NOTE: LED= Light Emitting Diode
LABELING EXPLANATION:
X: Self contained
1: Maintained (*)
A: Including test device
G: Internally illuminated
180: 3 hours duration
(*) Maintained operation: The luminaire lights its illumination source, when it is powered by the
mains power supply or not.
Non Maintained operation: The luminaire lights its illumination source, only in power supply's
failure.
The light source contained in this luminaire shall only be replaced by the manufacturer, or his
agent, or a similar qualified person.
NOTE! The light source is non-user replaceable.
WARRANTY
Olympia Electronics guarantees the quality, condition and operation of the goods. The period of warranty
is specified in the official catalogue of Olympia Electronics and also in the technical leaflet, which
accompanies each product. This warranty ceases to exist if the buyer does not follow the technical
instructions included in official documents given by Olympia Electronics or if the buyer modifies the goods
provided or has any repairs or re-setting done by a third party, unless Olympia Electronics has fully
agreed to them in writing. Products that have been damaged can be returned to the premises of our
company for repair or replacement, as long as the warranty period is valid.
Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the
buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the
buyer the transportation cost.
HEAD OFFICE
72
nd
km. O.N.R. Thessaloniki-Katerini
P.C. 60300 P.O. Box 06 Εginio Pierias Greece
www.olympia-electronics.gr
info@olympia-electronics.gr
LED MODULE CHARACTERISTICS
SLD-28/DZ
Manufacturer
Model Number
0106163
Voltage Range
Nominal Power
0.78W
Connections
Cable connection between main pcb and led module
Temperature (tc)
Page 4 from 4
SLD-34/DZ
SLD-44/DZ
Olympia Electronics S.A.
2312083
1307083
8.7-10.8V DC
0.975W
45 °C max. across the board
922044000_09_027
SELF TESTING MAINTAINED EMERGENCY ILLUMINATION SIGNS WITH WHITE LEDs
TECHNICAL CHARACTERISTICS
Mains voltage
Maximum power consumption
Battery (Ni-MH)
Battery protection
Indications
Recharging time
Minimum emergency duration
Light source intensity (230V) / (emerg.)
Degrees of cover protection
Produced in accordance with
Operation temperature range
Relative humidity
Construction materials
External panel's dimensions
External unit's dimensions
Typical weight
Guarantee
Thank you for your trust in our products
Olympia Electronics - European manufacturer
Description
The luminaire consists mainly from two parts.
The body, where all the electronics are located
and the lamp-head where the indication sign
and the high efficiency LEDs are located.
M a i n t a i n e d / N o n m a i n t a i n e d s e l e c t i o n
capability
Power on the device and press continuously the
TEST button for 10 seconds, until the led strip
turns off. Release the button and after a short
emergency test, the device operates as non-
maintained. If you want to restore the previous
condition (maintained operation), press
continuously the TEST button for 10 seconds,
until the led strip lights. Release the button and
after a short emergency test, the device
operates as maintained illumination sign.
Installation
To install the illumination sign follow the
installation instructions on page 2.
Battery Charging
The battery charging is completely controlled. In
this case, is achieved the perfect
battery
maintenance , as well as the elongation of its
duration. When the battery has completely
charged, it charges with a maintenance current.
Page 1 from 4
(for LED MODULE specifications see page 4)
SLD-28/DZ
SLD-34/DZ
220-240V AC/50-60Hz
9 VA
9.5 VA
3.6V/1.5Ah
Overcharging and deep discharging protection
Charge LED, Lamp LED, Fault LED, Test Button
24h
3h
100lm /100lm
125lm /125lm
IP30
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
o
5 to 40 C
up to 95%
ABS/PC, aluminum, Acrylic plate
280x120x15mm
340x190x15mm
440x240x15mm
289x65x34mm
680gr.
1020gr.
3 years (1 year for the battery)
Battery Cut-off
The luminaire enters in this operation when
the mains power supply fails and battery has
lost its energy. During this operation the
luminaire enters the idle state and battery
consumption is negligible, in order to be
protected from deep discharge.
Manual Test
The manual test can be conducted only if the
mains
power
supply
and
the
connected. By pressing the test button briefly an
operation test is initiated. During this test period
all indication LEDs are OFF.
Automatic Test
This test includes all the operations that provide
the manual test and is conducted automatically
every 15 days. In order to be performed, the
mains power supply and the battery should be
connected.
Automatic Autonomous Test
The Automatic Autonomous Test is conducted
and measures the luminaire`s back up operation.
This test is conducted automatically every six
months. In order to be performed, the mains
power supply and the battery should be
connected (the battery should be charged). If the
battery is not charged, the test is postponed until
the battery is completely charged. If during the
922044000_09_027
SLD-44/DZ
1380gr.
battery
is
Need help?
Do you have a question about the SLD-28/DZ and is the answer not in the manual?