EDUS371705A-N
15.2.2. Mode 2
value is possible.
In general, normal operation can be resumed without special interven-
tion, recovery/vacuuming setting, adding refrigerant setting, etc.). In
such a case, it is required to abort the special operation before normal
Cool/Heat selection setting is used in case the optional
Cool/Heat selector (KRC19-26A) is used. Depending on the
outdoor unit setup (single outdoor unit setup or multi outdoor
unit setup), the correct setting should be chosen. More
details on how to use the Cool/Heat selector option can be
found in the manual of the Cool/Heat selector.
Default value=0.
operation (by Cool/Heat selector if installed).
1=Master unit decides Cool/Heat operation when outdoor
units are connected in multiple system combination (a)
2=Sub unit for Cool/Heat operation when outdoor units
are connected in multiple system combination (a)
target temperature during cooling operation
e
Default value=0.
Value
[2-8]
method during cooling.
For more information and advice about the effect of these
target temperature during heating operation
c
Default value=0.
Value
[2-9]
method during heating.
For more information and advice about the effect of these
3P477778-1B
RELQ-TATJU / RELQ-TAYDU / RELQ-TAYCU
T
target
e
0
Auto (default)
2
43°F (6°C)
3
45°F (7°C)
4
46°F (8°C)
5
48°F (9°C)
6
50°F (10°C)
7
52°F (11°C)
T
target
c
0
Auto (default)
1
106°F (41°C)
3
109°F (43°C)
6
115°F (46°C)
English
If the system needs to run under low noise operation or
under power consumption limitation conditions when an
changed. This setting will only be effective when the optional
Default value=0.
-
In order to increase the static pressure the outdoor unit fan
is delivering, this setting should be activated. For details
Default value=0.
In order to add the additional refrigerant charge amount fol-
lowing setting should be applied.
Further instructions can be found in chapter 14.3. Method for
Default value=0.
To stop the additional refrigerant charge operation (when
the required additional refrigerant amount is charged), push
BS3. If this function was not aborted by pushing BS3, the
unit will stop its operation after 30 minutes. If 30 minutes
again.
In order to achieve a free pathway to recovering refrigerant
out of the system or to remove residual substances or to
vacuum the system it is necessary to apply a setting which
will open required valves in the refrigerant circuit so the
recovering of refrigerant or vacuuming process can be done
properly.
Default value=0.
To stop the refrigerant recovery/vacuuming mode, push
BS3. If BS3 is not pushed, the system will remain in refriger-
ant recovery/vacuuming mode.
By changing this setting, you can activate the automatic low
operation. Depending on the chosen level, the noise level
will be lowered (3: Level 3<2: Level2<1: Level1).
Default value=0.
If the system needs to run under low noise operation condi-
3<2: Level 2<1: Level 1).
control adaptor (DTA104A61/62) is installed and the setting
Default value=2.
Installation Manual
32
32