Fanspeed_Command (Multistate Output Object Type) - HMS Networks Intesis IN485MIT001I000 User Manual

For mitsubishi electric residential, mr. slim, and city multi systems to bacnet ms/tp
Hide thumbs Also See for Intesis IN485MIT001I000:
Table of Contents

Advertisement

IN485MIT001I000 Gateway

7.3.10. FanSpeed_command (Multistate Output Object Type)

It sets the indoor unit's fan speed.
Property Identifier
Property Datatype
Object_Identifier
BACnetObjectIdentifier
Object_Name
CharacterString
Object_Type
BACnetObjectType
Present_Value
Unsigned
Description
CharacterString
Device_Type
CharacterString
Status_Flags
BACnetStatusFlags
Event_State
BACnetEventState
Reliability
BACnetReliability
Out_Of_Service
BOOLEAN
Number_Of_States
Unsigned
State_Text
BACnetArray[N] of CharacterString
Priority_Array
BACnetPriorityArray
Relinquish_Default
Unsigned
Time_Delay
Unsigned
Notification_Class
Unsigned
Feedback_Value
Unsigned
Event_Enable
BACnetEventTransitionBits
Acked_Transitions
BACnetEventTransitionBits
Notify_Type
BACnetNotifyType
Event_Time_Stamps
BACnetArray[N] of BACnetTimeStamp
Profile_Name
CharacterString
Table 8. Fan speed command
Present_Value
State_Text
1
Auto
2
Fan Speed 1(Silent)
3
Fan Speed 2
4
Fan Speed 3
5
Fan Speed 4
6
Fan Speed 5
1
The lowest fan speed in some Mitsubishi Electric indoor units is Fan speed 2.
Page 26 of 55
Value
(Multistate Output, 1)
FanSpeed_command
MULTISTATE_OUTPUT (14)
1 .. 6
-
-
{FALSE, FALSE, FALSE, FALSE}
STATE_NORMAL (0)
NO_FAULT_DETECTED (0)
FALSE
6
Check the Fan speed command table below
BACnetPriorityArray
1
-
-
-
-
-
-
-
-
1
Objects and Properties
ASHRAE
Gateway
R
R
R
R
R
R
R
W
O
-
O
-
R
R
R
R
O
R
R
R
R
R
O
R
R
R
R
R
O
-
O
-
O
-
O
-
O
-
O
-
O
-
O
-
USER MANUAL Version 1.2.6

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Intesis IN485MIT001I000 and is the answer not in the manual?

Subscribe to Our Youtube Channel

Table of Contents