Eastron SDM230-LoRaWAN User Manual

Eastron SDM230-LoRaWAN User Manual

Din rail smart energy meter for long range wireless communication

Advertisement

SDM230-LoRaWAN User Manual
SDM230-LoRaWAN
DIN Rail Smart Energy Meter for Long Range Wireless Communication
USER MANUAL
2020 V1.0

Advertisement

Table of Contents
loading

Summary of Contents for Eastron SDM230-LoRaWAN

  • Page 1 SDM230-LoRaWAN User Manual SDM230-LoRaWAN DIN Rail Smart Energy Meter for Long Range Wireless Communication USER MANUAL 2020 V1.0...
  • Page 2: Table Of Contents

    SDM230-LoRaWAN User Manual Contents 1. Introduction 1.1 Unit Characteristics 1.2 Pulse Outputs 1.3 LoRaWAN Classes 1.4 Active Upload Mode 1.5 Join 1.6 Communication 2. Start Up Screens 3. Measurements 4 Setting Up 4.1 Setting 1 4.1.1 Pulse Output Type 4.1.2 Pulse Constant 4.1.3 Pulse Duration...
  • Page 3: Introduction

    Pulse output 2 is non-configurable. It is fixed to export kWh. The constant is 1000imp/kWh. 1.3. LoRaWAN Classes Eastron LoRaWAN energy meter is implement Class C functionality. The device will upload message after receiving the data sent from the network.
  • Page 4: Join

    The data format and encoding of meter communication protocol are modified based on the Modbus ASCII transmission mode. Remove the start and end characters from the Modbus ASCII transmission mode and change LRC validation to CRC validation. 2020 EASTRON EUROPE ALL RIGHTS RESERVED. www.eastroneurope.com - 2 -...
  • Page 5 Note: the first address of the register of the meter L1 current is 00 06 and the number of registers is 2. 2) After receiving the above command, the meter will return the current L1 current data of the meter, as shown in the following table after ASCII coding. 2020 EASTRON EUROPE ALL RIGHTS RESERVED. www.eastroneurope.com - 3 -...
  • Page 6: Start Up Screens

    2. Start Up Screens The first screen lights up all display segments and can be used as a display check. The second screen indicates the firmware version. (left picture is for reference only) 2020 EASTRON EUROPE ALL RIGHTS RESERVED. www.eastroneurope.com - 4 -...
  • Page 7: Measurements

    Selects the measured parameters In Set-up Mode, this is the “Up” button. In Set-up Mode, this is the “Enter”, “Left” and “Confirm” button The display order by scroll button Total kWh Import kWh 2020 EASTRON EUROPE ALL RIGHTS RESERVED. www.eastroneurope.com - 5 -...
  • Page 8 SDM230-LoRaWAN User Manual Export kWh Resettable total kWh Total kVArh Import kVArh 2020 EASTRON EUROPE ALL RIGHTS RESERVED. www.eastroneurope.com - 6 -...
  • Page 9 SDM230-LoRaWAN User Manual Export kVArh Resettable total kVArh Max. power demand Voltage 2020 EASTRON EUROPE ALL RIGHTS RESERVED. www.eastroneurope.com - 7 -...
  • Page 10 SDM230-LoRaWAN User Manual Current Active Power Reactive Power Apparent Power 2020 EASTRON EUROPE ALL RIGHTS RESERVED. www.eastroneurope.com - 8 -...
  • Page 11 SDM230-LoRaWAN User Manual Power Factor Frequency Pulse constant ID (High address) 2020 EASTRON EUROPE ALL RIGHTS RESERVED. www.eastroneurope.com - 9 -...
  • Page 12: Setting Up

    Total running time 4. Setting Up To enter set-up mode, pressing the button for 3 seconds, until the password screen appears. Display Descriptions The setting is done correctly The setting is not correct 2020 EASTRON EUROPE ALL RIGHTS RESERVED. www.eastroneurope.co - 10...
  • Page 13: Setting

    3s to confirm. 4.2.2 Pulse Constant Use this to set the energy represented by each pulse Pulse Constant Default: 1000 kWh (means 1 impulse represent 1000kWh) Range: 1 / 10/ 100/ 1000 kWh 2020 EASTRON EUROPE ALL RIGHTS RESERVED. www.eastroneurope.co - 11...
  • Page 14: Pulse Duration

    3s to confirm the setting. 4.2.3 Pulse Duration Pulse Duration Default: 200 Range: 60/ 100/ 200 mS Press for 3s, the red part will flash. Press to choose the required selection. 2020 EASTRON EUROPE ALL RIGHTS RESERVED. www.eastroneurope.co - 12...
  • Page 15: Demand Interval Time (Dit)

    Range: 60/ 30/ 15/ 10/ 5/ OFF Press for 3s, the current demand interval time will flash. Press to choose the required selection. Press for 3s to confirm the setting. 4.2.5 Automatic Scroll Time Interval 2020 EASTRON EUROPE ALL RIGHTS RESERVED. www.eastroneurope.co - 13...
  • Page 16: Backlight Time(Lp)

    The screen will show the currently selected backlight time. Default: 60 minutes Range: 120/ 60/ 30/ 20 / 10/ 5 / OFF If it is seated as 5, the backlit will be off in 5 minutes. 2020 EASTRON EUROPE ALL RIGHTS RESERVED. www.eastroneurope.co - 14...
  • Page 17: Clear Demand Information

    This option is to reset the demand and resettable kWh/kVArh information. From the Set-up menu, use buttons to select the clear option. Press for 3s. The CLR will flash. Press again for 3s to confirm the resetting. 2020 EASTRON EUROPE ALL RIGHTS RESERVED. www.eastroneurope.co - 15...
  • Page 18: Password

    The screen shows the current password. Default: 1000 Range: 0001-9999 Press for 3s, the current digit will flash. Press to choose the required digit, press to move to the next digit. 2020 EASTRON EUROPE ALL RIGHTS RESERVED. www.eastroneurope.co - 16...
  • Page 19: Checking Meter Information

    ( refer to section 4.3). 1) Join Information Activation Way:OTAA DevEui: end-device identifier ****************(16 digits) Activation Way:ABP DevAddr: End-device address ********(8 digits) Activation Way:OTAA AppEui: application identifier ****************(16 digits) 2020 EASTRON EUROPE ALL RIGHTS RESERVED. www.eastroneurope.co - 17...
  • Page 20 ********************************(32 digits) Activation Way:OTAA AppKey: Application key ********************************(32 digits) Activation Way:ABP AppSKey: Application session key ********************************(32 digits) 2) Join Status JOIN OK Means the meter is connected to the gateway successfully 2020 EASTRON EUROPE ALL RIGHTS RESERVED. www.eastroneurope.co - 18...
  • Page 21 JOIN MOdE: Abp 4) AUTO When AUTO function is ON, the meter will send a command to gateway automatically to check the connection status with gateway. Interval time is configurable. AUTO 2020 EASTRON EUROPE ALL RIGHTS RESERVED. www.eastroneurope.co - 19...
  • Page 22: Join Information

    Below information can be adjusted through password “2308”: 4.3.1 Join Information: Join information including DevEui, AppEui, Appkey under OTAA mode and DevAddr, NwkSKey, AppSKey under ABP mode. 2020 EASTRON EUROPE ALL RIGHTS RESERVED. www.eastroneurope.co - 20...
  • Page 23 And then set the same on P3 and P4 After P4 setting, Press return to the DevEui page, press move to the next setting page: AppEui and Appkey. Use the same way to set AppEui and Appkey. 2020 EASTRON EUROPE ALL RIGHTS RESERVED. www.eastroneurope.co - 21...
  • Page 24: Join Mode: Otaa/Abp

    4.3.2 Join Mode: OTAA/ ABP Join mode Option: OTAA, ABP Press for 3s, the current option will flash. to choose the option. Press for 3s to confirm. 4.3.3 Re-Join 2020 EASTRON EUROPE ALL RIGHTS RESERVED. www.eastroneurope.co - 22...
  • Page 25: Auto: Upload On/Off, Upload Interval Time

    AUTO option. Press for 3s enter to the setting page. UP LOAd: OFF Range: ON/OFF Press for 3s, the current option will flash. to choose the option. 2020 EASTRON EUROPE ALL RIGHTS RESERVED. www.eastroneurope.co - 23...
  • Page 26: 3.5 Join Delay

    When Join delay function is ON, the meter will join the LoRaWAN network with a few seconds delay after booting. When Join delay function is OFF, the meter will join the LoRaWAN network once the power is on. 2020 EASTRON EUROPE ALL RIGHTS RESERVED. www.eastroneurope.co - 24...
  • Page 27: 3.6 Off Line

    Default: 60 minutes 60 minutes means from the last message received from gateway, if over 60 minutes not receiving message, the meter will be considered OFFLINE and will re-join the network automatically. 2020 EASTRON EUROPE ALL RIGHTS RESERVED. www.eastroneurope.co - 25...
  • Page 28: 3.7 Confirm Mode

    Meter will send uplink again, upon to 3 times. From the Set-up menu, use buttons to select the Confirm mode option. Press for 3s, the current option will flash. to choose the option. 2020 EASTRON EUROPE ALL RIGHTS RESERVED. www.eastroneurope.co - 26...
  • Page 29: Specifications

    99999.99 kWh/ kVArh Mechanical Characteristics Weight 250g IP Degree of Protection IP51 (indoor) (IEC 60529) Dimensions (WxHxD) 100x36x63mm Mounting Din rail (DIN 43880) Material of meter case Self-extinguishing UL 94 V-0 Mechanical environment 2020 EASTRON EUROPE ALL RIGHTS RESERVED. www.eastroneurope.co - 27...
  • Page 30: Maintenance

    In the unlikely event of a repair being necessary, it is recommended that the unit be returned to the factory or nearest Eastron distributor. 2020 EASTRON EUROPE ALL RIGHTS RESERVED. www.eastroneurope.co...
  • Page 31: Installation

     This unit is not intended to function as part of a system providing the sole means of fault protection - good engineering practice dictates that any critical function be protected by at least two independent and diverse means. 2020 EASTRON EUROPE ALL RIGHTS RESERVED. www.eastroneurope.co - 29...
  • Page 32: Dimensions

     This product should only be operated with CT secondary connections Earthed.  If this equipment is used in a manner not specified by the manufacturer, protection provided by the equipment may be impaired. 7.3 Dimensions 7.4 Wiring Diagram 2020 EASTRON EUROPE ALL RIGHTS RESERVED. www.eastroneurope.co - 30...