all packaged in a single, independent package, and the lithium battery modules all need to be installed onsite.
Vertiv™ Liebert® APM2 Lithium Battery Module Installer/User Guide 3.5 Lithium Battery Module Paramset Set Up Open your laptop's Paramset software and left click on the red box labeled Battery Parameter. Figure 3.2 Paramset Software Set battery parameters: Set the battery material type as 7, battery cabinet type as 3, the number of built-in battery modules for 8, the number of external battery cabinets for 0, the number of batteries in each group for 132, the battery capacity of 14, the battery charging current limiting current for 1.1, the battery single float voltage of 4.180, the battery single average charging voltage of 4.180.
Page 21
Vertiv™ Liebert® APM2 Lithium Battery Module Installer/User Guide Figure 3.3 Configuration of Battery Parameters_1 Set the battery system communication protocol to 7, charger overvoltage fault detection point is 4.350, charging cutoff protection point is 4.270, minimum battery EOD voltage is 2.90, maximum battery EOD voltage is 2.90.
Vertiv™ Liebert® APM2 Lithium Battery Module Installer/User Guide 4 Startup, Operation, and Commissioning This chapter describes the process and operation of powering ON and OFF the Vertiv™ Liebert® APM2 lithium battery module. 4.1 Notes NOTE: Operate the UPS only after it is commissioned and started by the Vertiv authorized engineer.
User can also disconnect the battery by pressing the emergency shutdown EPO button of the UPS. For details, refer the SL-71058 Vertiv™ Liebert® APM2 300 to 600 kVA Modular UPS User Manual and SL-71076 Vertiv™ Liebert® APM2 30 to 120 kVA Modular UPS User Manual.
Vertiv™ Liebert® APM2 Lithium Battery Module Installer/User Guide 4.4 Commissioning Record List The commissioning record is given in the Table 4.1 below for user reference. Table 4.1 Reference Commissioning Record List Form Test Items Inspection Standards Result Test Items Inspection Standards...
5 Operation Control Display Panel 5.1 Overview Display HMI touch control panel of the Vertiv™ Liebert® APM2 lithium battery module UPS Cabinet (referred to as the touchscreen), collect information about the operating status of the Liebert® APM2 lithium battery module and displays it in the form of a graph or text.
Page 28
Vertiv™ Liebert® APM2 Lithium Battery Module Installer/User Guide The main interface of the system after startup is shows below. See Figure 5.2 below. Figure 5.2 Home Page Figure 5.3 below shows the main screen of the HMI display about the lithium battery module information, click battery icon on the main screen.
Page 29
Vertiv™ Liebert® APM2 Lithium Battery Module Installer/User Guide Figure 5.4 Lithium Battery Status Figure 5.5 below shows the main screen of the HMI display about the lithium module information, click battery icon on the main screen. The specific lithium battery module information will be displayed on the left side.
Page 30
Vertiv™ Liebert® APM2 Lithium Battery Module Installer/User Guide Figure 5.6 Event Log Details Figure 5.7 below shows the HMI display of the lithium module specific information, click on the STATUS in the upper left corner of the main screen then click on the horizontal ellipses and then click on BATTERY MONITOR.
Page 31
Vertiv™ Liebert® APM2 Lithium Battery Module Installer/User Guide Figure 5.8 below shows the battery discharge curve displayed by the HMI as below: Figure 5.8 Battery Discharge Curve Figure 5.9 below shows the battery voltage and temperature data displayed by the HMI as below: Figure 5.9 Battery Specific Voltage and Temperature Data...
Page 32
Vertiv™ Liebert® APM2 Lithium Battery Module Installer/User Guide Figure 5.10 Battery Specific Voltage and Temperature Data Figure 5.11 below shows the specific information of the lithium battery module of the HMI display, click on the STATUS in the upper left corner of the main screen then click on horizontal ellipses. Then click on ABOUT, to view the specific version of the battery information and the program version of module 1 to module 8.
Page 33
Vertiv™ Liebert® APM2 Lithium Battery Module Installer/User Guide Figure 5.12 below shows the specific information of the lithium battery module of the HMI display, click on the STATUS in the upper left corner of the main screen then click on horizontal ellipses and then click on EVENT LOG, to view the specific log information of the battery.
Vertiv™ Liebert® APM2 Lithium Battery Module Installer/User Guide 5.2 LED Display Figure 5.14 LED Indicators Item Name Descriptive Operational State Always On: High voltage power ON HV status High voltage indicator, green Normally extinguished: High voltage under power Always On: Charging...
Vertiv™ Liebert® APM2 Lithium Battery Module Installer/User Guide 5.3 Operation of Touchscreen 5.3.1 Access level login The touchscreen has three access levels: observer, operator, and administrator, and provides different permissions and functions respectively. Table 5.1 Access Level Login Access Level...
Vertiv™ Liebert® APM2 Lithium Battery Module Installer/User Guide 5.3.2 Touchscreens The main screen after power ON is shown in Figure 5.15 below. The information on the main screen is visible to all access level users. Figure 5.15 Components Display at Main Page On the main page, the right side displays the current battery system's available power status SOC.
Vertiv™ Liebert® APM2 Lithium Battery Module Installer/User Guide 5.4 Alarm List The Table 5.2 on the next page provides a complete list of all Vertiv™ Liebert® APM2 lithium battery module alarm messages that are displayed in the real time alarms and history menus.
Page 38
Vertiv™ Liebert® APM2 Lithium Battery Module Installer/User Guide Table 5.2 Alarm List (continued) Serial Alarm Meanings Number Charging low temperature Low temperature secondary protection when charging, protection cuts off the output. protection Charging high temperature High temperature secondary protection when charging, protection cut off output.
Vertiv™ Liebert® APM2 Lithium Battery Module Installer/User Guide 6 Product Specification This chapter provides product specifications for the Vertiv™ Liebert® APM2 lithium battery module. 6.1 Applicable Standards The Liebert® APM2 lithium battery module is designed to meet European and international standards as shown in Table 6.1 below.
The routine inspection and maintenance of the lithium battery module can be carried out by personnel who have received relevant training, and the inspection and replacement of its components should be carried out by Vertiv authorized professionals. The parts behind the protective cover that can be opened only by tools are not operable by users. Only qualified maintenance personnel are allowed to open the protective cover.
7.4.1 General The factory SOC of the Vertiv™ Liebert® APM2 lithium battery module is 70% to 80%. When using the APM2 for the first time, start the UPS to charge the lithium battery module. During this process, the lithium battery module has the power backup capability, but the backup time is shorter than the standard value.
Page 44
Vertiv™ Liebert® APM2 Lithium Battery Module Installer/User Guide Table 7.2 Vertiv™ Liebert® APM2 Lithium Battery Module Maintenance Record Sheet (continued) Form Test Items Record Test Items Record Maximum cell voltage Minimum cell voltage Battery parameter logging Maximum cell temperature Minimum cell temperature...
Contact the carrier and Vertiv local service personnel in a timely manner in case of any damage to the packaging caused by dropping, tipping, and squeezing.
Vertiv™ Liebert® APM2 Lithium Battery Module Installer/User Guide Appendices Appendix A: Technical Support and Contacts A.1 Technical Support/Service in the United States Vertiv Group Corporation 24x7 dispatch of technicians for all products. 1-800-543-2378 Liebert® Thermal Management Products 1-800-543-2378 Liebert® Channel Products 1-800-222-5877 Liebert®...
Need help?
Do you have a question about the Liebert APM2 and is the answer not in the manual?