Emerson Rosemount 485 Quick Start Manual

Emerson Rosemount 485 Quick Start Manual

Annubar flanged flo-tap assembly
Hide thumbs Also See for Rosemount 485:

Advertisement

Quick Links

Quick Start Guide
00825-0400-4809, Rev FC
July 2024
Rosemount
485 Annubar
Flanged
Flo-Tap Assembly

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Rosemount 485 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Emerson Rosemount 485

  • Page 1 Quick Start Guide 00825-0400-4809, Rev FC July 2024 Rosemount 485 Annubar Flanged ™ ™ Flo-Tap Assembly...
  • Page 2 Process leaks may result in serious injury or death. To avoid process leaks, only use gaskets designed to seal with the corresponding flange and o-rings to seal process connections. Flowing medium may cause the Rosemount 485 Annubar assembly to become hot and could result in burns.
  • Page 3: Table Of Contents

    July 2024 Quick Start Guide  WARNING Physical access Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end users’ equipment. This could be intentional or unintentional and needs to be protected against. Physical security is an important part of any security program and fundamental in protecting your system.
  • Page 4 Quick Start Guide July 2024 Emerson.com/Rosemount...
  • Page 5: Location And Orientation

    July 2024 Quick Start Guide 1  Location and orientation Correct orientation and straight run requirements must be met for accurate and repeatable flow measurements. Refer to Table 1-1 minimum pipe diameter distances from upstream disturbances. Note • Consult the factory for instructions regarding use in square or rectangular ducts.
  • Page 6 Downstream pipe Without With diameters straightening straightening vanes vanes Out of A’ C’ plane A plane A 3   4  4   N/A  N/A 4  N/A  4  30  N/A  4 Values are expressed as multiples of internal diameter, D Emerson.com/Rosemount...
  • Page 7 July 2024 Quick Start Guide Figure 1-1: Rosemount 485 Annubar Flanged Flo-Tap Assembly Exploded View A. Transmitter B. 2 x O-rings C. Temperature sensor connection housing D. Direct mount transmitter connection with valves E. Head plate F. Drive rods G. Mounting flange assembly H.
  • Page 8 Note Use an appropriate pipe sealing compound rated for the service temperature on all threaded connections. 1.1  Misalignment Rosemount 485 Annubar installation allows for a maximum misalignment of 3°. Figure 1-2: Misalignment 1.2  Horizontal orientation For proper venting and draining, the sensor should be located in the upper half of the pipe for air and gas applications.
  • Page 9 July 2024 Quick Start Guide Figure 1-3: Gas A. Recommended zone Figure 1-4: Liquid and Steam A. Recommended zone Note For steam applications with differential pressure readings between 0.75 and 2 inH O in horizontal pipes, it is recommended to install the primary element/flow meter mounting above the pipe.
  • Page 10 The maximum temperature for a direct mounted transmitter is 500 °F (260 °C). Figure 1-5: Steam A. Flow Figure 1-6: Liquid A. Flow Figure 1-7: Gas A. Flow Emerson.com/Rosemount...
  • Page 11: Weld Mounting Hardware

    July 2024 Quick Start Guide 2  Weld mounting hardware Note Rosemount-supplied mounting has an integral alignment built into the mounting hardware that assists in the correct drilling of the mounting hole. It also assists in the alignment of the sensor to the mounting hole for insertion.
  • Page 12 If outside of specified tolerance, make adjustments prior to making the finish weld. Figure 2-1: Alignment A. ODF B. Tack welds 3. To avoid serious burns, allow the mounting hardware to cool before continuing. Emerson.com/Rosemount...
  • Page 13: Install Isolation Valve

    July 2024 Quick Start Guide 3  Install isolation valve Procedure 1. Position the isolation valve onto the mounting flange. Ensure the valve stem is positioned so that when the Flo-Tap is installed, the insertion rods will straddle the pipe and the valve handle will be centered between the rods (see Figure 3-1).
  • Page 14: Mount Drilling Machine And Drill Hole

    4. Drill the hole into the pipe wall in accordance with the instructions provided by the drilling machine manufacturer (use Table 4-1 to select the proper drill bit for the sensor being used). 5. Retract the drill fully beyond the valve. Emerson.com/Rosemount...
  • Page 15: Remove Drilling Machine

    July 2024 Quick Start Guide 5  Remove drilling machine Procedure 1. Verify the drill has been retracted past the valve. 2. Close the isolation valve to isolate the process. 3. Bleed drilling machine pressure and remove. 4. Check isolation valve and mounting for leakage. Quick Start Guide...
  • Page 16: Mount The Rosemount Annubar Assembly

    4. Ensure the vent valves are closed before proceeding. 5. Open and close the isolation valve to pressurize the Rosemount 485 Sensor and identify any leak points in the installation. Use extreme caution if the flowing medium is steam or caustic.
  • Page 17 July 2024 Quick Start Guide Figure 6-1: Install Flo-Tap Assembly A. Support plate B. Isolation valve Quick Start Guide...
  • Page 18: Insert The Rosemount Annubar Sensor

    Place a finger above the packing gland while cranking. When movement stops, the sensor is in contact with the opposite side wall. c) Turn the handle an additional ¼ to ½ turn to secure the sensor. Emerson.com/Rosemount...
  • Page 19 July 2024 Quick Start Guide 3. Secure the drive by inserting the drive lock pin as shown in Figure 7-1. Note Do not place finger above packing gland for high temperature applications. Figure 7-1: Insert the Sensor Standard drive Gear drive (G)  ...
  • Page 20: Mount The Transmitter

    The following restrictions and recommendations apply to impulse piping location: Procedure 1. Impulse piping that runs horizontally must slope at least 1 in/ft. (83 mm/m). • Slope downward (toward the transmitter) for liquid and steam applications. Emerson.com/Rosemount...
  • Page 21 July 2024 Quick Start Guide • Slope upward (toward the transmitter) for gas applications. 2. Outdoor installations for liquid, saturated gas, or steam may require insulation and heat tracing to prevent freezing. 3. An instrument manifold is recommended for all installations. Manifolds allow an operator to equalize the pressures prior to zeroing and isolates the process fluid from the transmitter.
  • Page 22 Allows high and low side pressure to equalizer equalize Manifold vent Vents process fluid valve High pressure Low pressure 8.3  Recommended installations Gas service Secure the transmitter above the sensor to prevent condensible liquids from collecting in the impulse piping and the DP cell. Emerson.com/Rosemount...
  • Page 23 July 2024 Quick Start Guide Figure 8-2: Horizontal Gas Figure 8-3: Vertical Gas Steam and liquid service Secure the transmitter below the sensor to ensure that air will not be introduced into the impulse piping or the transmitter. Quick Start Guide...
  • Page 24 The transmitter should be located below the instrument connections of the Rosemount Annubar. Depending on the environmental conditions, it may be necessary to insulate the mounting hardware. Emerson.com/Rosemount...
  • Page 25 July 2024 Quick Start Guide Note Top mounting for steam applications is an appropriate mounting option in many cases. Consult Rosemount Customer Central for instructions, regarding steam on top mounting. Figure 8-6: Horizontal Top Mounting for Steams Quick Start Guide...
  • Page 26: Retracting The Rosemount Annubar Assembly

    Procedure 1. Remove the drive lock pin. 2. Rotate the crank counter-clockwise. If a power drill with an adapter is used, do not exceed 200 rpm. 3. Retract until the rod end nuts are against the gear box mechanism. Emerson.com/Rosemount...
  • Page 27: 10 Product Certifications

    Emerson.com/Rosemount. A hard copy may be obtained by contacting our local sales office. European Pressure Equipment Directive (PED) (97/23/EC) Rosemount 485 Annubar — Refer to EC Declaration of Conformity for conformity assessment Pressure Transmitter — See appropriate Pressure Transmitter Quick Start Guide 10.3 ...
  • Page 28 Quick Start Guide July 2024 10.4  Declaration of conformity Emerson.com/Rosemount...
  • Page 29 July 2024 Quick Start Guide Quick Start Guide...
  • Page 30 Quick Start Guide July 2024 Emerson.com/Rosemount...
  • Page 31 July 2024 Quick Start Guide Quick Start Guide...
  • Page 32 Quick Start Guide July 2024 Emerson.com/Rosemount...
  • Page 33 July 2024 Quick Start Guide 10.5  China RoHS Quick Start Guide...
  • Page 34 Quick Start Guide July 2024 Emerson.com/Rosemount...
  • Page 35 July 2024 Quick Start Guide Quick Start Guide...
  • Page 36 2024 Emerson. All rights reserved. Emerson Terms and Conditions of Sale are available upon request. The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount is a mark of one of the Emerson family of companies. All other marks are the property of their respective owners.