Download Print this page
olympia electronics POWER LIGHT Series Manual

olympia electronics POWER LIGHT Series Manual

For non-maintained emergency luminaires

Advertisement

Quick Links

``POWER LIGHT`` SERIES FOR NON-MAINTAINED EMERGENCY LUMINAIRES
TECHNICAL CHARACTERISTICS
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERY (Pb)
BATTERY PROTECTION
INDICATIONS - CONTROLS
CHARGING TIME
MINIMUM AUTONOMOUS DURATION
LIGHT SOURCE
EMERGENCY ILLUMINATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIALS
EXTERNAL DIMENSIONS
TYPICAL WEIGHT
GUARANTEE
Thank you for purchasing this product of
Olympia Electronics. A European manufacturer.
GENERAL
These luminaires are used indoors (ta 40 C)
where emergency light is needed. Each
luminaire must be permanently connected to
mains power supply. In normal operation the
power indicator lights and the charge indicator
blinks to show that the batteries are in charging
condition. In case of a mains power supply
failure the power and the charge indicators
turns off and the luminaire will light the spot
lamps automatically in emergency mode. When
the
mains
power
device turns to normal operation.
INSTALLATION
To install the luminaire follow the installation
instructions οn page 2.
OPERATION
When the device is powered from the mains,
the charge indicator blinks and confirms the
charging of the batteries. When the batteries
are charged, it lights constantly. If it does not
light, probably, the batteries are disconnected. If
it does not light and the batteries are
connected, then contact the technician. As long
as the charge indicator blinks, the batteries of
the luminaire are charging and in this period,
any autonomy test must be avoided. When the
charging circle is complete, the indicator lights
continuously (it can be used as an indication of
a power interruption). The batteries charging is
done by a 3 stages technological advanced
procedure, to ensure the appropriate and full
charging of the batteries. The power indicator
Page 1 from 2
GRL-21
3.5W / 10VA
6V/4Ah
White LEDs
660lm
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
1965gr.
supply
is
restored the
High Quality European based Manufacturers
GRL-21/H/90 GRL-21/H/180
220-240V AC/50-60Hz
12V/7Ah
From overcharge and deep discharge
Power indicator, battery charge indicator, TEST button
90 min
White power LEDs
0 to 40 C
Up to 95%
Bayblend FR3010, transparent polycarbonate
302x94x330mm
4100gr.
3 years (1 year for the battery)
confirms the proper connection to the mains. The
TEST button, has a dual use. If pressed
instantlly while the device is connected to the
o
mains,
the
interruption, by lighting the lamps for 3''. In this
way, we can control the driver circuit of the
lamps and the lamps as indicated in paragraph 3
in the text below.
Dimming option
When the voltage is interrupted, with
corresponding pressings of the button, we can
choose the illumination of 100%, 50%, 33% or
turned off, either to increase the autonomy time or
not to consume the battery power unnecessarily.
This option is canceled when the network is
restored.
ΑΤΤΕΝΤΙΟΝ!!!
1. Operations for installation, maintainance or
testing must be done by authorized personel
only.
2. The device must be connected to the mains
power supply thru a fuse dependent by the total
amount of the line's power load.
3. It is sugested to check every month the
indication LED for battery charging, and by
pushing instantly the TEST button to check the
emergency cirquit and the lamps. If the luminaire
does not light
4. It is sugested to check every 6 months the
minimum autononous duration by disconnecting
the mains power supply. Count the time that the
lamps light and in case of less time than the
minimum autonomous duration the batteries
must be replaced. If the measured time is
considerably less than the minimum autonomous
12W / 16VA
2x12V/7Ah
<24h
180 min
2000lm
IP 42
o
6300gr.
device
simulates
contact the installer.
923029009_09_005
GRL-29
12V/7Ah
White LEDs
1260lm
3560gr.
the
power

Advertisement

loading

Summary of Contents for olympia electronics POWER LIGHT Series

  • Page 1 3 years (1 year for the battery) Thank you for purchasing this product of confirms the proper connection to the mains. The Olympia Electronics. A European manufacturer. TEST button, has a dual use. If pressed GENERAL instantlly while the device is connected to the...
  • Page 2 duration contact the installer. The replacement (*) Non-Maintained operation: The luminaire of the battery and the light source must be done lights its illumination source, only in power u s i n g p a r t s o f t h e s a m e t y p e , b y t h e supply’s failure.

This manual is also suitable for:

Grl-21Grl-21/h/90Grl-21/h/180Grl-29