Parallel Operation
In order to connect Lifelynk inverters to operate in parallel, you need to set up the work mode configuration
for each the inverter. Basically, you have to set which inverter will be the master and which will be the slaves,
and then make the connections described in section "External Battery and Parallel Connections".
Basic Settings
Set Time
Set Date
Backlight
Work Mode
SOC/Voltage
Factory Reset
WARNING
To ensure the proper functioning of the parallel operation, it is important first to establish
the work mode for both the Master and Slave inverters and then make the necessary wir-
ing connections.
If you make the connection prior to changing the work mode, an F15 error will be dis-
played on the Fault Codes page. In the event of this error, please maintain the connection
and proceed to the settings to modify the work mode as presented above, and wait ap-
proximately 3-4 minutes. After that, the device should return to its normal working condi-
tion, with the error cleared.